Is It the Drive, the Motor, or the Load?
February 5, 2007
In troubleshooting situations involving a motor, more than half
the battle is simply isolating the problem. Whenever there’s a working motor,
there’s a load and there’s some sort of motor controller, which is increasingly
going to be an adjustable speed drive (ASD). So when problems arise, how can
you tell if it is the drive, the motor, or the load? Here are a few tips to
tackle the problem in a quick, systematic way, making a few key measurements as
you go.
IMBALANCE MEASUREMENTS
A good place to start is with a measurement of current drawn by
the motor. When we talk about motors here, we are referring to three-phase
induction motors, the workhorse of industry. Motors are balanced loads: the
current that they draw on each phase should be about the same (less than 10
percent, as measured below). If they are not balanced, the cause could be
internal to the motor (deteriorating stator insulation, for example), or it
could be the result of voltage imbalance. So if there is any problem with
current imbalance, make the voltage imbalance measurement (less than 3 percent)
at the output of the ASD. The following calculation works for either voltage or
current imbalance.
Voltage and current imbalance measurements should also be taken
at the line side of the drive. Drives are extremely sensitive to voltage
imbalance, even more so than motors. Drives are using the peak voltages of each
phase to charge internal capacitor banks. If one of these phases is even a bit
low, it will make it hard for the drive to draw current from that phase. So
voltage imbalance will cause current imbalance. The drive may still function,
but the charge cycle of the capacitors, and their ride-through time in the
event of voltage sags, will be diminished.
In addition to imbalance measurements, voltage drops across loose
connections should also be checked. This can be done with direct voltage
measurements or with infrared thermometers. Readings that are much higher than
the ambient temperature, or that are higher than other phases, can indicate
loose or otherwise bad connections.
ASD OVERVOLTAGE AND UNDERVOLTAGE TRIPS
Drives have diagnostic codes which identify the cause of trip.
Generally speaking, they can be classified as overvoltage, undervoltage, or
overload (overcurrent). Note that mechanical starters only have overload trips.
They’re not concerned with over or undervoltage. What makes drives different?
Drives turn sine wave ac into dc (converter section), and then
turn the dc back into ac (inverter section). However, the ac at the output is
not a sine wave. It is a special waveform known as the pulse-width modulated
(PWM). The PWM, from the motor’s point of view, is accepted as if it were a sine
wave — almost (see the Advanced Motor Measurements section below). For now,
though, let’s focus on the drive internals, specifically on what’s commonly
referred to as the dc link. The dc link is nothing but a capacitor bank,
usually with a series link inductor (reactor) thrown in for filtering and
protection. The dc link is carefully monitored by the drive; overvoltage or
undervoltage refers to the voltage of the dc link.
Undervoltage can be caused externally by voltage sags on the
drive input. The Sags and Swells function on a power quality analyzer can help
to identify line-related undervoltage problems. Problems could also exist
internally with the dc link capacitors and/or reactor. In many drives, there
are test points to measure the dc link voltage. To check the capacitors, use
the min/max function of a digital multimeter, or, preferably, the trend
function of a power quality analyzer or oscilloscope. Check if voltage
regulation is within the manufacturer’s specification. To check the reactor, check
the waveform on both sides — there should be no change.
When troubleshooting a system, the tendency is to view the drive
or PLC as the most susceptible to voltage sags. The ice-cube control relay is
most often the source of sag-related problems. Studies have shown that these
low-cost components are the first to drop out when voltage sags occur. So don’t
forget to look at any external control circuit while you’re troubleshooting
intermittent system shutdowns.
Overvoltage could be a symptom of problems in the capacitors or
reactor. Or it could be caused by line-related voltage transients. At one
point, utility capacitor switching transients were notorious for causing
overvoltage trips in drives. Overvoltage could also be caused by regenerative
loads. Loads such as cranes and elevators feed back voltage when they
decelerate. Dynamic braking circuits are installed to shunt off this energy
from the drive, where they would otherwise show up as overvoltage on the dc
link. Problems such as improper installation can result in overvoltage trips.
