the NEWS
Advertisement:
HVACR Directory | Extra Edition | Learning Center | Editorial Blogs | Product Gallery
  Home
  About the NEWS
  Subscription Info
  e-Newsletters
  Contact Us
  Resources
  Archived Editorial
  Blogs
  Career Center - Employers
  Career Center - Job Seekers
  Columns
  Distributor Corner
  Calendar of Events
  HVACR Directory
  Industry Links
  Learning Center
  Letters
  Manufacturer Reports
  Regional Reports
  Reprints
  Survey Says
  Training Track
  Webinars
  AEC Store
  Market Research
  Extra Edition
  HVACR Forum
  Legal forum
  Business Management
  Dot Comment
  Energy Matters
  Features
  Newsline
  People
  Service Hotline
  Service & Maintenance
  Technical
  Advertising
  Ad Index
  Media Kit
  Submit Press Release
  Services
  Classifieds
  Digital Edition
  Post Cards
spacer
Search in: EditorialProductsCompanies
The Question of Kitchen Cross Currents
by Al D'Ambola
June 29, 2009

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



Al D'Ambola
With smoke you can see them, with your nose you can smell them, and unfortunately for the workers in restaurant kitchens, they can feel the heat. Cross currents are air patterns that enter a capture hood and push the radiant heat, smoke, and odors from the cooking surfaces away from the hood, and into the kitchen.

All too often we are called in to evaluate problem restaurants where the hood is not capturing the heat or smoke from the cooking surfaces. One of the first things to look at when diagnosing a capture hood is the possibility of cross current interference. Typically this is caused by improper placement of supply registers for the a/c unit that are too close and above the plane of the hood.

As the cold air comes out of the supply registers, which are not balanced for velocity, the air now enters the capture zone of the hood. This causes tremendous turbulence and the cold dense air can push the radiant heat and smoke outside of the hood, causing extreme comfort and IAQ issues for the restaurant employees, as well as a huge waste of energy for the restaurant owner.


Advertisement:

For more info, click here
The supply registers should be a minimum distance of 10 feet from the hood and, most critical for side wall supply registers, be at an even plane with the hood. Unfortunately, this is not the norm. Consider changing the type of ceiling supply registers that will throw the air away from the capture hood, a two-way versus a four-way or side wall register that will allow you to direct the air away from the hood. This will reduce the turbulence and go a long way toward keeping the radiant heat and smoke from the cooking surfaces in the containment area of the hood on which you are working.

What if the restaurant cooking area is located in the dining area? Cross currents can push smoke and heat outside the hood and cause a host of odor and comfort issues for the patrons, and a nightmare for the restaurant. Supply a/c registers placement is extremely critical.

So if you are working in a retrofit application, remember, cross currents caused by the a/c unit could have a major impact on air quality, utility expense, and hood performance.

Publication date: 06/29/2009



Al D'Ambola
President of D’Ambola Associates. For more information, visit www.dambola.com or call 888-930-2004.