Troubleshooting Challenge: A Gas Furnace That's Heating Intermittently

March 9, 2009
/ Print / Reprints /
ShareMore
/ Text Size+
Figure 1. (Click on the image for an enlarged view.)

The customer in this particular situation is somewhat savvy about their 12-year-old gas furnace, so when they call for help, they tell you that when things got very cold in the house, they disconnected the power supply to the unit, and then, after turning the 120V service switch back on, the furnace operation seemed normal and the house got warm “for a day or so.” But, the failure repeated, and they again followed the reset procedure which got the unit operating again. And, even though they had heat again, they called for service.

When you arrive, you find the furnace running and the indoor temperature at an acceptable level. Your evaluation of the equipment includes checking the flame sensor (OK), checking the drain trap, and checking the fuel pressure at both inlet and outlet of the gas valve (also OK). As your next step, you go through the reset procedure by disconnecting the power supply for the appropriate time frame and then turning the service switch back on, expecting the blower motor to run for 30 seconds on a system restart since that’s considered normal operation for this particular unit after a power interruption.

But, the blower doesn’t start until you hand-spin the squirrel cage. At this point, you’re leaning toward the diagnosis that the motor is failing (see the partial diagram in Figure 1), so you double-check two things: A test at the motor leads from the printed circuit board that shows 120 volts, and a check of the run capacitor with your digital meter that shows a reading of 2.5 microfarads.

Your troubleshooting question: Which component was replaced, eliminating the intermittent equipment operation failures?

Compare your answer with ours by clicking here.

Publication date: 03/09/2009

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Recent Articles by Jim Johnson

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

Kyle Gargaro, editor-in-chief of The NEWS, hosted the 2014 ACCA CEO Forum. At the event, six well-known, highly respected company executives, Gary Michel, Ingersoll Rand/Trane; Chris Nelson, Carrier Corp.; Chris Peel, Rheem Mfg. Co.; Rod Rushing, Johnson Controls; Brent Schroeder, Emerson Climate Technologies; and Doug Young, Lennox; provided individual industry outlooks and fielded questions directly from attending contractors. Listen to the entire event on the NEWSMakers podcast. Posted on April 14.

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-14-14 cover

2014 April 14

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con