ACHR News
search
Ask ACHR NEWS AI
cart
facebook twitter instagram linkedin youtube
  • Sign In
  • Subscribe
  • Sign Out
  • My Account
ACHR News
  • NEWS
    • Breaking News
    • New HVAC Products
    • Featured Products
    • Manufacturer Reports
    • HVAC Data
    • Legislation
    • ACHR NEWS Centennial
  • RESIDENTIAL
    • Air Conditioners
    • Furnaces
    • Residential Heat Pumps
    • Ductless
    • Residential IAQ
    • Testing, Monitoring, Tools
    • Components & Accessories
  • COMMERCIAL
    • Air Handlers
    • Rooftop Units
    • Chillers and Cooling Towers
    • Commercial Heat Pumps
    • Boilers and Hydronics
    • VRF/Ductless
    • Commercial IAQ
  • REFRIGERATION
    • Refrigerants
    • Refrigerant Regulations
    • Leak Management
  • CONTRACTOR PRO
    • Geothermal
    • Homeowner Study
    • VRF and VRV Ductless
    • Unitary Trends
  • EDUCATION
    • Training and Education
    • Business Management
    • Service and Maintenance
    • Continuing Education
    • Market Research >
      • HVAC Brand Awareness Report
      • VRV, VRF, VRVZ Report
      • Unitary Trends Report
      • Water Heat Professionals Report
    • Webinars
    • Sponsor Insights
    • eProducts Info
    • White Papers
  • EVENTS
    • HVAC Contractor Forum
    • Industry Events and Webinars
  • MEDIA
    • Videos
    • AHR Expo 2025 Videos
    • Podcasts >
      • ACHR News Podcast
      • HARDI Podcasts
      • AHR Expo Podcasts
      • ACCA Podcasts
    • Interactive Spotlights
    • Quizzes
    • eBooks
    • HVAC Talkback
  • HVAC GROUP
    • ACHR NEWS >
      • Current Issue
      • Digital Edition
      • Subscribe
    • Distribution Trends
    • SNIPS NEWS >
      • Join SNIPS NEWS
    • Engineered Systems News >
      • Join ES News
    • HVACR Directory
    • Contests
    • Newsletters
    • Contact
    • Advertise
    • My Account
HVAC ContractingService and MaintenanceHeat Pumps

Btu Buddy 107: Heat Pump Service Call - Part 2

By Bill Johnson
February 20, 2012
Bob is a service technician who is well trained and nationally certified. However, he has sometimes suffered from the same confusion that all technicians occasionally do — the facts that he gathers may or may not point to the obvious cause of the problem or the best solution. But Bob has had something that no one else has. He recalled his long-time HVACR mentor and imagines him accompanying him as “Btu Buddy,” someone who reminded him to take time to stop and think before rushing to judgment, helping keep him on the right track, even with facts that are confusing.

Now, Bob’s company has promoted him to help train a new employee, right out of a school specializing in HVAC, just like Bob was. Bob is now Tim’s Btu Buddy. Tim is anxious to travel with Bob. Tim realizes that he is right out of school, with the theory and lab work that he accomplished in school, but still needs help. He knows that he worked with many of the components of the systems in the school, under ideal conditions with good light and air conditioning. Now it is into the field, sometimes under the house with poor lighting, or out on the rooftop in the sun, where the real action is. He is naturally and normally reluctant, but he has Bob to help guide him.

Bob and Tim are continuing a service call on a heat pump that has two failed auxiliary heaters. It’s very cold outside and they have just returned from the supply house with two new heaters.

They left the heat on with the heat pump and the one remaining auxiliary heater operating so the homeowner would have some heat while they were gone. The house temperature was down to 60°F with an outside temperature of 25° with the heat pump and one strip heat operating. They left the job wondering if the heat pump itself was operating up to capacity.

When they got back to the house with the new heaters, they went to the indoor unit and shut it down and replaced the two defective heaters and turned the system back on. They checked the amperage to the two new heaters and they were operating. Tim then asked, “What’s next?”

Bob said, “Let’s go to the heat pump for a visual inspection first to see what we see.”

They went outside and Tim said, “Wow, that heat pump is iced up. Ice is covering the whole coil.”

Bob said, “Look at that unit closely. There are weeds growing through the grille guard into the coil. When the normal ice pattern forms on that coil, the weeds will interfere with the defrost cycle. That unit is a mess. It’s a wonder it is heating at all.”

Looking for quick answers on air conditioning, heating and refrigeration topics? Try Ask ACHR NEWS, our new smart AI search tool. Ask ACHR NEWS →

Tim asked, “What can we do to get that ice off of the coil?”

Bob responded, “It would take many forced defrost cycles and a lot of time to get the ice off using the unit’s defrost cycles. We have a great external heat source for removing the ice right here. The city water temperature is about 45° and it will be great for the removing the ice. Remember, this is not block ice. It is not a dense ice. It has a lot of air in it.”

Tim asked, “What do we do next?”

