ACHR News
search
Ask ACHR NEWS AI
cart
facebook twitter instagram linkedin youtube
  • Sign In
  • Subscribe
  • Sign Out
  • My Account
ACHR News
  • NEWS
    • Breaking News
    • New HVAC Products
    • Featured Products
    • Manufacturer Reports
    • HVAC Data
    • Legislation
    • ACHR NEWS Centennial
  • RESIDENTIAL
    • Air Conditioners
    • Furnaces
    • Residential Heat Pumps
    • Ductless
    • Residential IAQ
    • Testing, Monitoring, Tools
    • Components & Accessories
  • COMMERCIAL
    • Air Handlers
    • Rooftop Units
    • Chillers and Cooling Towers
    • Commercial Heat Pumps
    • Boilers and Hydronics
    • VRF/Ductless
    • Commercial IAQ
  • REFRIGERATION
    • Refrigerants
    • Refrigerant Regulations
    • Leak Management
  • CONTRACTOR PRO
    • Geothermal
    • Homeowner Study
    • VRF and VRV Ductless
    • Unitary Trends
  • EDUCATION
    • Training and Education
    • Business Management
    • Service and Maintenance
    • Continuing Education
    • Market Research >
      • HVAC Brand Awareness Report
      • VRV, VRF, VRVZ Report
      • Unitary Trends Report
      • Water Heat Professionals Report
    • Webinars
    • Sponsor Insights
    • eProducts Info
    • White Papers
  • EVENTS
    • HVAC Contractor Forum
    • Industry Events and Webinars
  • MEDIA
    • Videos
    • AHR Expo 2025 Videos
    • Podcasts >
      • ACHR News Podcast
      • HARDI Podcasts
      • AHR Expo Podcasts
      • ACCA Podcasts
    • Interactive Spotlights
    • Quizzes
    • eBooks
    • HVAC Talkback
  • HVAC GROUP
    • ACHR NEWS >
      • Current Issue
      • Digital Edition
      • Subscribe
    • Distribution Trends
    • SNIPS NEWS >
      • Join SNIPS NEWS
    • Engineered Systems News >
      • Join ES News
    • HVACR Directory
    • Contests
    • Newsletters
    • Contact
    • Advertise
    • My Account
Refrigerants

The Professor: Condensing Temperatures and Condensing Splits

By John Tomczyk
July 2, 2012
Condensing temperatures often give service technicians valuable hints as to what the problem may be within a refrigeration system. In fact, most service technicians would rather troubleshoot the refrigeration system’s high side than the system’s low side. This is because almost all of the heat absorbed in the system is rejected in the condenser. All the heat absorbed in the evaporator and the suction line is rejected in the condenser. Also, the compressor’s motor heat and the heat generated in the compression stroke, often referred to as heat of compression, also has to be rejected in the condenser. The three functions of the condenser are desuperheating, condensation, and subcooling.

Desuperheating

The compressor delivers high-pressure, superheated vapor to the condenser through the discharge line. In a standard condenser, the first passes desuperheat the discharge line gases. This prepares the high-pressure superheated vapors for condensation or phase change from vapor to liquid because it takes the sensible (measurable) heat away from them and shrinks their volume.

Remember that these superheated gases must lose all of their superheat before reaching the condensing temperature for a certain condensing pressure. Once the initial passes of the condenser have rejected enough superheat and the condensing temperature or saturation temperature has been reached, these gases are referred to as 100 percent saturated vapor. The refrigerant is said to have reached the 100 percent saturated vapor point in the condenser. This point is the end of the desuperheating process.

Condensation

Now the vapor is ready to condense if any more heat is lost. In fact, condensation, or changing vapor to liquid, is the main function of the condenser. Condensing is system dependent and usually takes place in the lower two-thirds of the condenser. Once the saturation or condensing temperature is reached in the condenser and the refrigerant gas has reached 100 percent saturated vapor, condensation can take place if more heat is removed. As more heat is taken away from the 100 percent saturated vapor, it will force the vapor to become a liquid (condense). When condensing, the vapor will gradually phase change to liquid until all that remains is 100 percent liquid. This phase change, or change of state, is an example of a latent heat rejection process. This is because the heat that is being removed while phase changing is latent heat, not sensible heat. This phase change from vapor to liquid will happen at one temperature. In other words, the temperature will remain constant while phase changing even though heat is being removed.

Note: An exception to this is the 400 series refrigerant blends where there is a temperature change (temperature glide) when phase changing. This one temperature is the saturation temperature corresponding to the saturation pressure in the condenser. Remember, it is only at saturation in a phase changing region that there is a pressure/temperature relationship and the service technician can use a pressure/temperature chart. This pressure can be measured anywhere on the high side of the refrigeration system as long as line and valve pressure drops and losses are negligible.

