Quick Facts: TXV Selection and Sensing Bulb Location

TXV Selection

How do I select a TXV for a particular application?
In order to make an accurate thermostatic expansion valve (TXV) selection, it is necessary to match the flow rate (in tons) of the TXV to the tonnage rating of the evaporator coil. The following procedure is recommended:

  • Determine system refrigerant.

  • Determine tonnage rating of the evaporator coil at the operating temperature.

  • Determine liquid refrigerant temperature at the TXV inlet.

  • Calculate the pressure drop across the TXV by subtracting suction (low side) pressure from condensing (high side) pressure. Also subtract pressure drop from a distributor, if one is used. The difference is pressure drop across the TXV.

  • Find the proper extended capacity table in the catalog for the correct refrigerant at the proper evaporator temperature. Then locate the closest pressure drop column and find the nearest flow rate in tons (to the evaporator tonnage). Select the nominal tonnage rated valve.

  • You will have to recalculate the flow rate in tons using the "Liquid Correction Factor Table" if the actual liquid temperature is different from 100 degrees F used as the standard rating point.

    Sensing Bulb Location

    What is the correct position for the TXV sensing bulb?
    The placement of the remote sensing bulb of the TXV onto the suction line is critical to proper TXV performance. The important points to follow are:

  • Clean the suction line near the outlet of the evaporator.

  • The entire length of the sensing bulb must be in contact with the cleaned portion of the suction line.

  • The sensing bulb should be placed several inches downstream of the external equalizer connection.

  • The sensing bulb should be attached at 12 o'clock on any suction line of 7/8-inch diameter or smaller. On lines larger than 7/8-inch diameter, the bulb should be placed at either 4 or 8 o'clock. The bulb should never be placed at 6 o'clock.

  • Always insulate the sensing bulb after installation.

  • A sensing bulb can be installed on a vertical suction line if necessary, but never place the bulb downstream of a trap. Bulb placement before a trap (upstream) is recommended.

    Quick Facts is courtesy of the Flow Controls Division of Emerson Climate Technologies (formerly Alco Controls). For more information, visit www.emersonclimatecontractor.com.

    Publication date: 03/06/2006

  • Did you enjoy this article? Click here to subscribe to The NEWS Magazine

    You must login or register in order to post a comment.

    Multimedia

    Videos

    Image Galleries

    2013 ACCA Conference & IE3 Expo

    Photos from the 2013 ACCA Conference & IE3 Expo in Orlando, Fla.

    Podcasts

    Cade Clark, assistant vice president of government affairs for the Air-Conditioning, Heating & Refrigeration Institute (AHRI), gives a brief overview of the new version of the Shaheen-Portman bill, what AHRI thinks of the energy-efficiency legislation, and how it might affect the HVACR industry if it becomes law.
    More Podcasts

    THE MAGAZINE

    ACHRNEWS

    NEWS 05-20-13 cover

    2013 May 20

    Check out the weekly edition of The NEWS today!

    Table Of Contents Subscribe

    HVAC LEASING

    Some HVAC contractors have introduced leasing programs for consumers. Do you think this is a viable option?
    View Results Poll Archive

    Clear Seas Research

    Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

    DON'T MISS A THING

    Magazine image
     
    Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

    STAY CONNECTED

    facebook icontwitter iconyoutube iconLinkedIn i con