ACHR News
search
Ask ACHR NEWS AI
cart
facebook twitter instagram linkedin youtube
  • Sign In
  • Subscribe
  • Sign Out
  • My Account
ACHR News
  • NEWS
    • Breaking News
    • New HVAC Products
    • Featured Products
    • Manufacturer Reports
    • HVAC Data
    • Legislation
    • ACHR NEWS Centennial
  • RESIDENTIAL
    • Air Conditioners
    • Furnaces
    • Residential Heat Pumps
    • Ductless
    • Residential IAQ
    • Testing, Monitoring, Tools
    • Components & Accessories
  • COMMERCIAL
    • Air Handlers
    • Rooftop Units
    • Chillers and Cooling Towers
    • Commercial Heat Pumps
    • Boilers and Hydronics
    • VRF/Ductless
    • Commercial IAQ
  • REFRIGERATION
    • Refrigerants
    • Refrigerant Regulations
    • Leak Management
  • CONTRACTOR PRO
    • Geothermal
    • Homeowner Study
    • VRF and VRV Ductless
    • Unitary Trends
  • EDUCATION
    • Training and Education
    • Business Management
    • Service and Maintenance
    • Continuing Education
    • Market Research >
      • HVAC Brand Awareness Report
      • VRV, VRF, VRVZ Report
      • Unitary Trends Report
      • Water Heat Professionals Report
    • Webinars
    • Sponsor Insights
    • eProducts Info
    • White Papers
  • EVENTS
    • HVAC Contractor Forum
    • Industry Events and Webinars
  • MEDIA
    • Videos
    • AHR Expo 2025 Videos
    • Podcasts >
      • ACHR News Podcast
      • HARDI Podcasts
      • AHR Expo Podcasts
      • ACCA Podcasts
    • Interactive Spotlights
    • Quizzes
    • eBooks
    • HVAC Talkback
  • HVAC GROUP
    • ACHR NEWS >
      • Current Issue
      • Digital Edition
      • Subscribe
    • Distribution Trends
    • SNIPS NEWS >
      • Join SNIPS NEWS
    • Engineered Systems News >
      • Join ES News
    • HVACR Directory
    • Contests
    • Newsletters
    • Contact
    • Advertise
    • My Account

Supplement to ‘Ventilation and Heat Exchanger Testing'

April 17, 2006
Typical readings for furnace and boiler burners and heat exchangers, plus measurement procedures.

ATMOSPHERIC DRAFT GAS-FIRED BURNERS

  • Efficiency: 75 to 80 percent

  • Oxygen: 7 to 9 percent

  • CO2: 6.5 to 8 percent

  • Stack temperature: 325° to 500°F

  • Draft: -0.02 to -0.04 inch wc

  • CO: <100 ppm (undiluted)

    Always follow manufacturer's specifications.

    Atmospheric draft appliances tend to have higher excess air readings and higher stack temperatures due to less-complex heat exchanger designs. Remember, there is a positive pressure in the heat exchanger and a negative pressure in the vent connector and stack. A heat exchanger crack in this style furnace will show as an increase in excess air readings when the blower starts and a decrease when the blower stops.

    If the primary air shutters or gas pressure are adjusted, it is imperative that a combustion analysis is performed, as operating characteristics of the furnace have changed. For proper combustion and venting, approximately 30 cubic feet of air is required per 1,000 Btuh; this means a 100,000-Btuh furnace would require 300 cubic feet of ventilation hour ever hour of operation.

    Measurement procedure:
    1. Connect flue gas sampling probe assembly to analyzer per manufacturer's instructions.

    2. Verify condensate trap plug is properly seated in combustion analyzer water trap and thermocouple is not touching side of probe assembly.

    3. In uncontaminated air (outdoor) start the analyzer and allow unit to complete zeroing process. (Never allow the analyzer to zero in the stack (unless manufacturer's design allows this, e.g. Testo 330-2.)

    4. Measurements must be made in each cell of the heat exchanger. If needed a 5/16-inch hole can be made in the front of the draft diverter to allow measurement.

    5. Allow furnace to operate for ten minutes or until stack temperature stabilizes. The furnace must establish draft (measured in the flue pipe) with 10 minutes of operation.

