the NEWS
Advertisement:
HVACR Directory | HVACR In-Depth | Extra Edition | Learning Center | Editorial Blogs | Product Gallery
  Home
  About the NEWS
  Subscription Info
  e-Newsletters
  Contact Us
  Resources
  HVACR In-Depth
  Archived Editorial
  Blogs
  Career Center - Employers
  Career Center - Job Seekers
  Columns
  Distributor Corner
  Calendar of Events
  HVACR Directory
  Industry Links
  Learning Center
  Letters
  Manufacturer Reports
  Regional Reports
  Reprints
  Survey Says
  Training Track
  Webinars
  AEC Store
  Market Research
  Extra Edition
  HVACR Forum
  Legal forum
  Business Management
  Dot Comment
  Energy Matters
  Features
  Newsline
  People
  Service Hotline
  Service & Maintenance
  Technical
  Advertising
  Ad Index
  Media Kit
  Submit Press Release
  Services
  Classifieds
  Digital Edition
spacer
Search in: EditorialProductsCompanies
Ice Breaker: Evaporator Superheat Explained
by Joe Marchese
June 1, 2009

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



Advertisement:

For more info, click here
Generally the term “superheat” is used to describe the state of a refrigerant. Refrigerant in its vapor state is said to be superheated because it is at a temperature above its saturation (boiling point) temperature.

The degree at which a refrigerant is superheated is the temperature difference between its actual temperature and its saturation temperature. For example, if the saturation temperature of a refrigerant is 20˚F and its actual temperature is 30˚, then the refrigerant is said to be superheated by 10˚. This could be also stated as “the refrigerant has 10˚ of superheat.”

In a properly operating system, the refrigerant will be in a superheated state from the last section of the evaporator to the first section of the condenser. Technicians can measure the superheat condition anywhere along this path. One common location is at the outlet of the evaporator. This is typically referred to as the “evaporator’s superheat.”

Measuring the evaporator’s superheat value is an important part of analyzing a system’s performance. If a lower than normal value is measured, too much refrigerant is entering the evaporator for the heat load. Many technicians refer to this as a “flooded evaporator.” If a higher than normal value is measured, too little refrigerant is entering the evaporator for the heat load. Technicians generally refer to this as a “starved evaporator.”

Part of effectively troubleshooting a refrigeration system should always include looking at the performance of the evaporator. This means measuring the evaporator’s superheat value. If this is overlooked, the true system problem can be misdiagnosed.

For example, a system with a lower than normal suction pressure can be the result of several problems, two of which are a low refrigerant charge and a lack of airflow across the evaporator. The difference between these two problems can be seen by looking at the evaporator’s superheat. A low refrigerant charge will have a higher than normal evaporator superheat value. Lack of airflow across the evaporator will cause the evaporator’s superheat to be lower than normal.


PROCEDURE

Below is a procedure for calculating an evaporator’s superheat value:

1. First, measure the pressure of the refrigerant at the outlet of the evaporator. If this is not possible, measure the pressure at the next closest location (usually at the inlet of the compressor) and then estimate the pressure at the outlet of the evaporator by estimating the pressure drop from the measured location to the outlet of the evaporator. For many systems, a 2-psig pressure drop can be assumed from the outlet of the evaporator to the inlet of the compressor.

2. Next, convert the measured pressure to its saturation temperature using a pressure-temperature chart.

3. Then, measure the temperature of the refrigerant at the outlet of the evaporator. This is done by measuring the refrigerant line temperature, which is assumed to be the same as the refrigerant passing through.

4. Finally, subtract the measured refrigerant temperature from the converted saturation temperature. The difference is the superheat value of the refrigerant.


AN EXAMPLE

For example, let’s calculate the evaporator superheat for a walk-in cooler using HFC-134a refrigerant.

1. First, we measured a pressure of 18-psig at the inlet of the compressor (there are no valves at the outlet for the evaporator). Assuming a 2-psig pressure drop across the suction line, we have a 20-psig pressure at the outlet of the evaporator.

2. Next, using a pressure-temperature chart, we determine the saturation temperature to be 22˚.

3. Then, we measure a line temperature of 30˚.

4. Finally, we subtract 30˚ from 22˚, for a superheat value of 8˚.

What is the correct superheat value of the refrigerant leaving an evaporator? It is based on the system’s application and the manufacturer’s design. As a rule of thumb, medium-temperature systems will generally have a superheat of 8˚ to 10˚ and low-temperature applications 4˚ to 6˚. But again, always check with the system’s manufacturer for the recommended values.

Technicians should include measuring the evaporator superheat when diagnosing a system problem. Failing to include this measurement can lead to misdiagnosing the true system problem.

Publication date: 06/01/2009


Joe Marchese
is an author and instructor and former HVACR contractor. He can be reached at joe@rhvactools.com. His Website is www.rhvactools.com.

|PrintEmail
  Comments (2)Post a Comment
Title: superheat


very useful
thanks


Title: icing on compressor body when ambient temperature is too low?


the airconditioning unit why it is icing on the compressor body and entire suction line.a


 

No HTML or BBCode in comments please.
 


Did you enjoy this article? Click here to subscribe to the magazine.








© 2010 BNP Media. All rights reserved. | Privacy Policy