Applying Fibrous Glass Duct Wrap

Fibrous glass duct wrap with FSK facing
This article addresses the specific uses, performance characteristics, fire safety, condensation control, and installation recommendations for fibrous glass duct wrap.

USES

Fibrous glass duct wrap insulation is designed for application to the exteriors of commercial and residential sheet metal heating, ventilating, and air conditioning ducts and plenums operating at temperatures between 40°F (4°C) and 250°F (121°C). Duct wrap insulation reduces heat loss or gain through duct walls, conserving energy and controlling moisture condensation. Fibrous glass duct wrap insulations are useful in situations where acoustical performance is not an issue.

DESCRIPTION

Fibrous glass duct wrap insulations are flexible, resilient, light-density blankets of glass fibers factory-laminated to vapor retarder facings. These products are easily cut and fitted to achieve a neat, thermally effective insulation blanket over the exteriors of rectangular, round, oval, or irregularly shaped duct surfaces. They are available in a range of R-values depending on product type, thickness, and density.

FEATURES AND BENEFITS

Condensation control
When installed thickness recommendations are followed, fibrous glass duct wrap insulation installed over sealed sheet metal ducts reduces the likelihood of condensation occurring on the vapor retarder facing, and of moisture damage to ceilings and other interior finishes.

Figure 1. Required R-values to prevent moisture condensation.
Enhanced comfort control
By reducing heat loss or gain through duct walls, conditioned air reaches occupied spaces at temperatures close to design conditions. Central air equipment may therefore be operated at reduced levels, saving energy.

Flexible, easily installed
Fibrous glass duct wrap insulation is easily cut to proper fit. For ease of application, a staple flap is provided by the manufacturers.

Code compliance
Fibrous glass duct wrap insulations meet the physical property requirements of ASTM C 1290 as well as meeting the fire safety requirements of NFPA 90A and 90B including limited combustibility. They also comply with all widely used model codes including ICC, BOCA, CABO, ICBO, and SBCCI.

ASSURED THERMAL PERFORMANCE

When installed in accordance with manufacturers' instructions, fibrous glass duct wraps will provide specified thermal performance as printed on the vapor retarder facing. This is achieved by determining the "stretch-out" cutting dimension required so that, once installed, the duct wrap is not compressed to less than 75 percent of nominal (out-of-package) thickness.

Figure 2. Installing fibrous glass duct wrap insulation to assure full installed R-value.
Commonly available installed R-values as published by manufacturers show fibrous glass duct wrap insulations to perform in the R-value ranges shown in Table 1.

CONDENSATION CONTROL

Figure 1 shows the installed R-values of fibrous glass duct wrap required to prevent moisture condensation on the vapor retarder surface under varying conditions of ambient temperature and relative humidity. Curves are based on cold duct internal temperatures of 55°F (13°C) and no air movement on the external surface.

Note: R-values as required by ASHRAE 90.1-1989 may not be sufficient for condensation control as may be seen in Figures 1 and 2.

INSTALLATION

Fibrous glass duct wrap insulations are installed with facings away from the duct surface. See Figure 2. A stapling flap, prepared at the time of installation, overlapping the insulation and facing at the other end of the piece of duct wrap, is stapled to form a longitudinal seam. Where a vapor retarder is required, the seam is sealed with pressure-sensitive tape. Adjoining duct wrap sections are similarly stapled and sealed using the facing flap on one edge of the duct wrap as produced at the factory. Seams and joints may also be sealed with mastic and glass fiber fabric.

For complete installation details, consult the manufacturer or National Commercial and Industrial Insulation Standards, 1999, 5th Edition, Midwest Insulation Contractors Association (MICA).

Dimensions in Table 2 are established by ASTM C 1290 and should be used when cutting duct wrap insulation so that, once installed, it is not compressed to less than 75 percent of nominal (out-of-package) thickness.

Reprinted with permission from the North American Insulation Manufacturers Association's (NAIMA's) Insulation Facts #66: Fibrous Glass Duct Wrap. NAIMA is the association for North American manufacturers of fiberglass, rock wool, and slag wool insulation products. For more information, visit www.naima.org

Publication date: 04/03/2006

You must register or login in order to post comments.

Multimedia

Videos

Image Galleries

Podcasts

NEWSMakers: Greg McAfee

Kyle Gargaro talks with contractor Greg McAfee, owner of McAfee Heating and Air Conditioning and author of It’s My Your Dream: Eight Elements to Guide Your Successful Business. www.gregmcafee.com

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 020612 cover

2012 February 6

Check out the weekly edition of The NEWS today!

TABLE OF CONTENTS SUBSCRIBE

Homeowners who buy online

What do you do with homeowners who buy their HVAC equipment online and want you (the contractor) to install it?
See Poll Results Poll Archive

HVACR INDUSTRY STORE

prof-reference-master-ed-2.gif
DEWALT HVAC/R Professional Reference Master Edition

With more than 500 pages of extensive information on such important topics as refrigeration systems, piping, ductwork, motors, compressors, fans, pumps and more, this "answer book" is one of the most complete HVAC/R professional references available.

More Products

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

The NEWS AHR EXPO PAGE

AHR Expo Message Board Graphic

The NEWS’ AHR Expo page is providing comprehensive coverage of the 2012 AHR Expo, before, during, and after the show. Check out our Daily Reports highlighting the events and announcements from the show in Chicago. Click here for total coverage.

STAY CONNECTED

Facebook Twitter  Linkedin