    6. Measure and print combustion results for each cell in the furnace.

    7. Compare results for each cell.

    DRAFT-INDUCED GAS-FIRED BURNERS

  • Efficiency: 80 to 82 percent

  • Oxygen: 7 to 9 percent

  • CO2: 6.5 to 8 percent

  • Stack temp: 325° to 400°F

  • Draft: -0.02 to -0.004 inch wc

  • CO: <100 ppm (undiluted)

    Always follow manufacturer's specifications.

    Draft-induced appliances have similar operating characteristics to atmospheric draft appliances with the exception of lower flue gas temperatures. The stack draft operates identically, but the heat exchanger pressure is now negative. The function of the draft inducer is to pull combustion byproducts through the heat exchanger, not to create a positive pressure in the vent. If the vent pressure is positive the flue pipe is clogged. These furnaces characteristically do not leak flue gas into the house when heat exchanger failure occurs due to the negative heat exchanger pressure. Combustion ventilation air requirements are reduced to 15 cubic feet/1000 Btuh. No dilution air is required for venting.

    Measurement procedure:
    1. Connect flue gas sampling probe assembly to analyzer per manufacturer's instructions.

    2. Verify condensate trap plug is properly seated in combustion analyzer water trap and thermocouple is not touching side of probe assembly.

    3. In uncontaminated air (outdoor) start the analyzer and allow unit to complete zeroing process (never allow the analyzer to zero in the stack (unless manufacturer's design allows this, e.g. Testo 330-2).

    4. Measurements must be made in the vent connector or stack.

    5. Allow furnace to operate for 10 minutes or until stack temperature stabilizes. The furnace must establish draft (measured in the flue pipe) with ten minutes of operation. Verify flue gasses are not spilling from the draft hood of the hot water tank if common vented!

    6. Measure and print combustion results prior to and after making any adjustment to the furnace.

    Note: If the furnace is multistage or modulating, each stage must be checked independently to ensure safe operation through the entire operating range.

    DRAFT-SEALED COMBUSTION INDUCED GAS-FIRED BURNERS (90 PLUS)

  • Efficiency: 88 to 92 percent

  • Oxygen: 5 to 7 percent

  • CO2: 7 to 8.5 percent

  • Stack temp: Less than 125°F

  • Draft: 0.02 to 0.08 inch wc

  • CO: <100 ppm (undiluted)

    Always follow manufacturer's specifications.

    High-efficiency appliances are considerably different in operation. Their heat exchanger pressure is negative, and vent pressure becomes positive. Flue gas temperature drops below 125°. Often outdoor air is used for combustion, allowing these furnaces to operate without indoor air ventilation requirements. If used with a two-pipe configuration, the combustion air temperature must be referenced to get an accurate combustion test result. All burner shields and doors must be in place.

    The high efficiency of these appliances is achieved by removing the latent (hidden) heat from the flue gasses by condensing the water from the byproducts of combustion. This additional removal of heat through a secondary heat exchanger lowers the flue gas temperature below 125°. High heat extractions, in conjunction with careful control of combustion air, allow these furnaces to operate with high combustion efficiencies and very high thermal efficiencies. Combustion air required by these furnaces is reduced to 10 cubic feet/1,000 Btuh. Provisions for condensate removal must be made for condensing-type furnaces and boilers.

    Measurement procedure:
    1. Connect the flue gas sampling probe assembly to the analyzer per the manufacturer's instructions.

    2. Verify that the condensate trap plug is properly seated in the combustion analyzer water trap, and that the thermocouple is not touching the side of probe assembly.

    3. In uncontaminated air (outdoor), start the analyzer and allow the unit to complete the zeroing process. Never allow the analyzer to zero in the stack (unless the manufacturer's design allows this, e.g. Testo 330-2).

    4. Measurements must be made in the PVC flue pipe, and temperature of combustion air must be referenced in the intake pipe with an auxiliary temperature probe to get accurate combustion efficiency results.

    5. Allow furnace to operate for ten minutes or until stack temperature stabilizes.

    6. Measure and print combustion results prior to and after making any adjustment to the furnace.

    Note: If the furnace is multistage or modulating, each stage must be checked independently to ensure safe operation through the entire operating range.

    GAS-FIRED POWER BURNERS

  • Oxygen: 3 to 6 percent

  • CO2: 8.5 to 11 percent

  • Stack temp (gross): 320° to 570°F

  • Draft: -0.02 to -0.04 inch wc (overfire)

  • Draft: Positive pressure (manufacturer's specifications)

  • CO: <100 ppm (diluted)

    Always follow manufacturer's specifications.