Subcooling

The last function of the condenser is to subcool the liquid refrigerant. Subcooling is defined as any sensible heat taken away from the 100 percent saturated liquid. Technically, subcooling is defined as the difference between the measured liquid temperature and the liquid saturation temperature at a given pressure. Once the saturated vapor in the condenser has phase changed to saturated liquid, the 100 percent saturated liquid point has been reached. If any more heat is removed, the liquid will go through a sensible heat rejection process and lose temperature as it loses heat. The liquid that is cooler than the saturated liquid in the condenser is subcooled liquid. Subcooling is an important process because it starts to lower the liquid temperature closer to the evaporating temperature before it reaches the metering device. This will reduce flash loss in the evaporator so more of the vaporization of the liquid in the evaporator can be used for useful cooling of the product load. In other words, the net refrigeration effect is increased.

Condenser Splits

When talking about air-cooled condensers, the temperature difference between the ambient and the condensing temperature is often referred to as the condenser split. For example, if the condensing temperature is 110˚F and the ambient is 80˚, the condenser split would be 30˚ (110–80). The condensing temperature in any system is obtained from the condensing pressure using a pressure/temperature chart. Condenser splits can range from 10˚ to 30˚ depending on whether the condensing unit is a standard-, mid-, or high-efficiency condensing unit. The higher the efficiency, the more coil surface area there will be, thus the lower the condenser split will be. For the balance of this article, I will deal with a standard efficiency condenser that normally runs a 20-30˚ split.

Condenser splits are not affected by ambient changes. If there is an increase in the ambient temperature, there will also be an increase in the condensing temperature, but the condenser split (difference between the two temperatures) will remain the same.

Looking for quick answers on air conditioning, heating and refrigeration topics? Try Ask ACHR NEWS, our new smart AI search tool. Ask ACHR NEWS →

On the other hand, condensing temperatures for a single condenser can vary depending on two factors: ambient swings and evaporator heat loading.

Ambient Swings

As the ambient temperature increases, less heat can be rejected from the air-cooled condenser to the hotter ambient. This means that more of the heat absorbed by the evaporator and suction line, and the heat of compression generated by the compressor, will remain in the condenser. This will increase the condenser’s internal temperature and pressure. The condenser is now operating at an elevated condensing temperature for the elevated ambient, but the difference between the condensing temperature and the ambient (condenser split) has remained the same.

Evaporator Heat Loading

As the evaporator sees more heat load, more heat has to be rejected to the condenser. As more heat is rejected to the condenser, its condensing temperature increases. With an increased condensing temperature, the condenser split is now increased because ambient temperature remained the same.

Low Condenser Splits

If a service technician experiences a low condenser split, say 7˚F, the technician immediately knows that not much heat is being absorbed in the evaporator. The low split tells the technician that the refrigerator or freezer is not working very hard. This holds true no matter what the ambient or condensing temperature is. It could mean a frosted evaporator coil, evaporator fan out, high superheat condition in the evaporator from undercharge or starving metering device, inefficient compressor, a plugged filter drier, or similar. The low condenser split is a reflection of these problems.

High Condenser Splits

On the other hand, if the service technician experiences a high condenser split, the technician immediately knows that the refrigerator or freezer is rejecting a lot of heat out of the condenser. This means that there must be a lot of heat being absorbed in the evaporator. It could be from a door opening, warm product in the box, just after a defrost period, or similar.

Because what happens in the condenser is a direct reflection on what is happening in the rest of the refrigeration system, the service technician should never ignore troubleshooting the high side of the refrigeration system. The high side of the refrigeration system will often give valuable information to the wise service technician.

Publication date: 7/2/2012

KEYWORDS: troubleshooting and HVACR

Share This Story

Looking for a reprint of this article?
From high-res PDFs to custom plaques, order your copy today!

 

John Tomczyk is HVACR professor emeritus, Ferris State University, Big Rapids, Michigan, and coauthor of Refrigeration & Air Conditioning Technology, published by Cengage Learning. Contact him at tomczykjohn@gmail.com.

Recommended Content

JOIN TODAY
To unlock your recommendations.