Overload problems are usually load related and will be addressed
below.
LOAD PROFILING
To troubleshoot the interaction between the load and the motor,
you have to understand the relationship between torque and current. A motor is
nothing but a device to turn electrical energy (current) into rotational
mechanical energy (torque), via the magical effects of magnetism. What a load
demands of a motor is torque. For all practical
purposes, this torque is directly proportional to current used by
the motor. This should make perfect sense, because we all know
that for constant-speed motors — which include all motors started across the
line (with electro-mechanic starters) — voltage is, or should be, stable, and
current is the variable. When a load demands more torque and current than a
motor can supply, the result is an overload condition. Overloading will cause
overheating of the motor. Motor controllers will shut down the motor (and thereby
the load) rather than allow permanent winding insulation damage to occur.
Overloading is always relative to time: a high overload will trip
the motor in a short time, while a lower level of overload will take longer to
trip the motor.
When we want to evaluate the impact of a load on the motor-drive
system, we have to measure the current it draws. Of course, this current draw
typically varies over time as the load varies. The measurement of
current over some period of time is called load profiling. For
load profiling, the power-record function of a power quality analyzer is ideal
for capturing a trend line of current consumption (and kW too, if you want it).
A cursor enables you to identify the current values at different points on the
trend line, along with a time stamp for those points. It is not necessary to
measure all three phases of the induction motor because the motor
is a balanced load. Before load profiling, first make the current
imbalance measurement to make sure the motor is healthy. If your concern is
nuisance tripping, then pick the high leg and measure that (an overload on one
leg will trip all three legs).
When load profiling, we are looking for periods of especially
high current, relative to the full load amps of the motor. Full load amp
information is available on the nameplate of the motor. If there is a service
factor, the range calculation should be made on the basis of full load amps
times service factor.
While high current is the main concern, low current should also
be avoided. A motor is most efficient, and has the best power factor, in the 60
to 80 percent range of its full load amps. There
is no immediate penalty for underloading — the motor will not
trip. In fact, many motors are routinely oversized for the load, on the theory
that the motor is less likely to trip from overload.
However, as is most often the case, there is no free lunch. In
the case of underloading, the energy company sends a higher bill.
TWO DIFFERENT LOADS: VARIABLE TORQUE AND CONSTANT TORQUE
Most drive systems are used with variable torque or constant
torque loads. Variable torque loads include fans and rotary pumps. These are by
far the majority of loads, from an energy consumption point of view. When ASDs
are used with these loads, dramatic energy savings can be realized. For
example, a fan at half-speed (30 Hz) ideally uses only one-eighth of the power
of the same fan at 60 Hz (we say ideally, because there is always some level of
loss due to inefficiencies in the drive-motor-load system). From a
troubleshooting point of view, the important thing to realize is that these
variable torque loads rarely cause overload-related problems for drives
(assuming the load has been sized correctly). That is because they spend a lot
of their time running at lower speeds (less than 60 Hz) and drawing less
current. If this were not the case, that is, if the load demanded full speed
(and torque) most or all of the time, there would be no economic justification,
i.e., energy savings, to install an ASD in the first place. Sometimes these
loads will cause a trip at startup, but that is usually an indication that the
load has not been sized correctly to the drive. Another possibility is that the
load has changed. For example, a bearing starting to seize up demands more
initial torque to get the load going.
Constant torque loads can be more challenging. Frictional or
gravitational loads are constant torque loads. The key thing to understand
about these loads is that they require the same level of current (more or less)
at lower speeds. This can be dangerous for the motor. Motors are usually cooled
by fans built onto the rotor; when the motor slows, the fan cools less.
Therefore excessive heating can occur. The danger is that motor overload
circuits are built to measure heat indirectly by measuring current (there are
motors with heat sensors embedded in their stators, but these are obviously
more expensive). Here we have a situation where normal current draw at low speed
can cause overheating. The common solution is to install externally powered
fans to cool the motor.
Before we leave the subject of load troubleshooting, it should be
noted that there is a whole area of expertise having to do with the mechanical
linkage of the motor and load. These include vibration, shaft alignment, motor
mounting, etc. These are obviously important issues, but they are outside of
the scope of this article.