    Power burner appliances tend to have lower excess air readings and higher stack temperatures due to their less-complex heat exchanger designs, although some do approach condensing. Remember, there could be a positive pressure in the heat exchanger and a negative pressure in the stack depending on the design.

    A heat exchanger crack in this style furnace may not show an increase in excess air readings when the blower starts, and a decrease when the blower stops. If the primary air shutters/air band or gas pressure is adjusted, it is imperative that a combustion analysis be performed as operating characteristics of the furnace have changed. For proper combustion and venting, approximately 20 cubic feet of air is required per 1,000 Btuh; a 100,000-Btuh furnace would require 200 cubic feet of ventilation air for every hour of operation. Always set gas manifold pressure per the manufacturer's specifications.

    Measurement procedure:
    1. Connect the flue gas sampling probe assembly to the analyzer per the manufacturer's instructions.

    2. Verify that the condensate trap plug is properly seated in the combustion analyzer water trap, and that the thermocouple is not touching the side of the probe assembly.

    3. In uncontaminated air (outdoor), start the analyzer and allow the unit to complete the zeroing process. Never allow the analyzer to zero in the stack (unless the manufacturer's design allows this, e.g. Testo 330-2).

    4. Measurements must be made in the stack before the barometric damper (if so equipped).

    5. Allow the furnace to operate 10 minutes, or until stack temperature stabilizes. The furnace must establish draft (measured in the flue pipe) with 10 minutes of operation.

    6. Measure and print combustion results prior to and after any adjustments are made.

    OIL-FIRED POWER BURNERS

  • Oxygen: (cast iron cone) 5 to 9 percent

  • Oxygen: (flame retention) 3 to 6 percent

  • CO2: 10 to 12.5 percent

  • Stack temp: 60 to 79 percent AFUE, 400° to 600°F

  • Stack temp: 80-plus AFUE, 330° to 450°

  • Stack temp: 90-plus AFUE, less than 125°

  • Draft: -0.02 inch wc (overfire)

  • Draft (stack): -0.02 inch wc/0.04 inch wc

  • CO: <50 ppm (diluted)

  • Smoke spot: #0-#1

  • Oil pressure: 100 to 150 psi (per manufacturer)

    Always follow manufacturer's specifications.

    Oil power burner appliances tend to have lower excess air readings and higher stack temperatures due to less-complex heat exchanger designs. Some high- and ultra-high-efficiency models do approach and operate in condensing. Remember, these furnaces must operate with a negative pressure in the heat exchanger and a negative pressure in the stack unless otherwise specified by the manufacturer.

    A sizable heat exchanger crack in this style furnace will show as an increase in excess air readings when the blower starts and a decrease when the blower stops. If the primary air shutters/air band or oil pressure is adjusted, it is imperative that a combustion analysis is performed as the operating characteristics of the furnace have changed. For proper combustion and venting, approximately 25 cubic feet of air is required per 1,000 Btuh; a 100,000-Btuh furnace would require 250 cubic feet of ventilation air every hour of operation.

    Measurement procedure:
    1. Connect flue gas sampling probe assembly to analyzer per manufacturer's instructions.

    2. Verify condensate trap plug is properly seated in combustion analyzer water trap and thermocouple is not touching side of probe assembly.

    3. In uncontaminated air (outdoor), start the analyzer and allow the unit to complete its zeroing process. Never allow the analyzer to zero in the stack (unless the manufacturer's design allows this, e.g. Testo 330-2).

    4. Measurements must be made in the stack before the barometric damper, if so equipped.

    5. Allow the furnace to operate 10 minutes or until stack temperature stabilizes. The furnace must establish draft (measured in the flue pipe) within 10 minutes of operation.

    6. Measure and print combustion results prior to and after any adjustments are made.

    Sidebar: A Field Guide to Furnace Efficiencies

    Determining the gas furnace Annual Fuel Utilization Efficiency (AFUE) in the field is often hard, if not impossible. There are several types of efficiency ratings, including AFUE, combustion efficiency, thermal system operating efficiency, and steady-state operating efficiency.

    An old furnace can have 85 percent combustion efficiency yet have an AFUE of 60 percent because of the amount of heat going up the stack (heat not being transferred by the heat exchanger). A 95-percent-AFUE furnace can be operating in the 60-percent range due to poor installation or operation.

    Furnace efficiency (AFUE) can be generalized by applying the following information, provided the installation is adequate.

