An Outline for Successful Fan Selections
June 18, 2007
This article outlines the considerations involved to properly
select, apply, and control fans. Emphasis is placed upon matching the fan
equipment to the requirements of the system from several different
perspectives. However, specific fan design and construction details are not
within the scope of this article.
An improperly selected and applied piece of equipment can be
rendered completely ineffective if the application itself is not properly
defined right at the beginning. It is imperative to address each and every item
listed in the following section.
DEFINE THE APPLICATION
• What is the application and what is the fan supposed to do?
• How many systems are there and are they interdependent?
• How many fans per system?
• Where is the fan equipment located (inside, outside, next to an office, on the ground or several stories up in a building)? If outside, what are the ambient conditions?
• What space limitations exist? Is there adequate space for maintenance and removal of parts?
• What facility limitations exist in the form of weight, electrical capability, noise, or vibration?
• What fan orientation is best suited for the application?
• What fan arrangement is best suited for the application?
• Are there any leakage requirements for the fan or ductwork?
• Are there any sound limitations including casing radiated or duct breakout noise?
• Are there any storage requirements? If so, how long and under what conditions?
• What are the cost of electricity and any support functions required?
PERFORMANCE AND SYSTEM DUTY CYCLE
|
|
| Figure 1. System duty cycle. |
|
In order to analyze and make fan and control selections it is
necessary to define the system duty cycle. All of the design and operating
points must be defined and how long the system operates at each point. This
should include present as well as future ratings.
The following information for each operating point is necessary:
• Volume flow
rate;
• Inlet and
outlet static pressures;
•
Temperature: design, operating, and rate of change;
• Gas
composition if other than air;
• Gas
contaminants taking into account erosion and corrosion;
• Elevation
and barometric pressure or gas density;
• Single fan,
series or parallel operation;
• Method of
control.
It is also necessary to create a system duty cycle plot if
several performance points are given. That is, plot all operating points on a
single graph at a common density. By overlaying the fan performance curve
information, it is easy to evaluate the basic fan selection along with the
control characteristics. All operating points in the system duty cycle must
fall within the fan’s performance envelope. If any operating points fall
outside of the envelope, those points will not be realized. This concept is
illustrated in Figure 1.
LIFE CYCLE CONSIDERATIONS
The overall effectiveness of the fan/system selection should be
evaluated taking each of the following into account:
• Initial
cost — What is the purchase price and cost of installation?
• Operating
cost — What is the total cost per year to operate the fan, accessories, and any
support equipment?
• Maintenance
— Is maintenance costly and frequent? And, is the equipment accessible for ease
of maintenance?
• Frequency
of repair and downtime — What is the reliability of the equipment and the cost
of downtime?
• Spare parts
— Are spare parts expensive and readily available? Must an inventory of spare
parts be maintained?
• System
availability — What percentage of time must the system be operable? There may
be the requirement to have a "standby fan."
• Expected
life — What is the expected life of the equipment before it is to be replaced?
THE BASIC FAN SELECTION
The fan type and its performance characteristics influence the
basic fan selection. The fan and system must be compatible both structurally as
well as from a performance standpoint. For any one performance point, there are
many different fans which will satisfy that rating. However, based upon any one
set of priorities such as fan size, efficiency, motor size, etc., there is only
one best fan for that application.
As an example, for a single operating point of 60,000 cfm at 7.0
inches total pressure at a density of 0.075 lbs/cf (70 degrees), several
different fans will satisfy that rating. The possible selections are tabulated
in the chart above taking into account impeller size, operating speed,
horsepower, relative selling price, and recommended motor size.
Depending upon which priority is chosen with regards to
acceptability, the optimum fan selection will change. Based upon selling price
the 48 inch axial fan would be selected. Based upon operating costs, the 48
inch axial or the 60 inch backwardly inclined fan could be selected. If there
was dust in the airstream, the radial tipped fan might be selected taking into
account erosion. The optimum fan to satisfy the future rating would be the 48
inch axial utilizing a blade angle change since the centrifugals would have to
be increased in speed 16 percent with a corresponding horsepower increase of 58
percent. The motor for the 48 inch axial would simply require better initial
insulation so as to handle the increased power.
FAN SELECTION AND RATING POINT LOCATION
|
|
| Figure 2. Rating point location. |
|
A very important concept is the relationship between size and the
rating point location on the fan curve. The generic performance curve for the
three backwardly curved fans from the chart is shown in Figure 2. This figure
illustrates that the relative position of the rating point on the fan curve
changes with a change in fan size for a particular rating. As can be seen, the
smaller the fan size used to satisfy a rating, the faster it must run and the
farther it will be to the right on the fan curve. In general, it will also be
less efficient. It will be louder and wear out faster. This concept is
important when considering types of control and fan stability when operation is
near peak pressure.
FAN CONTROL AND MOVING THE OPERATING POINT
|
|
| Figure 3. Moving the operating point. |
|
The following is intended to provide an understanding of the
interdependence of the fan and its control with how effectively the system’s
performance envelope is satisfied. The fan control method is the means by which
the fan/system operating point is manipulated in order to change the desired
flow/pressure somewhere else in the system. If you change the system
resistance, the operating point will move along the fan curve. Fans equipped
with an outlet damper, opposed bladed inlet box damper or a system damper are
examples. If you change the fan performance capability, the operating point
will move along the established system resistance curve. By having the ability
to adjust both the system and the fan performance, the operating point can be
moved to almost any desired position under the fan curve. This is illustrated
in Figure 3. Controls which move the operating point along the system curve
include variable inlet vanes, parallel bladed inlet box dampers, blade angle
changes on axial fans, and the many techniques used to change fan speed. It is
extremely important to know the individual performance characteristics for each
type of fan control.
FAN CONTROL CRITERIA
Having the ability to move the operating point creates a whole
new set of considerations. These range from performance to physical equipment
limitations. Most of these considerations are listed below. Depending upon the
installation, some are more important than others; however, all should be
considered.
•
Turndown/leakage
• Sensitivity
to change/stability/transients
•
Repeatability
• Reliability
• Efficiency
expected
• Sound
considerations
• Structural
considerations
•
Environmental considerations
• Interface
considerations to computer control
SUMMARY
This article has attempted to outline the major considerations
which should be included in any fan and control selection. This can act as a
form of checklist or reminder for those who are not involved in selecting fans
on a regular basis. It does not guarantee a successful application, but it goes
a long way in eliminating many of the common problems associated with a lack of
information and communication up front in the selection process.
Reprinted with permission from Greenheck’s Engineering
Update, Volume IV Issue III. For more information, visit
www.greenheck.com.
Publication
date: 06/18/2007
|