the NEWS
Advertisement:
HVACR Directory | Extra Edition | Learning Center | Editorial Blogs | Product Gallery
  Home
  About the NEWS
  Subscription Info
  e-Newsletters
  Contact Us
  Resources
  Archived Editorial
  Blogs
  Career Center - Employers
  Career Center - Job Seekers
  Columns
  Distributor Corner
  Calendar of Events
  HVACR Directory
  Industry Links
  Learning Center
  Letters
  Manufacturer Reports
  Regional Reports
  Reprints
  Survey Says
  Training Track
  Webinars
  AEC Store
  Market Research
  Extra Edition
  HVACR Forum
  Legal forum
  Business Management
  Dot Comment
  Energy Matters
  Features
  Newsline
  People
  Service Hotline
  Service & Maintenance
  Technical
  Advertising
  Ad Index
  Media Kit
  Submit Press Release
  Services
  Classifieds
  Digital Edition
  Post Cards
Search in: EditorialProductsCompanies
Quick Facts: TXV Selection and Sensing Bulb Location

March 6, 2006

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



TXV Selection



How do I select a TXV for a particular application?
In order to make an accurate thermostatic expansion valve (TXV) selection, it is necessary to match the flow rate (in tons) of the TXV to the tonnage rating of the evaporator coil. The following procedure is recommended:

  • Determine system refrigerant.

  • Determine tonnage rating of the evaporator coil at the operating temperature.

  • Determine liquid refrigerant temperature at the TXV inlet.

  • Calculate the pressure drop across the TXV by subtracting suction (low side) pressure from condensing (high side) pressure. Also subtract pressure drop from a distributor, if one is used. The difference is pressure drop across the TXV.

  • Find the proper extended capacity table in the catalog for the correct refrigerant at the proper evaporator temperature. Then locate the closest pressure drop column and find the nearest flow rate in tons (to the evaporator tonnage). Select the nominal tonnage rated valve.

  • You will have to recalculate the flow rate in tons using the “Liquid Correction Factor Table” if the actual liquid temperature is different from 100 degrees F used as the standard rating point.


  • Sensing Bulb Location

    What is the correct position for the TXV sensing bulb?
    The placement of the remote sensing bulb of the TXV onto the suction line is critical to proper TXV performance. The important points to follow are:

  • Clean the suction line near the outlet of the evaporator.

  • The entire length of the sensing bulb must be in contact with the cleaned portion of the suction line.

  • The sensing bulb should be placed several inches downstream of the external equalizer connection.

  • The sensing bulb should be attached at 12 o’clock on any suction line of 7/8-inch diameter or smaller. On lines larger than 7/8-inch diameter, the bulb should be placed at either 4 or 8 o’clock. The bulb should never be placed at 6 o’clock.

  • Always insulate the sensing bulb after installation.

  • A sensing bulb can be installed on a vertical suction line if necessary, but never place the bulb downstream of a trap. Bulb placement before a trap (upstream) is recommended.

    Quick Facts is courtesy of the Flow Controls Division of Emerson Climate Technologies (formerly Alco Controls). For more information, visit www.emersonclimatecontractor.com.

    Publication date: 03/06/2006