  • 60- to 70-percent AFUE:

    Standing pilot, draft diverter, belt-drive blower, and a single upshot burner; single-wall flue pipe.

  • 70- to 78-percent AFUE:

    Intermittent pilot, direct spark or hot surface igniter; draft diverter, with/without flue damper; direct-drive blower; multicell construction with ribbon, slotted, or ported burners; single-wall flue pipe.

  • 80-percent AFUE:

    Intermittent pilot direct spark or hot surface igniter; induced-draft, direct-drive blower, could be multistage and/or variable-speed; jet or in-shot-type burners; single- or double-wall flue pipe. If vented in masonry chimney, chimney must be lined.

  • 90- to 97-percent AFUE:

    Intermittent pilot, direct spark, or hot surface igniter; induced-draft, direct-drive blower, could be multistage or modulating and/or variable speed; jet or in-shot-type burners; secondary heat exchanger; plastic flue pipe.

    Thermal efficiency can be field calculated provided the heating value of the fuel being burned is known, accurate measurement of the airflow across the heat exchanger is made, and the values are input into the sensible heat formula then divided by the appliance input.

    Table 1. Average Btu content of fuels. (Source: U.S. Department of Energy.)

    Sidebar: Calculating Field Thermal Efficiency or Btuh Output

    To calculate field thermal efficiency or Btuh output, measure airflow across the heat exchanger, preferably using a mini-vane anemometer such as a Testo 416, or measure total external static pressure using a Testo 506-3 or 506-2 and the manufacturer's chart to determine cfm. Measure the temperature rise across the heat exchanger, being careful not to let radiant energy affect the temperature reading. It is preferable to make your temperature measurements in several locations and average them. Enter the results into the sensible heat formula.

    Total sensible heat (TSH): This is the heat added that causes a change in temperature of the air without adding or removing humidity.

    TSH formula: TSH = 1.08 x cfm x ∆T

    cfm = Airflow in cubic feet per minute

    ∆T (Delta T) = Change in temperature across the heat exchanger

    If the heat content of the natural gas is verified, the meter can be clocked and the actual input can be divided into the measured output to calculate the actual operating thermal efficiency.

    Sidebar: Problem Notification Form for Customers

    Company Name

    Heat Exchanger/Venting/Combustion Problem:

    While inspecting your furnace, performing the three-part inspection procedure as outlined in Refrigeration Service and Engineering Society (RSES) publication 630-92 9/86 and adopted by the Gas Appliance Manufacturers Association, and/or during venting/combustion air testing outlined in the National Fuel and Gas Code, we found the following:

    _____ The heat exchanger has a visible crack, hole, or opening that may allow flue gasses to enter the home.

    _____ Chemical testing using the salt spray test (chemical test) gave a positive result. This indication shows that flue gasses may enter the home through a crack, hole, or opening that isn't visible.

    _____ There is a venting or combustion air problem.

    Any breach in the heat exchanger or venting/combustion air problem that may allow flue gasses to enter the home creates a potentially dangerous situation for the homeowner. We highly recommend that you allow us to turn off the furnace until this problem can be corrected.

    I understand that by operating this appliance without correcting the problem, I assume full responsibility for any harm or damage that may result by my decision. I will not hold [Company Name], its heirs, or any of its employees, liable for my decision.

    Customer's Name: ______________________________ Date: _________________

    Customer's Signature: ____________________ PRINTED _____________________

    Technician's Signature: ___________________ PRINTED _____________________

    Publication date: 04/17/2006

  • Share This Story

    Looking for a reprint of this article?
    From high-res PDFs to custom plaques, order your copy today!

     

    Recommended Content

    JOIN TODAY
    To unlock your recommendations.

    Already have an account? Sign In

    • HVAC-enrollment

      The Trades Are Back: HVACR Programs See Nearly 30% Enrollment Spike

      A new wave of future technicians is entering the pipeline.  
      News
      By: Matt Jachman
    • 2025 Top 40 Under 40

      2025 Top 40 Under 40 HVACR Professionals List

      The 11th annual Top 40 Under 40 list highlights those...
      HVAC Contracting
      By: Hannah Belloli-Oster
    • LG Ductless Mini-Split Systems

      The 9 Types of Heat Pumps

      As the U.S. moves toward electrification, heat pumps are...
      Air Source Heat Pumps
      By: Joanna R. Turpin
    Subscription Center
    • Create an Account
    • Start a Subscription
    • Manage My Account
    • Sign Up for Newsletters
    • Visit Customer Service
    • Update Preferences

