ACHR News
search
Ask ACHR NEWS AI
cart
facebook twitter instagram linkedin youtube
  • Sign In
  • Subscribe
  • Sign Out
  • My Account
ACHR News
  • NEWS
    • Breaking News
    • New HVAC Products
    • Featured Products
    • Manufacturer Reports
    • HVAC Data
    • Legislation
    • ACHR NEWS Centennial
  • RESIDENTIAL
    • Air Conditioners
    • Furnaces
    • Residential Heat Pumps
    • Ductless
    • Residential IAQ
    • Testing, Monitoring, Tools
    • Components & Accessories
  • COMMERCIAL
    • Air Handlers
    • Rooftop Units
    • Chillers and Cooling Towers
    • Commercial Heat Pumps
    • Boilers and Hydronics
    • VRF/Ductless
    • Commercial IAQ
  • REFRIGERATION
    • Refrigerants
    • Refrigerant Regulations
    • Leak Management
  • CONTRACTOR PRO
    • Geothermal
    • Homeowner Study
    • VRF and VRV Ductless
    • Unitary Trends
  • EDUCATION
    • Training and Education
    • Business Management
    • Service and Maintenance
    • Continuing Education
    • Market Research >
      • HVAC Brand Awareness Report
      • VRV, VRF, VRVZ Report
      • Unitary Trends Report
      • Water Heat Professionals Report
    • Webinars
    • Sponsor Insights
    • eProducts Info
    • White Papers
  • EVENTS
    • HVAC Contractor Forum
    • Industry Events and Webinars
  • MEDIA
    • Videos
    • AHR Expo 2025 Videos
    • Podcasts >
      • ACHR News Podcast
      • HARDI Podcasts
      • AHR Expo Podcasts
      • ACCA Podcasts
    • Interactive Spotlights
    • Quizzes
    • eBooks
    • HVAC Talkback
  • HVAC GROUP
    • ACHR NEWS >
      • Current Issue
      • Digital Edition
      • Subscribe
    • Distribution Trends
    • SNIPS NEWS >
      • Join SNIPS NEWS
    • Engineered Systems News >
      • Join ES News
    • HVACR Directory
    • Contests
    • Newsletters
    • Contact
    • Advertise
    • My Account

Fundamentals: It Was a Fine Yesterday

August 29, 2001
The problem: No air conditioning.

The apprentice: A second-year mechanic.

The technician: A 15-year veteran.

The diagnosis and repair sequence:

A homeowner advises them that the system was working fine yesterday.

“I change the filter every month,” he says. “I don’t know what could be wrong with the unit.”

The team goes to the unit and finds the following during their visual inspection:

  • The condenser fan is running, but they can’t hear the compressor operating.
  • The unit is a 220-volt, single-phase, 3-ton system.
  • The condenser fins are clean and unbent.


  • Technician: “Do you think we should check the power supply?”

    Apprentice: “No.”

    Technician: “Good. But tell me, why not?”

    Apprentice: “Well, the condenser fan motor is still operating. I think that means we still have power to the unit.”

    Technician: “OK. Let’s shut down the unit so we can open it up. What should we check when we get the unit open?”

    Looking for quick answers on air conditioning, heating and refrigeration topics? Try Ask ACHR NEWS, our new smart AI search tool. Ask ACHR NEWS →

    a) The operating head pressure.

    b) The operating suction pressure.

    c) The operating oil pressure.

    d) The system idle pressure.

    ANSWER:

    d) The system idle pressure.



    b>Apprentice: “I can’t check the operating pressures because we will have the unit shut down. And I think that we should check the system idle pressure to make sure the system isn’t discharged.”

    After properly connecting the service gauges, the team determines that the system has pressure. The veteran asks the apprentice to momentarily touch the compressor. The apprentice tells the veteran that the body seems to be at ambient temperature.

    Technician: “What does that tell us about the compressor?”

    a) It is normal for the compressor body to feel about the same as the ambient temp.

    b) It is normal because of the liquid refrigerant that comes back to keep the motor cool.

    c) It is not normal because the compressor should be warm due to operation.

    d) It is not normal because superheated refrigerant should make it hot.

    ANSWER:

    c) It is not normal because the compressor should be warm due to operation.

    b>Apprentice: “I know that we have voltage to the system because the condenser fan motor operates. And I know that the system is calling for cooling because on this type of equipment the condenser fan motor comes on at the same time as the compressor through the contactor.”

    Technician: “Tell me, which one of the following is the most likely cause of what we are sensing?”

    a) Nothing. Power is properly applied.

    b) The compressor is broken up.

    c) The compressor is off on internal overload.

    d) The compressor capacitor is defective.

    ANSWER:

    c) The compressor is off on internal overload.

    Technician: “How are you going to check the internal overload?”

    a) Attach my voltmeter to the wires connected to the contactor and check the voltage.

    b) Attach my amp meter to the wires connected to the contactor and check the amperage.

    c) Attach my ohmmeter to the wires after disconnecting them from the contactor and check motor resistance.

    d) Attach my wattmeter to the wires after disconnecting them from the contactor and check motor wattage.

    ANSWER:

    c) Attach my ohmeter to the wires after disconnecting them from the contactor and check motor resistance.

    Technician: “Why are you going to disconnect the wires from the contactor?”

    a) To make sure that only the compressor motor windings are checked.

    b) To make sure that the fan motor amperage doesn’t affect the readings.

    c) To make sure that the contactor coil voltage doesn’t seep into the lines.

    d) To make sure that the system has a good ground.

    ANSWER:

    a) To make sure that only the compressor motor windings are checked.

    Technician: “Now that the test is done, tell me what your findings were and what you think they indicate.”

    Apprentice: “The compressor motor windings test out properly with the normal differences between the start and run windings. The internal overload is completing the circuit. I also checked for shorts to ground and didn’t find any. I’m lost.”

