ACHR News
search
Ask ACHR NEWS AI
cart
facebook twitter instagram linkedin youtube
  • Sign In
  • Subscribe
  • Sign Out
  • My Account
ACHR News
  • NEWS
    • Breaking News
    • New HVAC Products
    • Featured Products
    • Manufacturer Reports
    • HVAC Data
    • Legislation
    • ACHR NEWS Centennial
  • RESIDENTIAL
    • Air Conditioners
    • Furnaces
    • Residential Heat Pumps
    • Ductless
    • Residential IAQ
    • Testing, Monitoring, Tools
    • Components & Accessories
  • COMMERCIAL
    • Air Handlers
    • Rooftop Units
    • Chillers and Cooling Towers
    • Commercial Heat Pumps
    • Boilers and Hydronics
    • VRF/Ductless
    • Commercial IAQ
  • REFRIGERATION
    • Refrigerants
    • Refrigerant Regulations
    • Leak Management
  • CONTRACTOR PRO
    • Geothermal
    • Homeowner Study
    • VRF and VRV Ductless
    • Unitary Trends
  • EDUCATION
    • Training and Education
    • Business Management
    • Service and Maintenance
    • Continuing Education
    • Market Research >
      • HVAC Brand Awareness Report
      • VRV, VRF, VRVZ Report
      • Unitary Trends Report
      • Water Heat Professionals Report
    • Webinars
    • Sponsor Insights
    • eProducts Info
    • White Papers
  • EVENTS
    • HVAC Contractor Forum
    • Industry Events and Webinars
  • MEDIA
    • Videos
    • AHR Expo 2025 Videos
    • Podcasts >
      • ACHR News Podcast
      • HARDI Podcasts
      • AHR Expo Podcasts
      • ACCA Podcasts
    • Interactive Spotlights
    • Quizzes
    • eBooks
    • HVAC Talkback
  • HVAC GROUP
    • ACHR NEWS >
      • Current Issue
      • Digital Edition
      • Subscribe
    • Distribution Trends
    • SNIPS NEWS >
      • Join SNIPS NEWS
    • Engineered Systems News >
      • Join ES News
    • HVACR Directory
    • Contests
    • Newsletters
    • Contact
    • Advertise
    • My Account
NewsService and MaintenanceRefrigerationComponents & AccessoriesRefrigerantsValves & Pumps

Determining the Cause of a Restricted Liquid Line

Restrictions can starve refrigeration components of refrigerant, resulting in system problems

By John Tomczyk
Evaporator Installation.
RESTRICTED LINE: A technician prepares to install an evaporator for a refrigeration system. If there is a restriction in the liquid line, the evaporator could be starved of refrigerant. (Courtesy of Defense Visual Information Distribution Service)
June 28, 2022

The liquid line in a refrigeration system begins at the outlet of the receiver and includes the filter drier, sight glass, metering device, and any other components located between the receiver and TXV. The filter drier is a very likely component to become restricted from moisture and/or debris accumulation because it is designed to absorb and store debris and moisture. A restricted filter drier will give the same symptoms as a restricted TXV since it, too, is in the liquid line.

READ MORE ABOUT

• TXV

• Troubleshooting

• Service & Maintenance

There are multiple ways a TXV can become restricted. Remember that a TXV becoming partially restricted will have the same symptoms as a restriction anywhere in the liquid line. The following are the many ways the metering device (TXV) can become restricted:

  • Too much oil in the system;
  • TXV adjusted too far closed;
  • Plugged inlet screen on TXV;
  • Sludge from the byproducts of a compressor burnout;
  • Partial TXV orifice freeze-up from excessive moisture in the system;
  • Foreign material in orifice of the TXV;
  • Oil-logged TXV from refrigerant flooding the compressor;
  • Restricted liquid line solder joint;
  • Kinked liquid line;
  • Receiver outlet valve (King valve) partially closed off;
  • Wax build-up in TXV from wrong oil in system; and/or
  • Manufacturer's defect in the valve.

 

Restriction Consequences

Liquid line restrictions cause the evaporator, compressor, and condenser to be starved of refrigerant. The mass flow rate of refrigerant through the system will decrease, and liquid refrigerant will accumulate in the bottom of the condenser and receiver, causing condenser subcooling readings to be normal-to-high. The system will have symptoms of low suction pressures, high evaporator and compressor superheats, normal-to-high condenser subcooling, low compressor amp draws, and low head pressures.

