the NEWS
Advertisement:
HVACR Directory | Extra Edition | Learning Center | Editorial Blogs | Product Gallery
  Home
  About the NEWS
  Subscription Info
  e-Newsletters
  Contact Us
  Resources
  Archived Editorial
  Blogs
  Career Center - Employers
  Career Center - Job Seekers
  Columns
  Distributor Corner
  Calendar of Events
  HVACR Directory
  Industry Links
  Learning Center
  Letters
  Manufacturer Reports
  Regional Reports
  Reprints
  Survey Says
  Training Track
  Webinars
  AEC Store
  Market Research
  Extra Edition
  HVACR Forum
  Legal forum
  Business Management
  Dot Comment
  Energy Matters
  Features
  Newsline
  People
  Service Hotline
  Service & Maintenance
  Technical
  Advertising
  Ad Index
  Media Kit
  Submit Press Release
  Services
  Classifieds
  Digital Edition
  Post Cards
spacer
Search in: EditorialProductsCompanies
Finding Alternatives to R-22
by Steve Mella
July 6, 2009

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShare



Enlarge this picture
The Cable & Wireless communications facility in the United Kingdom underwent a retrofit from HCFC-22 to HFC-424A.
The replacement of HCFC-22 is fast becoming an important global issue. For example, in Europe within the next year it will be unlawful to use virgin R-22. Only recovered R-22 will be permitted for sale and use.

In the United States, increased restrictions on the use, production, and importation of R-22 have been introduced, which will result in higher prices and reduced availability. So, how do we deal with these issues related to HCFCs such as R-22? The scale of the problem is little short of daunting.


TRANSITIONS

Advertisement:

For more info, click here
Beside its long-standing use in air conditioning, R-22 also found its way into the refrigeration section over the years. During the transition away from CFCs, retrofitting directly from a CFC to a HFC was found in some instances to be both costly and technically unsatisfactory. The oil in the system needed to be replaced by a synthetic lubricant, which in some cases was not practical. And there were many cases of a deleterious effect on the seals. Also, hardware changes were required.

For such reasons, interim HCFC refrigerants were introduced to replace CFCs in refrigeration. These transitional refrigerants, which included many blends, contained at least one HCFC component that facilitated oil return and eliminated the need to make changes to the hardware.


OPTIONS

The first HFCs, such as R-407C, were not soluble in mineral and alkyl benzene (AB) lubricants, and new synthetic oils had to be developed. The new synthetic lubricants pick up moisture rapidly and are more expensive than the traditional oils.

So another option was to figure a way to use HFCs with the existing mineral or AB oil when retrofitting HCFC systems. In one case, Refrigerant Solutions (RSL) took that premise and started work on replacements for R-22. The new replacement refrigerants needed to be compatible with the existing lubricant in the system, provide a similar performance to R-22 and, of course, have zero ozone depletion potential (ODP).

The resulting refrigerants from RSL are R-424A, R-434A, and R-428A (which the company respectively brands as RS-44, RS-45, and RS-52.) Each uses a small amount of an HC refrigerant to help in oil return. They are Significant New Alternatives Program- (SNAP-) approved with an A-1 safety classification from the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

R-424A is suitable to replace R-22 in air conditioning applications in systems with a capillary as well as an expansion device. R-424A is a replacement for R-22 in existing equipment. There is no need to change the lubricant since R-424A is compatible with mineral, AB, and POE oils.

A testing program was carried out on R-424A which, compared to R-22, demonstrated a higher coefficient of performance, lower head pressures, lower discharge temperatures and pressures, a similar performance, and good oil return with all types of oils.

Conversions to and trials with R-424A have shown energy savings ranging from 10-20 percent compared to R-22 when R-424A is retrofitted into the same system while achieving similar capacity.

Companies which have converted away from R-22 to R-424A include Cable & Wireless, UK; Loblaws supermarket in Canada; Pratt & Whitney in the United States; Tropicana in the United States; Suncor in Canada; Kraft in the Philippines; Coca-Cola in Thailand; Irichi in Malaysia; and Valeo in China, amongst many others. Carrier Commercial replaced R-22 with R-424A in Carrier equipment at the Pratt & Whitney plant in Connecticut in 2007.

R-434A, with its high-cooling capacity, complements R-424A. R-434A replaces R-22 in both larger refrigeration and air conditioning equipment. With its low glide (less than one-third of R-407C), R-434A can be used in a wide range of applications such as air conditioning, refrigerated transport, bus, train, supermarkets, dairy chillers, cold stores, freezers, beer cellars, water chillers, and others.

R-434A has a coefficient of performance that matches R-22, similar discharge pressure to R-22, identical compression ratio, and a considerably lower discharge temperature than R-22. That makes R-434A a good alternative to replace R-22 in a low-cost retrofit situation, and in new, larger R-22 systems. OEMs can achieve cost savings as opposed to converting or redesigning R-22 systems for other HFC alternatives such as R-407C, R-410A, or R-134a.

For low temperatures, RSL developed R-428, which is similar to CFC-507 in its performance with a high capacity. R-428A has been designed as a replacement for R-502 and the interim HCFC blends (such as R-402A, R-403B, R-408A and R-411B), but also a replacement for R-22 at low temperatures where the system is designed to withstand R-502 pressures and can accommodate the higher capacity of R-428A (as compared to R-22).

R-428A replaced R-402A in Bidgood’s supermarket, Newfoundland, Canada. Provincial Refrigeration Ltd., working with Kerr Controls Ltd., carried out the conversion.

The high capacity of R-428A at low temperatures is a prominent feature of this new refrigerant. R-428A has a low-temperature glide of less than ½°C and is suitable for use in flooded systems.



DAUNTING DAYS

The industry faces a daunting time over the coming months. Refrigerants to replace R-22 satisfactorily, easily, and at the lowest possible cost will be the talk of the industry.

Contractors and service technicians will do well to explore the new options and share them with their customers.

For more information, visit www.comstarproducts.com.

Publication Date: 07/06/2009



Steve Mella
is president of ComStar International, which distributes refrigerants. For more information, go to www.comstarproducts.com.