the NEWS
  Home
  About the NEWS
  Subscription Info
  e-Newsletters
  Contact Us
  Dealer Design Products
  Resources
  Archived Editorial
  Blogs
  Career Center
  Columns
  Distributor Corner
  Calendar of Events
  HVACR Directory
  Industry Links
  Learning Center
  Manufacturer Reports
  Regional Reports
  Reprints
  Survey Says
  Training Track
  Webinars
  AEC Store
  Market Research
  Extra Edition
  HVACR Forum
  Legal forum
  Business Management
  Dot Comment
  Energy Matters
  Features
  Reader Mail
  Newsline
  People
  The Hotline
  Service & Maintenance
  Technical
  Advertising
  Ad Index
  Media Kit
  Submit Press Release
  Services
  Classifieds
  Digital Edition
  How To Corner
  Post Cards
Search in: EditorialProductsCompanies
Selecting and Applying Buck-Boost Transformers

October 22, 2007

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



HVAC equipment manufacturers build units that can be applied with various voltages. Some applications utilize an input or supply voltage of 277-1-60. This power supply comes from a 460-3-60 (4-wire) system (the neutral leg and the line side opposite the neutral leg).

While some components are available for direct application of 277-1-60 power, most manufacturers, including United CoolAir, find that the use of a buck-boost transformer to lower the voltage is more cost effective. The units are fabricated using components suitable for 208/230-1-60 power supply. The control voltage transformer is wired on the 230-volt tap to provide the 24-volt control voltage.


SELECTING A BUCK-BOOST TRANSFORMER

Enlarge this picture
Table 1. Available buck-boost transformers. (Click on the table for an enlarged view.)
The following information should be confirmed for the application:

Line Voltage — Confirm that the supply/input voltage is 277.

Frequency — Input power supply frequency must match the equipment — either 50 or 60 Hertz (Hz). This article is based on only applications of 60 Hz.

Phase — The supply/input power phasing must be the same as the equipment requirements. This article is based on single-phase applications.

Load KVA or Load Amps — You only need to know one or the other. This information usually can be found on the unit nameplate(s). On United CoolAir equipment the minimum circuit ampacity (MCA) should be used as the load amps.

The transformer is used to buck (decrease) the incoming power supply from 277 volts down to the 230 volts required for the unit. Table 1 lists the buck-boost transformers available from United CoolAir.

Read down the column until you see a KVA or amp value that is just higher than the equipment to be operated.


Enlarge this picture
Figure 1. Transformer connection diagram. (Click on the diagram for an enlarged view.)
Connect the transformer according to the diagram shown in Figure 1. Only one transformer is required in the wiring diagram for each power supply to the equipment.

CAUTION: Do not make connections other than those shown. The transformer must be as large (KVA) as the load it must operate. Never exceed the nameplate rating as this could result in overheating, reduced life expectancy, or worst case, fire.

Notes:
1. The symbol “O” used in this connection diagram illustrates where to field install an overcurrent protective device (typically a fuse or circuit breaker) when one input conductor is grounded and the other input conductor is ungrounded.

2. When both input conductors are ungrounded an overcurrent protection device is required to be installed in series with each input conductor.

3. For additional information refer to the National Electrical Code, Article 450-4.

General
The installation, operation, and maintenance of dry-type transformers should be performed by an electrician or other qualified personnel who are familiar with international, national, or local electrical codes. Familiarity with the potential shock hazards associated with electrical equipment is also necessary.

Encapsulated units are NEMA 3R enclosures suitable for either indoor use in harsh environments or for outdoor use. CE marked units have a protection index of IP23.

The transformer must be installed per the National Electrical Code (NEC) and local code requirements. CE marked transformers must be installed per EN 60742.

Inspection and Handling
The transformer should be inspected carefully upon receipt to check for any visible or concealed damage that may have occurred during shipment. If damage is found, a claim should be filed immediately with the carrier.

Transformers 55 pounds or larger are provided with lifting ears. Incorrect handling can bend the enclosure, cause other damage, or result in personal injury.

Installation
When installing a buck-boost transformer, always follow all applicable national and local codes. Outside installation of the transformer should have the wiring in a conduit or as required by national and local codes.