Already have an account? Sign In

  • HVAC-enrollment

    The Trades Are Back: HVACR Programs See Nearly 30% Enrollment Spike

    A new wave of future technicians is entering the pipeline.  
    Training and Education
    By: Matt Jachman
  • 2025 Top 40 Under 40

    2025 Top 40 Under 40 HVACR Professionals List

    The 11th annual Top 40 Under 40 list highlights those...
    HVAC Residential Market
    By: Hannah Belloli-Oster
  • LG Ductless Mini-Split Systems

    The 9 Types of Heat Pumps

    As the U.S. moves toward electrification, heat pumps are...
    Heat Pumps
    By: Joanna R. Turpin
Subscription Center
  • Create an Account
  • Start a Subscription
  • Manage My Account
  • Sign Up for Newsletters
  • Visit Customer Service
  • Update Preferences

More Videos

Sponsored Content

Sponsored Content is a special paid section where industry companies provide high quality, objective, non-commercial content around topics of interest to The News audience. All Sponsored Content is supplied by the advertising company and any opinions expressed in this article are those of the author and not necessarily reflect the views of The News or its parent company, BNP Media. Interested in participating in our Sponsored Content section? Contact your local rep!

close
  • Piggy Bank
    Sponsored byWatercress Financial

    Energy Prices, Inflation, and HVAC: What Today’s Homeowners Care About

  • Refrigerated Food
    Sponsored bySolstice Advanced Materials

    R-455A Refrigeration: A Cold Storage Solution for the Future

  • Airex Rooftop Units
    Sponsored byAirex Manufacturing Inc

    Consolidating Roof Penetrations: A Growing Trend in Multifamily HVAC Design

Popular Stories

HVAC-Price-Increase-graphic

HVAC Price Increase List: June 2026

Trump-Section-232.jpg

Trump Reduces Section 232 Tariffs on HVAC Equipment to 15%

Refrigerants-and-gauge.jpg

HVAC Industry Warns of Counterfeit Refrigerants Entering U.S. Supply Chain

U.S. Supreme Court building

95% Furnace Efficiency Rule to Get New Hearing

Midea-training.jpg

HVAC Workforce Crisis Expands Beyond Technicians to Instructor Shortages

View The ACHR NEWS
Centennial Anniversary Timeline

The ACHR News Timeline Chart
Submit a Letter
Submit a letter to our editors.

Events

November 6, 2025

Next-Gen Data Center Cooling: HVAC Innovation and Real-World Solutions

On Demand As AI workloads and high-density computing push traditional cooling methods to their limits, the data center industry is accelerating the adoption of next-generation HVAC technologies.

June 23, 2026

HVAC Duct Sealing Mastics: Why Selection Matters

In this webinar we will detail what HVAC material buyers and technicians need to know when selecting duct mastics, including matching mastic to substrate, alternatives to liquid mastic, and where UL 181 Listings fit into real world installations.

View All Submit An Event

Poll

Summer Staff

Are you fully staffed for the summer season?
View Results Poll Archive

Products

BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

See More Products
HVAC Duct Sealing Mastics: Why Selection Matters - Free Webinar - 6/23/2026

Related Articles

  • The Professor: Calculating Net Temperature Glide

    See More
  • These condenser fins have been bent horizontally and are blocking airflow through the condenser. Photos courtesy of John Tomczyk

    The Professor: The Importance of the Condenser

    See More
  • The Professor: Foiling Frosted Evaporator Coils

    See More

Events

View AllSubmit An Event
  • July 16, 2025

    Let’s Talk: Condensing Equipment, (Acidic) Condensate, and the Code

    On Demand During this webinar, we will define what acidic condensate is, illustrate how it’s formed in today’s high-efficiency, gas-fired heating appliances, and hit on the damage it can cause if not treated.
View AllSubmit An Event

Related Directories

  • Condenser and Chiller Services

    Offers in-field eddy current inspection, remote video inspection, protective epoxy coatings and complete retubing service with tubes in stock.
×

Sign Up. Stay Informed.

The #1 trusted source for the HVACR industry since 1926

SUBSCRIBE
  • RESOURCES
    • Advertise
    • Contact Us
    • Advisory Board
    • Classifieds
    • Submit a Letter
    • Directories
    • Store
  • ACCOUNT CENTER
    • Create an Account
    • Start a Subscription
    • Manage My Account
    • Sign Up for Newsletters
    • Visit Customer Service
    • Update Preferences
  • SERVICES
    • Marketing Services
    • Reprints
    • Market Research
    • List Rental
    • Survey/Respondent Access
  • STAY CONNECTED
    • LinkedIn
    • Facebook
    • Instagram
    • YouTube
    • X (Twitter)
  • PRIVACY
    • PRIVACY POLICY
    • TERMS & CONDITIONS
    • DO NOT SELL MY PERSONAL INFORMATION
    • PRIVACY REQUEST
    • ACCESSIBILITY

Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

Design, CMS, Hosting & Web Development :: ePublishing