Here is a service checklist for a restricted liquid line after the receiver and before the filter drier:

Measured values
Compressor discharge temperature 215°F
Condenser outlet temperature 70°F
Evaporator outlet temperature 30°F
Compressor in temperature 60°F
Ambient temperature 75°F
Box temperature 30°F
Compressor volts 230
Compressor amps Low
Low-side (evaporating) pressure 1.8 psig (-10°F)
High-side (condensing) pressure 95 psig (85°F)
Calculated values
Condenser split 10°F
Condenser subcooling 15°F
Evaporator superheat 40°F
Compressor superheat 70°F

Many technicians believe that when any part of the systems high side is restricted or plugged, head pressures will elevate. This is simply not the case, especially on a TXV/receiver system. A restricted liquid line will starve the evaporator of refrigerant, causing low evaporator pressures. The compressor and condenser will also be starved, since they are in series with one another, which will cause both condenser and evaporator pressures to be lowered.

 

Analysis

A liquid line restriction may exhibit the following symptoms:

  • Higher-than-normal discharge temperature;
  • High superheats;
  • Low evaporator pressure;
  • Low condensing pressure;
  • Normal condenser subcooling;
  • Low condenser splits;
  • Local cool spot or frost after the restriction;
  • Bubbles may appear in the sight glass if restriction is before the sight glass;
  • Low amp draw; and/or
  • Short-cycle the low pressure control (LPC).

Higher-than-normal discharge temperature. High discharge temperatures are caused from high compressor superheats, as a result of the starved evaporator. High compression ratios from the low evaporator pressure will cause high heat of compressions, thus high discharge temperatures.

High superheats. Both evaporator and compressor superheats will be high as a result of the TXV, evaporator, and compressor being starved of refrigerant from the liquid line restriction. Most of the refrigerant will be in the receiver, with some in the condenser.

Low evaporator pressure. The low evaporator pressure is caused from the compressor being starved of refrigerant. The compressor will try to draw refrigerant from the evaporator through the suction line, but the liquid line restriction will prevent refrigerant from entering the evaporator. This will cause the compressor to put the evaporator in a low-pressure situation.

Low condensing pressure. Since both the evaporator and compressor are starved of refrigerant, the condenser will be, too. Reduced refrigerant to the evaporator will cause a reduced heat load to be delivered to the condenser, which in turn will not have to elevate its temperature and pressure to reject heat.

Looking for quick answers on air conditioning, heating and refrigeration topics? Try Ask ACHR NEWS, our new smart AI search tool. Ask ACHR NEWS →

Normal condenser subcooling. Since the condenser is being starved, it is not condensing much vapor to liquid. All of the liquid in the condenser will probably sit there for a while and subcool because of the low refrigerant flow caused from the restriction. The receiver will have a reduced flow in and out of it, and most of the refrigerant will be in the receiver with some in the condenser. If the receiver is in a hot ambient, subcooling may be lost as refrigerant sits in the receiver. This is why some commercial systems have receiver bypasses for certain situations. Receiver bypasses are a liquid line solenoid valve controlled by a thermostat, which will bypass liquid around the receiver to the liquid line.

Low condenser splits. Because the condenser is being somewhat starved, there is not much heat to reject, which will cause low condenser splits.

Local cold spot or frost where restriction occurs. Liquid refrigerant flashing to vapor might occur at the restriction if the restriction is severe enough. Simply running your hand along the liquid line and on the filter drier may find a local cold spot. A thermistor on the liquid line about 12 inches before the entrance of the TXV should not be colder than the ambient that surrounds it. If it is, there is a sure restriction somewhere upstream.

There are many times when a filter drier or line may be partially plugged and the technician cannot feel a temperature difference. Because of this, many filter driers restrictions go unchecked, but the use of a sight glass after the filter drier will assist the technician with this issue, as well as with system charging. A moisture-indicating sight glass will alert the technician if the system is contaminated with moisture by changing colors.

