Total System Superheat

Servicing and maintaining refrigeration equipment often requires technicians to measure the pressures and temperatures, and calculate the condition of the refrigerant at several different locations throughout a system. One aspect that is sometimes overlooked is the superheat value of the refrigerant at the inlet of the compressor. This is commonly referred to as the system’s total superheat.

Most compressor manufacturers recommend that this measurement be taken approximately 6 inches from the suction service valve. This can be an important measurement for reciprocating compressors; it ensures that the returning refrigerant will not cause damage to the compressor.

Reciprocating compressor manufacturers normally state the accepted range of superheat values for refrigerant returning to their compressors. Superheat that is too low or too high may cause damage to a compressor.

A refrigerant with a 0°F superheat value (saturated refrigerant) at this location indicates that some amount of liquid refrigerant is returning to the compressor. In this condition, the amount of liquid refrigerant returning is unknown, but any amount is too much. Liquid refrigerant returning to a compressor can damage a compressor in one of two ways:

1. Liquid refrigerant can mix with the compressor’s lubricating oil. As the liquid refrigerant comes into contact with the bearing surfaces, it will wash away the oil film, causing bearing wear. Depending on the percentage of liquid refrigerant to oil, the wear could be mild to severe.

2. If a sufficient amount of refrigerant returns to the compressor, it may be possible for liquid to enter the compressor cylinder(s) and cause further damage to the compressor as it attempts to compress a liquid.

TOO LOW, TOO HIGH

Too low of a superheat is also a problem. Even though liquid refrigerant may not currently be returning to the compressor, it may be possible that during low load conditions the superheat value of the refrigerant will drop to 0° - then some amount of liquid refrigerant will return to the compressor. One compressor manufacturer recommends that the superheat value returning to its compressor be no less than 20°.

Too high of a superheat can cause the heat of compression to increase, causing the temperature at the discharge valves to increase. If the temperature increases beyond its safe operating temperature, it will cause damage to the compressor.

For a reciprocating compressor to operate properly, the temperature of the discharge valves should never rise above 300°. At temperatures between 300° and 320° inside the compressor, the oil will start to lose its ability to lubricate, causing premature wear of the compressor’s cylinder and piston rings. At temperatures above 350° the oil will start to break down, causing accelerated bearing wear.

When you are servicing or maintaining refrigeration systems, check the superheat of the refrigerant returning to the compressor and compare it to the specifications provided by the compressor manufacturer. This is one way you can make sure the compressor is working within safe operating conditions.

Publication date: 08/06/2007

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Joe Marchese is an author and instructor and former HVACR contractor. He can be reached at joe@reachtechnicaltraining.com.

Recent Articles by Joe Marchese

You must login or register in order to post a comment.

measurement of superheat

Alkesh K Patel
February 4, 2009
total system superheat be taken appro. 6" from suction service valve why? can we measure it 12" or 2" from the suction service valve?

Multimedia

Videos

Image Galleries

2013 ACCA Conference & IE3 Expo

Photos from the 2013 ACCA Conference & IE3 Expo in Orlando, Fla.

Podcasts

Selling Zoning is Easier Than You Might Think

This overview of the benefits of zoning includes tips for selling to consumers and businesses. Tom Jackson discusses options for new construction and retrofit, as well as some ways a residential contractor can get into the light commercial business with zoning products. Speaker: Tom Jackson, CEO, Jackson Systems
More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 05-13-13 cover

2013 May 13

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

HVAC LEASING

Some HVAC contractors have introduced leasing programs for consumers. Do you think this is a viable option?
View Results Poll Archive

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con