Bob said, “Before you do anything, use your cell phone and take some pictures of this coil. Then turn the power off and take the top off of the unit. It contains the fan and we can set it aside without removing the wiring. The wires are long enough. Then cover the control box with plastic to keep it dry.”

Tim did this and then Bob said, “Get the water hose from the truck and connect it to this hose bib on the side of the house and set the hose to a spray and wash the ice off of the unit. It will take maybe 20 minutes.”

After Tim cleared the ice from the unit, Bob said, “We have to remove the weeds from the coil. I believe we will have to remove the coil guard to do a good job. Take a few more pictures showing those weeds in the coil.”

They removed the coil guard and pulled the weeds from the coil by hand and put the coil guard back on, and Bob said, “Boy, it is cold out here, but I believe that we need to apply some coil cleaner to the coil and then back wash it with this water hose. I hate to do this in this weather, but we are here and have the unit set up for a coil cleaning.”

Tim asked, “What do you mean by back wash?”

Bob explained, “The airflow is towards the center of the coil because the fan pulls the air in and discharges it through the top of the unit (Figure 1). This means that any dust or dirt will be in contact with the outside of the coil first. To back wash, we will apply the water to the inside of the coil and force the dirt to the outside of the coil. We’ll spray the coil with coil cleaner and get it soaked. This will help remove the dirt from the coil.”

Tim said, “I get it. If we wash the coil from the outside inward, we may force any dirt on the outside of the coil to the inside of the coil. We probably wouldn’t get the coil as clean.”

They cleaned the coil and Tim said, “I just thought of this. We shut down the unit and have had the heat off in the house. I bet it is getting cold in there.”

Bob said, “Where is the power supply for the low voltage?”

Tim said, “I didn’t think of that. It is in the air handler. The house has had the strip heat operating, so it shouldn’t be too bad.”

When they finished cleaning the coil, they put the unit back together, turned the power on, and the unit started running. Tim asked, “Should we do a performance check on the unit?”

Bob said, “To do a full performance check, we would have to put gauges on the unit and take wet and dry bulb readings. I think that we will do a simple check on the system. We can measure the discharge air temperature of the air leaving the heat pump, without the electric heat coils. If the air temperature is about 95°, we can declare the unit good to go.

“On this unit, we can disconnect the electric heat by removing the W1 wire in the air handler (Figure 2), and insert a thermometer probe in the air stream and we will record only the heat pump discharge air temperature to see if it is really heating. Let’s place the thermometer lead in the first air discharge register, which is in the dining room.

“We can also observe the outdoor unit frost pattern to see if it has enough refrigerant charge. If there is enough refrigerant, the coil will be iced to the top of the unit.”

After the unit had been running for about 20 minutes they observed the temperature in the dining room air register to be 96°. Then they looked at the outdoor unit and the frost line on the coil was very near the top of the coil. Bob said, “From a visual observation, this unit is doing well. Let’s show these pictures to the homeowner. Take another photo of the cleaned unit for comparison.”

They reconnected the strip heat. Then they showed the photos to the homeowner and she had them email them to her email address so she could show her husband.

Tim said, “Well, that was an interesting service call. The picture of before and after to the homeowner was a great idea. She could see the evidence and that verifies the value of a service call well done to the customer.”

Bob said, “Doing a good job and proving it to the customer is always good. They want good value for what they pay, just like we do.”

Publication date: 02/20/2012

KEYWORDS: maintenance for HVACR troubleshooting and HVACR

Share This Story

Looking for a reprint of this article?
From high-res PDFs to custom plaques, order your copy today!

 

Active in the HVACR industry since the 1950s, Bill Johnson graduated in gas fuel technology and refrigeration from the Southern Technical Institute, a branch of Georgia Tech (now known as Southern Polytechnic Institute). He taught HVAC classes at Coosa Valley Vocational & Technical Institute for four years. He moved on to become service manager for Layne Trane, Charlotte, N.C. He taught for 15 years at Central Piedmont Community College, part of this time as program director. He had his own business for five years doing installation and service work. Now retired, he is the author of Practical Heating Technology and Practical Cooling Technology, and continues as a co-author of Refrigeration & Air Conditioning Technology, seventh edition, all published by Delmar Cengage Learning. For more information, he can be reached at 704-968-0000 or thebillj1@gmail.com.

Btu Buddy Notebook is a collection of more than 50 service call scenarios in book form covering both cooling season and heating season troubleshooting. For more information and to purchase the book, visit the HVACR Industry Store.

Recommended Content

JOIN TODAY
To unlock your recommendations.