    More Videos

    Sponsored Content

    Sponsored Content is a special paid section where industry companies provide high quality, objective, non-commercial content around topics of interest to The News audience. All Sponsored Content is supplied by the advertising company and any opinions expressed in this article are those of the author and not necessarily reflect the views of The News or its parent company, BNP Media. Interested in participating in our Sponsored Content section? Contact your local rep!

    close
    • Piggy Bank
      Sponsored byWatercress Financial

      Energy Prices, Inflation, and HVAC: What Today’s Homeowners Care About

    • Refrigerated Food
      Sponsored bySolstice Advanced Materials

      R-455A Refrigeration: A Cold Storage Solution for the Future

    • Airex Rooftop Units
      Sponsored byAirex Manufacturing Inc

      Consolidating Roof Penetrations: A Growing Trend in Multifamily HVAC Design

    Popular Stories

    HVAC-Price-Increase-graphic

    HVAC Price Increase List: June 2026

    Trump-Section-232.jpg

    Trump Reduces Section 232 Tariffs on HVAC Equipment to 15%

    R410A-Refrigerant-Cylinder.jpg

    Refrigerant Recovery is a Revenue Opportunity

    Heat-pump-cutaway.jpg

    PFAS Rules and A2L Building Codes Continue to Evolve

    Midea-training.jpg

    HVAC Workforce Crisis Expands Beyond Technicians to Instructor Shortages

    View The ACHR NEWS
    Centennial Anniversary Timeline

    The ACHR News Timeline Chart
    Submit a Letter
    Submit a letter to our editors.

    Events

    November 6, 2025

    Next-Gen Data Center Cooling: HVAC Innovation and Real-World Solutions

    On Demand As AI workloads and high-density computing push traditional cooling methods to their limits, the data center industry is accelerating the adoption of next-generation HVAC technologies.

    June 17, 2026

    Decarbonization Without Disruption

    This webinar will explore practical HVAC decarbonization strategies that minimize disruption while maximizing long-term performance and ROI.

    View All Submit An Event

    Poll

    Summer Staff

    Are you fully staffed for the summer season?
    View Results Poll Archive

    Products

    BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

    BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

    See More Products
    Decarbonization Without Disruption - Free Webinar - 6/17/2026

    Related Articles

    • Ventilation and Heat Exchanger Testing

      See More
    • Heat Exchanger Market to Grow to $21.3 Billion by 2022

      See More
    • A Solution for Heat Exchanger Failures

      See More

    Related Products

    See More Products
    • 9781439842126.jpg

      Heat Exchanger Design Handbook, Second Edition

    • HVAC/R Electrical Troubleshooting: Component Testing Training Kit

    • A-Heat-Pump-Thats-Not-Delivering-Any-Air-DVD-Cover-218x300.jpg

      A Heat Pump That’s Not Delivering Any Air

    See More Products

    Related Directories

    • Polaris Plate Heat Exchangers LLC

      Plate heat exchangers, compact brazed plate heat exchangers, double-wall plate heat exchangers, semi-welded plate heat exchangers and automatic self-cleaning filters/strainers.
    • A to Z Sales & Marketing

      We strive to revolutionize indoor living through innovative solutions that improve air quality, enhance comfort, and promote sustainable living for people around the world.
    ×

    Sign Up. Stay Informed.

    The #1 trusted source for the HVACR industry since 1926

    SUBSCRIBE
    • RESOURCES
      • Advertise
      • Contact Us
      • Advisory Board
      • Classifieds
      • Submit a Letter
      • Directories
      • Store
    • ACCOUNT CENTER
      • Create an Account
      • Start a Subscription
      • Manage My Account
      • Sign Up for Newsletters
      • Visit Customer Service
      • Update Preferences
    • SERVICES
      • Marketing Services
      • Reprints
      • Market Research
      • List Rental
      • Survey/Respondent Access
    • STAY CONNECTED
      • LinkedIn
      • Facebook
      • Instagram
      • YouTube
      • X (Twitter)
    • PRIVACY
      • PRIVACY POLICY
      • TERMS & CONDITIONS
      • DO NOT SELL MY PERSONAL INFORMATION
      • PRIVACY REQUEST
      • ACCESSIBILITY

    Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

    Design, CMS, Hosting & Web Development :: ePublishing