Bubbles in sight glass. With a restriction in the liquid line before the sight glass, bubbles are sure to occur in the sight glass. Many technicians believe that a bubbling sight glass means nothing but an undercharge of refrigerant, but this is not true. On startup of some refrigeration systems when there is a large load on the system, bubbling and flashing could occur in the sight glass downstream of the receiver. This bubbling is caused from a pressure drop at the entrance of the outlet tube of the receiver.

Bubbling could also occur during rapid increases in loads. The TXV could be opened wide during an increase in load and some flashing could occur even though the receiver has sufficient liquid. Also, sudden changes in head pressure control systems, which may dump hot gas into the receiver to build up head pressure, often will bubble a sight glass even though there is sufficient liquid in the receiver to form a seal on the receiver's dip tube outlet. A sight glass on the receiver prevents technicians from overcharging in this case.

A sight glass on the liquid line before the TXV would also help let the technician know if any liquid flashing is occurring before the TXV. This flashing could be from loss of subcooling or too much static and/or friction pressure drop in the liquid line before it reaches the TXV.

There is a big difference between a bubbling sight glass and a low flow rate sight glass. If bubbles are entrained in the liquid, this is sign of a pressure drop causing liquid flashing, or an undercharge, or refrigerant causing vapor and liquid to exit the receiver because of no subcooling. Remember, the condenser subcooling will be low if an undercharge is causing the bubbling of the sight glass. Otherwise, the bubbling sight glass could mean a restricted liquid line, restricted filter drier, loss of receiver or liquid line subcooling from hot ambient, or static and friction losses in the liquid line are too great.

On the other hand, a low flow rate sight glass is an indication that the system is about ready to cycle off, because the box temperature has pulled down to a low enough temperature. It is at these times that the system is at its lowest heat loads and the refrigerant flow rate through the system will be the lowest. The sight glass may be only one-quarter to one-half full with no entrained bubbles. This situation is especially true with horizontal liquid lines. Do not add refrigerant in this situation, because you will overcharge the system, which will be noticed at higher heat loads. The low heat loads cause the system to be at its lowest suction pressure, so the density of refrigerant vapors entering the compressor will be lowest. Because of the lowest evaporator pressures, the compression ratio will be high, causing low volumetric efficiencies and thus low refrigerant flow rates. There is usually plenty of subcooling in the condenser, but the sight glass will only be partially filled.

A sight glass after the filter drier is a good method to tell if the drier is starting to plug, because of the refrigerant flash from the added pressure drop in the restricted drier.

Low amp draw. Because the compressor is being starved of refrigerant from the restriction in the liquid line, it will not have to work as hard in compressing what vapors do pass through it. The low density of the vapors from the low evaporator pressure will require less work from the compressor, requiring a low amp draw.

Short cycle the low pressure control. The LPC will cycle the compressor off and on from the low evaporator (suction) pressures. Once off, refrigerant will slowly enter the evaporator and cycle the compressor back on. This on and off of the compressor will continue until the problem is fixed.

Given the many different reasons why a liquid line may become restricted, it is incumbent upon the technician to thoroughly troubleshoot the system to find the root cause and then fix it.

KEYWORDS: evaporators FROSTlines maintenance for HVACR troubleshooting and HVACR TXV (thermostatic expansion valve)

Share This Story

Looking for a reprint of this article?
From high-res PDFs to custom plaques, order your copy today!

 

John Tomczyk is HVACR professor emeritus, Ferris State University, Big Rapids, Michigan, and coauthor of Refrigeration & Air Conditioning Technology, published by Cengage Learning. Contact him at tomczykjohn@gmail.com.

Recommended Content

JOIN TODAY
To unlock your recommendations.

Already have an account? Sign In

  • HVAC-enrollment

    The Trades Are Back: HVACR Programs See Nearly 30% Enrollment Spike

    A new wave of future technicians is entering the pipeline.  
    Training and Education
    By: Matt Jachman
  • 2025 Top 40 Under 40

    2025 Top 40 Under 40 HVACR Professionals List

    The 11th annual Top 40 Under 40 list highlights those...
    HVAC Light Commercial Market
    By: Hannah Belloli-Oster
  • LG Ductless Mini-Split Systems

    The 9 Types of Heat Pumps

    As the U.S. moves toward electrification, heat pumps are...
    HVAC Residential Market
    By: Joanna R. Turpin
Subscription Center
  • Create an Account
  • Start a Subscription
  • Manage My Account
  • Sign Up for Newsletters
  • Visit Customer Service
  • Update Preferences