    Technician: “We’re going to have to check the system with the voltage turned on. We have to be extremely careful, as the condenser fan will be running and there will be live voltage at the terminals we have to check.”

    Technician: “OK, with the power back on and the system calling for cooling, we are going to check the voltage at the contactor terminals. What should the voltage be between Terminals T1 and T2?”

    a) 480 volts

    b) 240 volts

    c) 120 volts

    d) 24 volts

    ANSWER:

    b) 240 volts

    Technician: “It seems that we have the proper voltage at the terminals of the contactor. What might we examine next?”

    a) The voltage at the compressor terminals.

    b) The amperage draw of the compressor.

    c) The contacts of the contactor.

    d) The holding coil inrush current.

    ANSWER:

    c) The contacts of the contactor.

    Technician: “We could check the compressor terminals, but for safety’s sake, we will check the contactor’s contacts first. What do you think we’ll find?”

    a) Perfectly flat contacts

    b) Slightly convex contacts

    c) Slightly concave contacts

    d) Pitted contacts

    ANSWER:

    d) Pitted contacts.

    Technician: “Smart call. We had voltage by the meter yet the compressor wouldn’t run.”

    Technician: “Can you tell me why the compressor wouldn’t run?”

    a) The pits on the contact surfaces, which don’t fit together, will let enough voltage pass for the meter but not for the compressor motor to operate.

    b) The pits groove together perfectly, creating a reduced current flow.

    c) The pitted scorching creates an insulating effect that increases amperage requirements.

    d) The pitting increases the contactor surface and therefore more voltage is needed to run the compressor.

    ANSWER:

    a) The pits on the contact surfaces, which don't fit together, will let enough voltage pass for the meter but not for the compressor motor to operate.



    Technician: “Well, it looks like we have determined the problem. Let’s tell the customer and get permission to change the contactor. Then we’ll do a complete operational check on the system to make sure there is nothing else that may have caused the contactor to become pitted.”

    Publication date: 08/27/2001

    Share This Story

    Recent Comments

    Very good...

    Commercial ITC & the Limited-use property Doc allowing 3rd party leasing of commercial geo systems

    Energy Star and trust

    HVACR TECHNICIAN

    Opp

    Blog Roll

    Editors Blog

    Guest Blog

    Opinions

    Subscription Center
    • Create an Account
    • Start a Subscription
    • Manage My Account
    • Sign Up for Newsletters
    • Visit Customer Service
    • Update Preferences

    More Videos

    Sponsored Content

    Sponsored Content is a special paid section where industry companies provide high quality, objective, non-commercial content around topics of interest to The News audience. All Sponsored Content is supplied by the advertising company and any opinions expressed in this article are those of the author and not necessarily reflect the views of The News or its parent company, BNP Media. Interested in participating in our Sponsored Content section? Contact your local rep!

    close
    • Piggy Bank
      Sponsored byWatercress Financial

      Energy Prices, Inflation, and HVAC: What Today’s Homeowners Care About

    • Refrigerated Food
      Sponsored bySolstice Advanced Materials

      R-455A Refrigeration: A Cold Storage Solution for the Future

    • Airex Rooftop Units
      Sponsored byAirex Manufacturing Inc

      Consolidating Roof Penetrations: A Growing Trend in Multifamily HVAC Design

    Popular Stories

    HVAC-Price-Increase-graphic

    HVAC Price Increase List: June 2026

    Trump-Section-232.jpg

    Trump Reduces Section 232 Tariffs on HVAC Equipment to 15%

    R410A-Refrigerant-Cylinder.jpg

    Refrigerant Recovery is a Revenue Opportunity

    Heat-pump-cutaway.jpg

    PFAS Rules and A2L Building Codes Continue to Evolve

    Midea-training.jpg

    HVAC Workforce Crisis Expands Beyond Technicians to Instructor Shortages

    View The ACHR NEWS
    Centennial Anniversary Timeline

    The ACHR News Timeline Chart
    Submit a Letter
    Submit a letter to our editors.

    Events

    November 6, 2025

    Next-Gen Data Center Cooling: HVAC Innovation and Real-World Solutions

    On Demand As AI workloads and high-density computing push traditional cooling methods to their limits, the data center industry is accelerating the adoption of next-generation HVAC technologies.

    June 17, 2026

    Decarbonization Without Disruption

    This webinar will explore practical HVAC decarbonization strategies that minimize disruption while maximizing long-term performance and ROI.

    View All Submit An Event

    Poll

    Summer Staff

    Are you fully staffed for the summer season?
    View Results Poll Archive

    Products

    BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

    BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

    See More Products
    Decarbonization Without Disruption - Free Webinar - 6/17/2026
    ×

    Sign Up. Stay Informed.

    The #1 trusted source for the HVACR industry since 1926

    SUBSCRIBE
    • RESOURCES
      • Advertise
      • Contact Us
      • Advisory Board
      • Classifieds
      • Submit a Letter
      • Directories
      • Store
    • ACCOUNT CENTER
      • Create an Account
      • Start a Subscription
      • Manage My Account
      • Sign Up for Newsletters
      • Visit Customer Service
      • Update Preferences
    • SERVICES
      • Marketing Services
      • Reprints
      • Market Research
      • List Rental
      • Survey/Respondent Access
    • STAY CONNECTED
      • LinkedIn
      • Facebook
      • Instagram
      • YouTube
      • X (Twitter)
    • PRIVACY
      • PRIVACY POLICY
      • TERMS & CONDITIONS
      • DO NOT SELL MY PERSONAL INFORMATION
      • PRIVACY REQUEST
      • ACCESSIBILITY

    Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

    Design, CMS, Hosting & Web Development :: ePublishing