Ice Breaker: Diagnosing a Defective TXV

Thermostatic expansion valves (TXV) are responsible for metering the proper amount of refrigerant into an evaporator coil. When they fail, they either cause the evaporator to be flooded (overfed) or starved (underfed) for refrigerant. This can be observed by measuring the superheat value of the refrigerant as it leaves the evaporator.

A TXV that overfeeds an evaporator can be observed by measuring a lower than normal refrigerant superheat value at the outlet of the evaporator.

A TXV that underfeeds an evaporator can be observed by measuring a higher than normal refrigerant superheat value at the outlet of the evaporator.

Although a defective TXV can result in either a higher or lower refrigerant superheat value, it is definitely not the only possible cause. Before condemning a TXV, all other possible causes should be investigated and ruled out before looking at the TXV.

A defective TXV that results in a starved evaporator can be the result of a lost refrigerant charge within the sensing bulb of the valve. This is due to the fact that the refrigerant charge in its sensing bulb is the opening force of the TXV. When a loss of charge exists, there is not a sufficient force to throttle the valve open to its correct position.

PROCEDURES

The following procedure can be used to see if loss of charge in the bulb of a TXV is the cause of a higher than normal evaporator superheat at the outlet of the evaporator:

• First, if the valve has an external superheat adjustment, turn the adjustment nut counter- clockwise several turns. Allow the system to operate for 10 to 15 minutes and monitor the evaporator’s superheat value. If the evaporator’s superheat has lowered, the valve may just need to be adjusted. Try to further adjust the valve to obtain the correct evaporator superheat value.

• Next, remove the bulb from the suction line and hold it in your hand for several minutes to warm it up. Observe the suction pressure. If the valve has a refrigerant charge, it should open and you should see an increase in the suction pressure.

• If no change in the pressure occurs, it is reasonable to conclude that the TXV is defective and a likely cause is its sensing bulb has lost its refrigerant charge.

• Some TXVs have a power assembly that can be removed and replaced instead of changing the entire TXV. Once the power assembly has been removed, the bulb charge can also be checked. Try depressing the diaphragm with your thumb. If you are able to do this, then the assembly has lost its charge.

If a replacement TXV or power assembly cannot be immediately replaced and the system needs to be operational, one trick of the trade to use as a temporary fix is to install a dime or similar sized solid disk in between the power assembly and the body of the TXV. This will depress the push rods within the TXV and cause the valve opening to go to a more open position. The TXV will now meter more refrigerant in the evaporator but the valve will continue to feed at the same rate.  It is possible now to cause too much refrigerant to enter the evaporator, leading to liquid refrigerant flooding back to the compressor, resulting in compressor damage. When using this trick be sure to understand the pros and the cons of its application. You may fix the immediate problem but cause a more serious issue for you and your customer.

Publication date: 08/02/2010
Joe Marchese is an author and instructor and former HVACR contractor. He can be reached at joe@reachtechnicaltraining.com.

Recent Articles by Joe Marchese

temperary fix for the power assembly with the dime...

delroy willoughby
September 14, 2010 9:05 PM
being that the txv is now metering the freon at a steady pace without the use of the sensing bulb...is it fair to say that the metering is no the same as fix orifice,piston type or cap tube metering divice system and the superheat mothed of charge could be temperary implemented until the power assemble is located and installed....this way the compressor and evaporator will not experience flooding......answer me at...delroyw21@gmail.com


You must register or login in order to post comments.

Multimedia

Videos

Image Galleries

2012 ACCA Conference & Indoor Air Expo

Highlights from the 2012 ACCA Conference & Indoor Air Expo in Las Vegas.

Podcasts

NEWSMakers: Doyle James
Angela Harris sat down with Doyle James, president of Aire Serv to discuss the ins and outs of franchising. Whether you are looking for a franchise opportunity or are content with the way things are, this man has some business tips for every HVAC contractor.
More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 05-21-12 cover

2012 May 21

Check out the weekly edition of The NEWS today!

TABLE OF CONTENTS SUBSCRIBE

Energy management

Do you think home energy management will gain traction in the residential market?
See Poll Results Poll Archive

HVACR INDUSTRY STORE

prof-reference-master-ed-2.gif
DEWALT HVAC/R Professional Reference Master Edition

With more than 500 pages of extensive information on such important topics as refrigeration systems, piping, ductwork, motors, compressors, fans, pumps and more, this "answer book" is one of the most complete HVAC/R professional references available.

More Products

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

Facebook Twitter  Linkedin  YouTube logo