Chillers, Ice Storage Keep Schools Open In North Carolina

"Our goal was never again to dismiss school because of classroom heat." Bill Gilbert had an ambitious mission, because as energy director for the Johnston County school district near Raleigh, N.C., he had experienced classes being frequently dismissed because school buildings were simply too hot.

Johnston County operates 32 air conditioned schools and additional administrative buildings. It is one of the fastest-growing school districts in the state, with an enrollment of 23,000, and adding over 1,000 students each year. Because of this growth, Gilbert looked for standardized energy solutions that could be applied in multiple buildings to save money on maintenance supplies and spare parts. As at most districts, holding down operating and energy costs is a priority.

But as the pace of school construction was accelerating, the need for improved classroom comfort was emphasized. The district's energy team and its construction department worked with Trane to standardize a school design featuring air-cooled screw chillers and ice storage tanks as an optimum solution for school cooling.

The district's typical elementary school encompasses 82,000 square feet and is equipped with two 90-ton Trane air cooled Series R™ screw chillers and six Calmac Icebank™ ice storage tanks. Middle schools of 111,000 square feet typically have two 125-ton chillers and nine ice tanks. The new high school is 260,000 square feet and has three Trane air-cooled chillers and 12 Calmac tanks.

Gilbert said the air-cooled chiller with ice storage makes good sense. "We like the Trane Series R air-cooled chillers because of their reliability, and that we don't have to deal with condenser water. No water treatment or tower maintenance is needed, so this approach also eliminates water and sewer charges. Unattended operation is also more practical."

The primary advantage of ice storage is that it reduces electric demand charges, and allows the schools to qualify for a favorable time-of-use electric energy rate from their electric supplier. The chillers operate on a primary loop, with a 25 percent glycol solution at 24 degrees F going to the ice storage tanks.

Normally, the schools make ice during the nighttime hours. In the morning, the chillers are used directly — through a Polaris heat exchanger — from 7:00 a.m. until 9:00 or 9:30 a.m., when the system is switched over to use the stored ice, which normally lasts through the day.

Chilled water from the secondary loop is circulated to air-handling units (AHUs) and fancoils throughout the building. The system's Trane Modular Climate Changer™ AHUs are located on mechanical platforms in the buildings for distribution of air to the larger spaces such as hallways, gyms, and the cafeteria. These AHUs are directly ducted to ceiling diffusers in these large areas.

Classrooms are served by individual AHUs that have thumb-wheel classroom controls. The classrooms are given a range from 68 to 76 degrees. The AHUs typically receive chilled water at temperatures ranging from 46 down to 41 degrees, depending on outdoor temperatures. For space heating and for air tempering purposes, the AHUs receive hot water from a gas-fired boiler. All of the AHUs are on a four-pipe system.

Gilbert noted that with the tight construction in newer school buildings, ventilation and humidity management are increasingly important. Most schools use humidistats, which are set to initiate air handler operation in a dehumidifying mode when rh levels exceed 60 percent.

Gilbert said the economic benefits of ice storage are impressive. "We have found simple project paybacks of as little as two years. Over the anticipated life of the school of 40 years or more, we believe the total savings could be as great as $1.2 million in a typical middle school."

Gilbert points out that the largest portion of the savings comes from reduced electric energy and demand charges. "Another element is that the chiller size can be smaller than if you had no storage, which partially offsets the cost of the ice storage system."

With an average of two new schools being built every year, the scale of ice storage increases every year. The school system today has met one of its top energy goals, and has demonstrated its commitment to keeping classrooms occupied every day of the school year.

Publication date: 05/05/2003

You must register or login in order to post comments.

Multimedia

Videos

Image Galleries

2012 ACCA Conference & Indoor Air Expo

Highlights from the 2012 ACCA Conference & Indoor Air Expo in Las Vegas.

Podcasts

NEWSMakers: Doyle James
Angela Harris sat down with Doyle James, president of Aire Serv to discuss the ins and outs of franchising. Whether you are looking for a franchise opportunity or are content with the way things are, this man has some business tips for every HVAC contractor.
More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 05-21-12 cover

2012 May 21

Check out the weekly edition of The NEWS today!

TABLE OF CONTENTS SUBSCRIBE

Energy management

Do you think home energy management will gain traction in the residential market?
See Poll Results Poll Archive

HVACR INDUSTRY STORE

prof-reference-master-ed-2.gif
DEWALT HVAC/R Professional Reference Master Edition

With more than 500 pages of extensive information on such important topics as refrigeration systems, piping, ductwork, motors, compressors, fans, pumps and more, this "answer book" is one of the most complete HVAC/R professional references available.

More Products

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

Facebook Twitter  Linkedin  YouTube logo