The Professor: Oil Safety Controllers and Their Circuits

By John Tomczyk
Figure 1. The tubing connected to the bellows can be a high-pressure rubber hose, such as shown in the lower right of this photo.


Oil safety controllers often come in two types: bellows (mechanical) and transducer (electronic).

Remember, net oil pressure (NOP) or sometimes referred to as useful oil pressure, is the difference between the oil pump discharge pressure and the crankcase pressure (as referenced in my column in the Jan. 11 issue). Bellows-type controllers sense both crankcase pressure and oil pump discharge pressure, usually through some type of tubing, and then transmit the pressure to flexible bellows. The tubing connected to the bellows is usually copper capillary tubes, high-pressure rubber hose, or a type of high-pressure plastic with a braided aluminum shrouding (Figures 1 and 2 illustrate the internal action of the bellows-type controller.)

Transducer-type controllers use a pressure transducer, which senses a combination of oil pump discharge pressure and crankcase pressure. The pressure transducer has two separate ports to sense both crankcase pressure and oil pump discharge pressure.

The subtraction or difference between these two pressures (net oil pressure) is accomplished by the transducer mechanically. The pressure transducer is connected to an electronic controller by wires. The pressure transducer then transforms a pressure signal to an electrical signal for the electronic controller to process.

Both types of oil safety controllers are referred to as differential-type controllers. The nomenclature comes from the fact that they sense two different pressures. Those pressures are crankcase pressure and oil pump discharge pressure.

Figure 2. Internal action of the bellows type controller.

BELLOWS (MECHANICAL) CONTROLLER

The oil pump discharge pressure acts to open the differential pressure switch. Conversely, the crankcase pressure acts to close the switch. One has to remember that the difference between these two pressures is the net oil pressure.

Oil pump discharge pressure - Crankcase pressure = Net oil pressure

So, if there is a fall in net oil pressure below 9 pounds per square inch differential (psid), the pressure differential switch will close and a heater in series with the pressure differential switch will be energized. There is usually a two-minute delay before the heater will warp a bimetallic strip. This warping action will open the timing switch contacts, which are in series with the motor starter or contactor coil. This action takes the motor out of service and must be manually reset on most controls.

Notice that manually pushing the reset button will reset (close) the timing switch contacts once the bimetal strip cools down. The reason for the two-minute time delay is to prevent nuisance trips of the oil safety controller. Often, there are times when the crankcase may have liquid refrigerant in it from an imperfect system. The two-minute delay gives the crankcase time to clear any unwanted refrigerant during periods when refrigerant migration or flooding has occurred. It also avoids shutdowns during short fluctuations in net oil pressure on start-ups.

Figure 3. The addition of a current relay on one leg of the compressor will tell the electronic controller that the compressor is not running and will open a circuit to the safety heater on the oil safety control.

Remember, when the compressor is off, the net oil pressure is 0 psi and the differential pressure switch contacts are closed. The heater in the oil safety controller will not be energized during the off-cycle because it is wired to the line side of the motor starter contacts. When the motor starter contacts are opened, this action takes L2 out of the heater circuit. At start-up, when the motor starter contacts close and the compressor starts, the differential pressure switch contacts will stay closed and the heater will be energized until at least 9 psid of net oil pressure is developed. As mentioned before, this time delay will prevent nuisance trips of the controller at start-ups.

INTERNAL OVERLOADS

If a motor is equipped with both an internal inherent motor protector and an oil safety controller, the oil safety controller may trip due to a motor overheating or overloading problem on some systems. When the internal overload opens, the motor is shut off but the motor starter coil remains energized with contacts closed. This will trip the oil safety controller in a matter of two minutes because of a lack of net oil pressure. However, the addition of a current relay on one of the legs of the compressor will tell the electronic controller that the compressor is not running and will open a circuit to the safety heater on the oil safety controller (Figure 3).

Publication date: 02/01/2010
John Tomczyk is a professor of HVACR at Ferris State University, Big Rapids, Mich., and co-author of Refrigeration & Air Conditioning Technology, sixth edition, published by Delmar Cengage Learning. To order, call 800-648-7450. Tomczyk can be reached by email at tomczykj@ferris.edu.

Recent Articles by John Tomczyk

normly ref sys what is the seting of oil presser need

nayaz
September 30, 2010 5:53 PM
35ton 250 ton350,how much need oil pesser range need


normly ref sys what is the seting of oil presser need

nayaz
September 30, 2010 5:54 PM
35ton 250 ton350,how much need oil pesser range need


You must register or login in order to post comments.

Multimedia

Videos

Photos

Podcasts

NEWSMakers: Greg McAfee

Kyle Gargaro talks with contractor Greg McAfee, owner of McAfee Heating and Air Conditioning and author of It’s My Your Dream: Eight Elements to Guide Your Successful Business. www.gregmcafee.com

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 020612 cover

2012 February 6

Check out the weekly edition of The NEWS today!

TABLE OF CONTENTS SUBSCRIBE

Homeowners who buy online

What do you do with homeowners who buy their HVAC equipment online and want you (the contractor) to install it?
See Poll Results Poll Archive

HVACR INDUSTRY STORE

prof-reference-master-ed-2.gif
DEWALT HVAC/R Professional Reference Master Edition

With more than 500 pages of extensive information on such important topics as refrigeration systems, piping, ductwork, motors, compressors, fans, pumps and more, this "answer book" is one of the most complete HVAC/R professional references available.

More Products

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

The NEWS AHR EXPO PAGE

AHR Expo Message Board Graphic

The NEWS’ AHR Expo page is providing comprehensive coverage of the 2012 AHR Expo, before, during, and after the show. Check out our Daily Reports highlighting the events and announcements from the show in Chicago. Click here for total coverage.

STAY CONNECTED

Facebook Twitter  Linkedin