Crankcase Pressure Regulators

A crankcase pressure regulator (CPR) is a common accessory added to many low-temperature refrigeration applications, such as walk-in and reach-in freezers. They are designed to prevent the compressor's motor from overloading when its crankcase pressure rises above its designed working pressure. On many low-temperature applications, this can occur during or after a defrost cycle, or after a normal shutdown period. The CPR is an outlet pressure regulator and will not allow the crankcase pressure to rise above a predetermined level.

Typically the CPR is installed in the suction line between the compressor and the evaporator. Normally, there are no other components installed downstream, between the outlet of the CPR and the compressor. This is to ensure that the outlet of the CPR senses the true crankcase pressure of the compressor.

This type of regulator is not recommended for a system that also uses a maximum operating pressure (MOP) expansion valve. The use of both of these valves on the same system may cause longer pull-down times. This, however, may be overcome if the pressure settings of both valves are sufficiently spread apart.

When using a CPR on a system that is also using a discharge bypass valve for capacity control, the pressure setting of the CPR must be higher than that of the bypass valve.

The typical CPR is a close-on-rise regulator. The outlet pressure (crankcase pressure) of the valve is the closing force within it. The opposing opening force within the valve is an interior spring. These two forces oppose each other to regulate the port size within the valve.

The interior spring is adjustable to apply a maximum opening force. If the pressure applied at the outlet of the valve (crankcase pressure) is above the spring force, the valve will close down. The inlet pressure of the CPR is applied equally to both the underside of its bellows and the top of its valve seat disc, canceling out the effect of the inlet pressure.

The selection of a CPR is based on five system considerations:

1. Refrigerant.

2. Refrigeration capacity.

3. Design suction pressure.

4. Maximum crankcase pressure recommended by the compressor manufacturer.

5. Pressure drop across the valve at design load conditions.

These valves should not be selected based on the size of the suction line, since a manufacturer may use the same line size for many different capacities.

The adjustment of a CPR should be done on start-up, when the evaporator pressure is normally at its highest level. Some valves will have a pressure tap on the inlet port in order to allow a technician to measure the pressure there. When adjusting these valves, the pressure setting should be low enough to protect the compressor, but not so high as to penalize the system's capacity or pull down time. Always refer to the manufacturer's instructions when adjusting these valves.

Joe Marchese is owner of Coldtronics, Pittsburgh. He can be reached at 412-734-4433, www.coldtronics.com, or joe@rhvactools.com.

Publication date: 06/07/2004

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

crankcase pressure regulator

Erick Lema
May 6, 2010
Hey This is Erick Lema from Tanzania. Please help me how to answer the following questions, List the criteria required for selection ot crankcase pressure regulator from manufacturers catalougues. Explain the conditions in operating refrigeration plant that will require the fitting of a crankcare presure regulator to the compressor. List the procedure required to set a crankcase pressure regulator that that will ensure compressor motor overload protection Explain two types of application that will require the use of crankcase pressure protection

freezer

tech
December 3, 2010
I have problem with a reach in freezer,not cooling, temp at 30,low pressure 25psi,high 240psi gas R 404,help

crankcase pressure regulator

John Walter
December 14, 2010
If the adjusting spring on a crankcase pressure regulator is tightened, will the range of refrigerant pressures entering the compressor increase or decrease?

Multimedia

Videos

Image Galleries

2013 ACCA Conference & IE3 Expo

Photos from the 2013 ACCA Conference & IE3 Expo in Orlando, Fla.

Podcasts

Selling Zoning is Easier Than You Might Think

This overview of the benefits of zoning includes tips for selling to consumers and businesses. Tom Jackson discusses options for new construction and retrofit, as well as some ways a residential contractor can get into the light commercial business with zoning products. Speaker: Tom Jackson, CEO, Jackson Systems
More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 05-13-13 cover

2013 May 13

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

HVAC LEASING

Some HVAC contractors have introduced leasing programs for consumers. Do you think this is a viable option?
View Results Poll Archive

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con