Encapsulated transformers can be installed indoors or outdoors. When installed outdoors, these units should be installed with the wiring compartment down to prevent the entrance of moisture. Some encapsulated units have a top-entry wiring compartment and can be installed vertically (wiring compartment up).

For indoor floor mounting of an encapsulated unit that has a bottom-entry wiring compartment, the unit can be installed horizontally (on its back side) for ease of making wire connections.

WARNING: Danger of electric shock. Turn power off supplying device before installing. Do not remove parts or make connections while transformer is energized.

Electrical Connections
Refer to the transformer nameplate label or enclosed wiring diagram for primary and secondary voltage combinations, frequency, and number of phases. Tap connections and voltage combinations are also listed on the diagram or nameplate.

Proper assembly of the field wiring to the transformer leads is extremely important. Make certain that the connector or terminal is sized for the cable. Space and insulate connections or terminals per the NEC.

Grounding
All dry-type transformers have a ground stud in the enclosure. The transformer enclosure should be solidly grounded to protect personnel. The customer-supplied grounding conductor should have a current-carrying capacity to meet international, national, and/or local requirements.

Maintenance
Non-ventilated encapsulated styles only require periodic wiping of dust and dirt from the outside of the case under normal conditions and environments. Adverse conditions may require more frequent inspections.

CAUTION: Never perform internal maintenance while the unit is energized.

If a dry-type transformer accidentally gets wet, it must be cleaned and thoroughly dried before energizing. Otherwise, complete failure could result.

Storage
Encapsulated transformers should be stored in a clean, dry area. Care shoud be taken to prevent moisture or condensation from entering the transformer. If stored outside, the transformer must be covered and protected from water, dust, and other airborne contaminants.

NOTICE: These instructions are general in nature and may not cover all variations in transformer design or conditions of installation, operation, and maintenance in enough detail to meet customer needs. Additional instructions may be included with the transformer. If you need further information or should a problem arise, contact the manufacturer.

Reprinted with permission from the United CoolAir Corp. TechTips sheet “Selecting and Applying Buck-Boost Transformers.” For more information, visit www.unitedcoolair.com.

Publication date: 10/22/2007



Did you enjoy this article? Click here to subscribe to the magazine.

Click here for more information.

The Breakthrough of the Scroll Compressor

October 15, 2007

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



The first Copeland Scroll® rolled off the production line in 1987, and the cooling industry was changed in a way that would benefit contractors and their customers in many, many ways. The prime benefits have been efficiency and product reliability.

Many features of the Scroll focus on preventing compressor failures, but the Scroll’s primary design also improves efficiency and reliability thanks to its classic, concentric compression scroll, in which one spiral-shaped part fits into another; the space between the two parts contains crescent-shaped gas pockets.


CLASSIC SCROLL OPERATION

In operation, one Scroll is fixed in place while the other orbits within the first. The refrigerant gas is drawn in by the movement and forced toward the center of the scroll through successively smaller pockets, thereby increasing the gas pressure until it reaches its maximum pressure. Then it’s released through a discharge port in the fixed scroll.

Copeland Scroll compressors are unique in the industry because they feature both axial and radial compliance in their design, whereas other scroll models utilize a mechanically fixed design and scroll tip seals.

Axial compliance refers to the ability of the scrolls to separate in the axial — or vertical — direction remaining in continuous contact around an axis, in all normal operating conditions, ensuring minimal leakage without the use of tip seals. Radial compliance refers to the ability of the scroll flanks to separate. These features of the Scroll design allow the compressor to be more tolerant of liquid refrigerant or debris than other technologies, making for a compressor that is extremely durable and reliable.

The combination of axial and radial compliance means that Scroll compressors actually “wear in” rather than wearing out. Continuous flank contact, maintained by centrifugal force, also minimizes gas leakage and maximizes efficiency of the compressor.

Next month: Tech Tips will begin examining the Scroll’s improved reliability through its oil control system.

For more information, click on the Emerson Climate Technologies logo above.



Did you enjoy this article? Click here to subscribe to the magazine.
© 2008 BNP Media. All rights reserved. | Privacy Policy