|
Advertisement:
For more info, click here
|
Generally the term “superheat” is used to describe the state of a refrigerant. Refrigerant in its vapor state is said to be superheated because it is at a temperature above its saturation (boiling point) temperature.
The degree at which a refrigerant is superheated is the temperature difference between its actual temperature and its saturation temperature. For example, if the saturation temperature of a refrigerant is 20˚F and its actual temperature is 30˚, then the refrigerant is said to be superheated by 10˚. This could be also stated as “the refrigerant has 10˚ of superheat.”
In a properly operating system, the refrigerant will be in a superheated state from the last section of the evaporator to the first section of the condenser. Technicians can measure the superheat condition anywhere along this path. One common location is at the outlet of the evaporator. This is typically referred to as the “evaporator’s superheat.”
Measuring the evaporator’s superheat value is an important part of analyzing a system’s performance. If a lower than normal value is measured, too much refrigerant is entering the evaporator for the heat load. Many technicians refer to this as a “flooded evaporator.” If a higher than normal value is measured, too little refrigerant is entering the evaporator for the heat load. Technicians generally refer to this as a “starved evaporator.”
Part of effectively troubleshooting a refrigeration system should always include looking at the performance of the evaporator. This means measuring the evaporator’s superheat value. If this is overlooked, the true system problem can be misdiagnosed.
For example, a system with a lower than normal suction pressure can be the result of several problems, two of which are a low refrigerant charge and a lack of airflow across the evaporator. The difference between these two problems can be seen by looking at the evaporator’s superheat. A low refrigerant charge will have a higher than normal evaporator superheat value. Lack of airflow across the evaporator will cause the evaporator’s superheat to be lower than normal.
By: gopakumar
Posted: June 23, 2009 8:25 PM
thanks
By: ricardo a. velasco
Posted: March 4, 2010 12:24 PM