Ice Breaker: How Automatic Expansion Valves Work

The automatic expansion valve (AXV) is similar in construction and appearance to the commonly used thermostatic expansion valve (TXV). However, the metering devices operate much differently.

The AXV is a constant pressure regulator. It is designed and constructed to maintain a constant evaporating pressure. The flow of the refrigerant into the evaporator is based on the pressure of the refrigerant in the evaporator. As the pressure in the evaporator decreases, the valve opens and allows more refrigerant to flow through it. As the pressure increases, the valve closes and allows less refrigerant to flow through it.



HOW IT WORKS

An AXV consists of a diaphragm, an adjustable spring, and a needle valve. The diaphragm controls the operation of the needle valve. The adjustable spring is placed on top of the diaphragm and acts to open the needle valve.

The opposing pressure that acts to close the needle valve is the pressure of the refrigerant in the evaporator. As the pressure in the evaporator drops, the spring pressure overcomes the pressure on the underside of the diaphragm and moves the needle valve to a more open position, allowing more refrigerant into the evaporator.

As the refrigerant pressure increases in the evaporator, it imposes a higher pressure on the underside of the diaphragm, which overcomes the spring tension and moves the needle valve to a more closed position, reducing the flow of refrigerant into the evaporator. The pressure applied by the spring can be adjusted to allow for different maximum evaporating pressures. Normally, an adjustment screw on top of the valve body is connected to the spring inside the dome of the valve.



CONSTANT LOADS

This type of metering device is applied similarly to the capillary tube. It should only be used on systems with a fairly constant heat load. Because it does not control the amount of superheat at the outlet of the evaporator, it does not work well on systems with dramatic changes in heat loads. In fact, dramatic changes in heat loads cause problems with the system.

If a high heat load is placed on the evaporator, the valve reduces the refrigerant flow into the evaporator instead of feeding more refrigerant. The evaporator pressure will rise - and because the closing force of the needle valve is the pressure of the refrigerant in the evaporator, it will move to a more closed position, restricting the flow of refrigerant into the evaporator.

During low heat load conditions, the valve will open more, allowing more refrigerant into the evaporator, when it should be restricting flow into the evaporator. On low heat load conditions, the pressure in the evaporator will drop. The spring pressure will keep the valve in a full-open position to feed more refrigerant into the evaporator.

One final note: An AXV looks similar to a TXV but operates much differently. It’s important not to confuse the two while servicing a refrigeration system. An easy way to tell the difference is to look at the top of the valve. If it has an adjustable screw on top of the diaphragm, it’s an AXV. If it has a capillary tube and sensing bulb connected to the top of the diaphragm, it’s a TXV.

Publication date: 02/02/2009

Joe Marchese is an author and instructor and former HVACR contractor. He can be reached at joe@reachtechnicaltraining.com.

Recent Articles by Joe Marchese

above article

Dan
March 11, 2010 2:06 AM
Hey Joe! It would help if you included a PICTURE!


You must register or login in order to post comments.

Multimedia

Videos

Image Galleries

Podcasts

NEWSMakers: Greg McAfee

Kyle Gargaro talks with contractor Greg McAfee, owner of McAfee Heating and Air Conditioning and author of It’s My Your Dream: Eight Elements to Guide Your Successful Business. www.gregmcafee.com

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 020612 cover

2012 February 6

Check out the weekly edition of The NEWS today!

TABLE OF CONTENTS SUBSCRIBE

Homeowners who buy online

What do you do with homeowners who buy their HVAC equipment online and want you (the contractor) to install it?
See Poll Results Poll Archive

HVACR INDUSTRY STORE

prof-reference-master-ed-2.gif
DEWALT HVAC/R Professional Reference Master Edition

With more than 500 pages of extensive information on such important topics as refrigeration systems, piping, ductwork, motors, compressors, fans, pumps and more, this "answer book" is one of the most complete HVAC/R professional references available.

More Products

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

The NEWS AHR EXPO PAGE

AHR Expo Message Board Graphic

The NEWS’ AHR Expo page is providing comprehensive coverage of the 2012 AHR Expo, before, during, and after the show. Check out our Daily Reports highlighting the events and announcements from the show in Chicago. Click here for total coverage.

STAY CONNECTED

Facebook Twitter  Linkedin