More Videos

Sponsored Content

Sponsored Content is a special paid section where industry companies provide high quality, objective, non-commercial content around topics of interest to The News audience. All Sponsored Content is supplied by the advertising company and any opinions expressed in this article are those of the author and not necessarily reflect the views of The News or its parent company, BNP Media. Interested in participating in our Sponsored Content section? Contact your local rep!

close
  • Piggy Bank
    Sponsored byWatercress Financial

    Energy Prices, Inflation, and HVAC: What Today’s Homeowners Care About

  • Refrigerated Food
    Sponsored bySolstice Advanced Materials

    R-455A Refrigeration: A Cold Storage Solution for the Future

  • Airex Rooftop Units
    Sponsored byAirex Manufacturing Inc

    Consolidating Roof Penetrations: A Growing Trend in Multifamily HVAC Design

Popular Stories

HVAC-Price-Increase-graphic

HVAC Price Increase List: June 2026

Trump-Section-232.jpg

Trump Reduces Section 232 Tariffs on HVAC Equipment to 15%

Refrigerants-and-gauge.jpg

HVAC Industry Warns of Counterfeit Refrigerants Entering U.S. Supply Chain

Midea-training.jpg

HVAC Workforce Crisis Expands Beyond Technicians to Instructor Shortages

U.S. Supreme Court building

95% Furnace Efficiency Rule to Get New Hearing

View The ACHR NEWS
Centennial Anniversary Timeline

The ACHR News Timeline Chart
Submit a Letter
Submit a letter to our editors.

Events

November 6, 2025

Next-Gen Data Center Cooling: HVAC Innovation and Real-World Solutions

On Demand As AI workloads and high-density computing push traditional cooling methods to their limits, the data center industry is accelerating the adoption of next-generation HVAC technologies.

June 17, 2026

Decarbonization Without Disruption

This webinar will explore practical HVAC decarbonization strategies that minimize disruption while maximizing long-term performance and ROI.

View All Submit An Event

Poll

Summer Staff

Are you fully staffed for the summer season?
View Results Poll Archive

Products

BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

See More Products
Decarbonization Without Disruption - Free Webinar - 6/17/2026

Related Articles

  • The Professor: Systematic Troubleshooting of a Restricted Liquid Line

    See More
  • Refrigerant Cylinders

    Don’t Mistake a Restricted Liquid Line for an Overcharge

    See More
  • Diagnosing A Restricted Liquid Line Can Be Tricky

    See More

Related Products

See More Products
  • air came to a stop.jpg

    The Air Came to a Stop

See More Products

Events

View AllSubmit An Event
  • May 21, 2026

    The A2L Genie is Out of the Refrigerant Canister – What Now?

    On Demand Join this webinar to learn about key updates to refrigerant regulations. We will cover practical installation and servicing content gathered from thousands of our interactions with contractors across the US and Canada.
View AllSubmit An Event

Related Directories

  • MA-LINE div. of Monti & Associates Inc.

    The MA-LINE provides access to specialized products for wholesalers in the HVAC/R industry. The MA-LINE prides itself on maintaining the highest level of customer service.
×

Sign Up. Stay Informed.

The #1 trusted source for the HVACR industry since 1926

SUBSCRIBE
  • RESOURCES
    • Advertise
    • Contact Us
    • Advisory Board
    • Classifieds
    • Submit a Letter
    • Directories
    • Store
  • ACCOUNT CENTER
    • Create an Account
    • Start a Subscription
    • Manage My Account
    • Sign Up for Newsletters
    • Visit Customer Service
    • Update Preferences
  • SERVICES
    • Marketing Services
    • Reprints
    • Market Research
    • List Rental
    • Survey/Respondent Access
  • STAY CONNECTED
    • LinkedIn
    • Facebook
    • Instagram
    • YouTube
    • X (Twitter)
  • PRIVACY
    • PRIVACY POLICY
    • TERMS & CONDITIONS
    • DO NOT SELL MY PERSONAL INFORMATION
    • PRIVACY REQUEST
    • ACCESSIBILITY

Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

Design, CMS, Hosting & Web Development :: ePublishing