ADVANCED MOTOR MEASUREMENTS
In ASD motor systems, there are a few measurements that need to
be taken that would not be taken in mechanical starter (across the line) motor
systems. This is because the fast switching, high-frequency element of the PWM
output waveform causes special problems that the sine wave doesn’t. At first
glance, the motor as a current-drawing load looks like nothing but a big set of
inductors or coils (stator windings), and the nature of inductors is that they
filter out the high frequency current elements. That is why the current
waveform looks like a sine wave. But unfortunately, those high-frequency
elements of the voltage waveform do not get filtered out, and are capable of
causing some mischief.
The first two of these measurements should be made with an
oscilloscope or with the scope function of a power quality analyzer:
• Overvoltage reflections. Measure phase-to-phase at the motor
terminals. The leading edges of the PWM pulses can have peak values much higher
(up to 200 percent in theory) than normal. These overvoltage reflections can
cause damage to motor windings. These overvoltages are clearly visible on the
scope waveform. Solutions fall into three categories: shorten the drive-motor
cable length; use a motor with higher grade insulation, so-called inverter duty
motors; use filters.
• Motor shaft voltages and bearing
currents. Measure
voltage rotor-to-frame (ground), using stranded wire or a carbon brush. Motors
run by sine waves have a "normal" shaft/bearing-to-frame voltage of 1
to 2 V. The PWM waveform can cause breakdown voltages of 8 to 15 V to occur
between the shaft (more specifically, the bearing) and the frame. This damages
bearings, causing pitting and scarring. Many solutions have been proposed, but
the most common is the shaft grounding device.
• Leakage current. Measure with a current clamp around
all three phase conductors. High frequencies cause increased leakage between
stator windings and the frame. This ground or leakage current can interfere
with control and communication signals. Common solutions are the use of EMI
suppression cables or a common mode choke.
What about harmonics at the output of the drive? Wouldn’t the
PWM-turned-into-sinewave current-waveform contain a lot of harmonics?
Absolutely. But we don’t have to measure these. First of all, they don’t get
into the rest of the power distribution system; they only affect the motor.
Specifically, they cause additional heating in the motor. However, motor and
drive manufacturers have addressed this problem by supplying higher grades of
motor insulation. In those cases where an older motor is retrofit with an ASD,
the recommendation is that the motor full load amp be derated.
SUMMARY
To determine whether it’s the load, the motor, or the drive that
is causing problems, it helps to proceed systematically. Start with the basic
motor measurements (imbalance) to check the health of the motor itself. Then do
some simple drive measurements to check for causes of over or undervoltage
trips. Profile the load to find the cause for intermittent overload trips.
Finally, for premature motor bearing or winding failures, as well as control
signal interference, use an instrument such as a portable oscilloscope to make
additional motor measurements. This by no means exhausts all the possible
sources of problems, but it will certainly identify a lot of the most common
ones.
WORK SAFELY
The high voltage and currents present in electrical power systems
can cause serious injury or death by electrocution and burns. Consequently,
only trained, experienced technicians who have knowledge of electrical systems
in general and the equipment under test should perform testing and modification
of electrical systems.
One cannot anticipate all possible precautions that must be taken
when performing the measurements described here. At a minimum, however, you
should:
• Use appropriate
safety equipment such as safety glasses, insulated gloves, insulating mats,
etc.
• Be sure that all
power has been turned off, locked out, and tagged in any situation where you
will be in direct contact with circuit components. Be certain that the power
can’t be turned on by anyone but you.
• Read and
understand all of the applicable manuals before applying the information in
this article. Take special note of all safety precautions and warnings in the
instruction manuals.
• Do not use
instruments on applications for which they are not intended, and always be
aware that if the equipment is used in a manner not specified by the manufacturer,
the protection provided by the equipment may be impaired.
Reprinted with permission from the Fluke Corp. Application Note “Is it the drive, the motor,
or the load?” For more information, visit www.fluke.com.
Publication date: 02/05/2007
|