Already have an account? Sign In

  • HVAC-enrollment

    The Trades Are Back: HVACR Programs See Nearly 30% Enrollment Spike

    A new wave of future technicians is entering the pipeline.  
    News
    By: Matt Jachman
  • 2025 Top 40 Under 40

    2025 Top 40 Under 40 HVACR Professionals List

    The 11th annual Top 40 Under 40 list highlights those...
    HVAC Light Commercial Market
    By: Hannah Belloli-Oster
  • LG Ductless Mini-Split Systems

    The 9 Types of Heat Pumps

    As the U.S. moves toward electrification, heat pumps are...
    HVAC Commercial Market
    By: Joanna R. Turpin
Subscription Center
  • Create an Account
  • Start a Subscription
  • Manage My Account
  • Sign Up for Newsletters
  • Visit Customer Service
  • Update Preferences

More Videos

Sponsored Content

Sponsored Content is a special paid section where industry companies provide high quality, objective, non-commercial content around topics of interest to The News audience. All Sponsored Content is supplied by the advertising company and any opinions expressed in this article are those of the author and not necessarily reflect the views of The News or its parent company, BNP Media. Interested in participating in our Sponsored Content section? Contact your local rep!

close
  • Piggy Bank
    Sponsored byWatercress Financial

    Energy Prices, Inflation, and HVAC: What Today’s Homeowners Care About

  • Refrigerated Food
    Sponsored bySolstice Advanced Materials

    R-455A Refrigeration: A Cold Storage Solution for the Future

  • Airex Rooftop Units
    Sponsored byAirex Manufacturing Inc

    Consolidating Roof Penetrations: A Growing Trend in Multifamily HVAC Design

Popular Stories

Refrigerants-and-gauge.jpg

HVAC Industry Warns of Counterfeit Refrigerants Entering U.S. Supply Chain

U.S. Supreme Court building

95% Furnace Efficiency Rule to Get New Hearing

Midea-training.jpg

HVAC Workforce Crisis Expands Beyond Technicians to Instructor Shortages

Data_Center_facility.jpg

HVAC Manufacturers Respond to Growing Data Center Backlash

HVAC Minute retail refrigeration system

EPA Final Rule’s Impact on R-410A Deadlines

View The ACHR NEWS
Centennial Anniversary Timeline

The ACHR News Timeline Chart
Submit a Letter
Submit a letter to our editors.

Events

November 6, 2025

Next-Gen Data Center Cooling: HVAC Innovation and Real-World Solutions

On Demand As AI workloads and high-density computing push traditional cooling methods to their limits, the data center industry is accelerating the adoption of next-generation HVAC technologies.

June 23, 2026

HVAC Duct Sealing Mastics: Why Selection Matters

In this webinar we will detail what HVAC material buyers and technicians need to know when selecting duct mastics, including matching mastic to substrate, alternatives to liquid mastic, and where UL 181 Listings fit into real world installations.

View All Submit An Event

Poll

Summer Staff

Are you fully staffed for the summer season?
View Results Poll Archive

Products

BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

BNI Mechanical/Electrical Square Foot Costbook, 2026 Edition

See More Products
HVAC Duct Sealing Mastics: Why Selection Matters - Free Webinar - 6/23/2026

Related Articles

  • Btu Buddy 106: Heat Pump Service Call - Part 1

    See More
  • Btu Buddy 121: Heat Pump No Heat Call - Part 2

    See More
  • Btu Buddy 117: Oil Burner Pump Problem - Part 2

    See More

Related Products

See More Products
  • HPOIS.png

    Heat Pump Operation, Installation, Service

  • A-Heat-Pump-Thats-Not-Delivering-Any-Air-DVD-Cover-218x300.jpg

    A Heat Pump That’s Not Delivering Any Air

  • A-Heat-Pump-That-Won__t-Cool-DVD-Cover-214x300.jpg

    A Heat Pump That Won't Cool

See More Products

Related Directories

  • BP Porter Inc. (Heat Pump Controls/Thermostats)

    BP Porter Inc., the products of this company BPC-1 Bill Porter Control (a fossil fuel control) and BPC-ODS micro'stat was developed (invented) by Bill Porter, an HVAC technician in early 1994.
  • IGSHPA-International Ground Source Heat Pump Assn.

    IGSHPA is an association of companies, professionals and users dedicated to promoting the science, utility and use of geothermal (ground source) heating and cooling technology.
×

Sign Up. Stay Informed.

The #1 trusted source for the HVACR industry since 1926

SUBSCRIBE
  • RESOURCES
    • Advertise
    • Contact Us
    • Advisory Board
    • Classifieds
    • Submit a Letter
    • Directories
    • Store
  • ACCOUNT CENTER
    • Create an Account
    • Start a Subscription
    • Manage My Account
    • Sign Up for Newsletters
    • Visit Customer Service
    • Update Preferences
  • SERVICES
    • Marketing Services
    • Reprints
    • Market Research
    • List Rental
    • Survey/Respondent Access
  • STAY CONNECTED
    • LinkedIn
    • Facebook
    • Instagram
    • YouTube
    • X (Twitter)
  • PRIVACY
    • PRIVACY POLICY
    • TERMS & CONDITIONS
    • DO NOT SELL MY PERSONAL INFORMATION
    • PRIVACY REQUEST
    • ACCESSIBILITY

Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

Design, CMS, Hosting & Web Development :: ePublishing