the NEWS
Advertisement:
HVACR Directory | Extra Edition | Learning Center | Editorial Blogs | Product Gallery
  Home
  About the NEWS
  Subscription Info
  e-Newsletters
  Contact Us
  Resources
  Archived Editorial
  Blogs
  Career Center - Employers
  Career Center - Job Seekers
  Columns
  Distributor Corner
  Calendar of Events
  HVACR Directory
  Industry Links
  Learning Center
  Letters
  Manufacturer Reports
  Regional Reports
  Reprints
  Survey Says
  Training Track
  Webinars
  AEC Store
  Market Research
  Extra Edition
  HVACR Forum
  Legal forum
  Business Management
  Dot Comment
  Energy Matters
  Features
  Newsline
  People
  Service Hotline
  Service & Maintenance
  Technical
  Advertising
  Ad Index
  Media Kit
  Submit Press Release
  Services
  Classifieds
  Digital Edition
  Post Cards
Search in: EditorialProductsCompanies
Troubleshooting Challenge: A Comfort Cooling System That’s Not Gettin’ Down
by Jim Johnson
May 4, 2009

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



Enlarge this picture
Figure 1. (Click on the image for an enlarged view.)
This time around we have a customer who has called to say that it’s warmer than it should be in their home. “It’s just not as comfortable as it used to be,” is the way they’re explaining it. When you arrive you find a nine-year-old package unit, and you determine in a short time that, electrically, everything is as it should be, which means that what you have is a unit that is running, but is not cooling enough.

After carefully checking airflow over the indoor coil and making sure that it’s not dirty, and that there isn’t a clogged filter problem, you turn your attention to the refrigeration system. Since this R-22 unit is equipped with a fixed-bore metering device (multiple capillary tube) you implement the use of the superheat method to check the charge. In order to accomplish your evaluation, you employ the chart shown in Figure 1, and plug in the following temperature readings you obtained.

• Air entering the indoor coil: 68°F

• Air entering the outdoor coil: 90°


Enlarge this picture
Figure 2. (Click on the image for an enlarged view.)
As your next step, you check the low-side operating pressure of the refrigeration system and find it to be 61.5 psig, which you plug into the chart in Figure 2 to convert it to a temperature. As your last step in the process, you measure the suction line temperature and find it to be 55°.

With your evaluation tests complete, you proceed to your diagnosis.

Your three-part troubleshooting question:

1. What was the superheat reading supposed to be for this unit?

2. What was the actual superheat of the unit?

3. What is your diagnosis?

Compare your answers with ours by clicking here.

Publication date: 05/04/2009


Jim Johnson
is the director of training for Technical Training Associates, a Tucson, Ariz.-based firm that provides HVACR technician training DVDs/videos, E-books, and workshops. For more information, call 520-625-6847 or visit www.technicaltrainingassoc.com.