Motor Troubleshooting: Failure To Rotate

As we mentioned at the end of last month's motor quiz, we are focusing on HVACR motor troubleshooting specifics. This month we will discuss troubleshooting if the motor isn't rotating; next month we will examine how to troubleshoot a motor if it isn't coming fully up to speed or accelerating.

What We Have Here Is A Failure To Rotate

The first tool you need to use is one of your most important: your ears. Is the motor humming?

If the motor hums, the problem could be:

  • A bad run capacitor - Check the capacitor or replace it with a known good one of the same microfarad (MFD) rating. Consider using a higher voltage rating.

  • A bad start capacitor - Check the capacitor or replace with a known good one of the same MFD rating. Look for oil leaks.

  • If it's in a rapid start-stop application, get a motor or capacitor designed for rapid starts and stops.

  • A bad starting switch - That is, if you spin the shaft, the motor will rotate. Replace the motor.

  • One winding is open - Again, if you spin the shaft, the motor will rotate. Replace the motor.

  • Bad bearings - You can move the motor shaft side to side. Replace the motor.

  • Improper connections - Verify that the motor connections are correct; check amps after you make any corrections, but be aware that you may need to replace the motor anyway.

    If the motor makes no sound, carefully measure power to motor.

  • No power to the motor could mean there is a blown fuse or circuit breaker. Verify that the fuse or circuit breaker size is correct. The size should be 3 X the nameplate amps for a fuse; 7 X the nameplate amps for an instantaneous breaker; 2.5 X the nameplate amps for a time delay breaker.

    If it's the correct size, replace the motor.

  • If there is power to the motor, and the motor is cool, check for open leads or an open winding. You may be able to see winding damage on inspection. It can be verified with your multimeter; you should read continuity between all of the leads.

    If there is no continuity, replace the motor.

  • If the thermal overload tripped, the motor will be hot to the touch. Wait for the motor to cool down! When the protector resets (or is reset), look for other symptoms.

    Next month Tech Tips will look at troubleshooting a motor that will not come up to speed or accelerate.

    For more information, click on the Emerson Climate Technologies logo above.

  • Did you enjoy this article? Click here to subscribe to The NEWS Magazine

    You must login or register in order to post a comment.

    Multimedia

    Videos

    Image Galleries

    2013 ACCA Conference & IE3 Expo

    Photos from the 2013 ACCA Conference & IE3 Expo in Orlando, Fla.

    Podcasts

    Cade Clark, assistant vice president of government affairs for the Air-Conditioning, Heating & Refrigeration Institute (AHRI), gives a brief overview of the new version of the Shaheen-Portman bill, what AHRI thinks of the energy-efficiency legislation, and how it might affect the HVACR industry if it becomes law.
    More Podcasts

    THE MAGAZINE

    ACHRNEWS

    NEWS 05-20-13 cover

    2013 May 20

    Check out the weekly edition of The NEWS today!

    Table Of Contents Subscribe

    HVAC LEASING

    Some HVAC contractors have introduced leasing programs for consumers. Do you think this is a viable option?
    View Results Poll Archive

    Clear Seas Research

    Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

    DON'T MISS A THING

    Magazine image
     
    Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

    STAY CONNECTED

    facebook icontwitter iconyoutube iconLinkedIn i con