SELECTING A BUCK-BOOST TRANSFORMER
|
|
| Table 1. Available buck-boost transformers. (Click on the table
for an enlarged view.) |
|
The following information should be
confirmed for the application:
•
Line Voltage —
Confirm that the supply/input voltage is 277.
•
Frequency —
Input power supply frequency must match the equipment — either 50 or 60 Hertz
(Hz). This article is based on only applications of 60 Hz.
•
Phase —
The supply/input power phasing must be the same as the equipment requirements.
This article is based on single-phase applications.
•
Load KVA or Load Amps —
You only need to know one or the other. This information usually can be found
on the unit nameplate(s). On United CoolAir equipment the minimum circuit
ampacity (MCA) should be used as the load amps.
The transformer is used to buck
(decrease) the incoming power supply from 277 volts down to the 230 volts
required for the unit. Table 1 lists the buck-boost transformers available from
United CoolAir.
Read down the column until you see a
KVA or amp value that is just higher than the equipment to be operated.
|
|
| Figure 1. Transformer connection diagram. (Click
on the diagram for an enlarged view.) |
|
Connect the transformer according to
the diagram shown in Figure 1. Only one transformer is required in the wiring
diagram for each power supply to the equipment.
CAUTION:
Do not make connections other than those shown. The transformer must be as
large (KVA) as the load it must operate. Never exceed the nameplate rating as
this could result in overheating, reduced life expectancy, or worst case, fire.
Notes:
1. The symbol
“O” used in this connection diagram illustrates where to field install an
overcurrent protective device (typically a fuse or circuit breaker) when one
input conductor is grounded and the other input conductor is ungrounded.
2. When both
input conductors are ungrounded an overcurrent protection device is required to
be installed in series with each input conductor.
3. For
additional information refer to the National Electrical Code, Article 450-4.
General
The installation, operation, and
maintenance of dry-type transformers should be performed by an electrician or
other qualified personnel who are familiar with international, national, or
local electrical codes. Familiarity with the potential shock hazards associated
with electrical equipment is also necessary.
Encapsulated units are NEMA 3R
enclosures suitable for either indoor use in harsh environments or for outdoor
use. CE marked units have a protection index of IP23.
The transformer must be installed per
the National Electrical Code (NEC) and local code requirements. CE marked
transformers must be installed per EN 60742.
Inspection and Handling
The transformer should be inspected
carefully upon receipt to check for any visible or concealed damage that may
have occurred during shipment. If damage is found, a claim should be filed
immediately with the carrier.
Transformers 55 pounds or larger are
provided with lifting ears. Incorrect handling can bend the enclosure, cause
other damage, or result in personal injury.
Installation
When installing a buck-boost
transformer, always follow all applicable national and local codes. Outside
installation of the transformer should have the wiring in a conduit or as
required by national and local codes.
Encapsulated transformers can be
installed indoors or outdoors. When installed outdoors, these units should be
installed with the wiring compartment down to prevent the entrance of moisture.
Some encapsulated units have a top-entry wiring compartment and can be
installed vertically (wiring compartment up).
For indoor floor mounting of an
encapsulated unit that has a bottom-entry wiring compartment, the unit can be
installed horizontally (on its back side) for ease of making wire connections.
WARNING: Danger of electric shock.
Turn power off supplying device before installing. Do not remove parts or make
connections while transformer is energized.
Electrical Connections
Refer to the transformer nameplate
label or enclosed wiring diagram for primary and secondary voltage
combinations, frequency, and number of phases. Tap connections and voltage
combinations are also listed on the diagram or nameplate.
Proper assembly of the field wiring to
the transformer leads is extremely important. Make certain that the connector
or terminal is sized for the cable. Space and insulate connections or terminals
per the NEC.
Grounding
All dry-type transformers have a ground
stud in the enclosure. The transformer enclosure should be solidly grounded to
protect personnel. The customer-supplied grounding conductor should have a
current-carrying capacity to meet international, national, and/or local
requirements.
Maintenance
Non-ventilated encapsulated styles only
require periodic wiping of dust and dirt from the outside of the case under
normal conditions and environments. Adverse conditions may require more
frequent inspections.
CAUTION: Never perform internal
maintenance while the unit is energized.
If a dry-type transformer accidentally
gets wet, it must be cleaned and thoroughly dried before energizing. Otherwise,
complete failure could result.
Storage
Encapsulated transformers should be
stored in a clean, dry area. Care shoud be taken to prevent moisture or
condensation from entering the transformer. If stored outside, the transformer
must be covered and protected from water, dust, and other airborne
contaminants.
NOTICE: These instructions are
general in nature and may not cover all variations in transformer design or
conditions of installation, operation, and maintenance in enough detail to meet
customer needs. Additional instructions may be included with the transformer.
If you need further information or should a problem arise, contact the
manufacturer.
Reprinted with permission from the United CoolAir Corp.
TechTips sheet “Selecting and Applying Buck-Boost Transformers.”
For more information, visit www.unitedcoolair.com.
Publication date: 10/22/2007