Service & Maintenance / Extra Edition

Troubleshooting Challenge: A Modular A/C Unit That's Not Cooling

January 4, 2010
/ Print / Reprints /
ShareMore
/ Text Size+
Figure 1. (Click on the image for an enlarged view.)

Yes, it’s January, but it’s always nice to look ahead to a busy summer season. Hence, a problem of ‘not cooling’ instead of ‘not heating.’

In this month’s troubleshooting situation we’re taking you to a school, but not to the equipment room of the main building. Instead, it’s a modular classroom (similar to a double-wide manufactured home) that is brand new, and employs a heating/cooling unit that mounts on one end of the building. This system employs resistance-type elements for the heating mode, and a direct expansion system for cooling. The complaint is that there is “very little cooling” being accomplished.

Upon your arrival you determine that the complaint would have been better stated as “blowing warm air” since only the indoor fan motor is running and the compressor and outdoor fan motor are not. Details on the thermostat settings are as follows:

1. System switch is set in the cooling mode.

2. Fan switch is set in the AUTO position.

3. Set point is far below room temperature.

After disconnecting the power supply and removing the appropriate access cover, you find two other factors to consider … that the compressor is very hot to the touch, and that the outdoor fan motor spins freely. While allowing time for the compressor to cool down, you make a complete visual inspection, checking for any loose connections and for proper wiring within the unit (see the diagram in Figure 1), and you find everything properly connected.

When you turn the equipment disconnect switch back on, you note that the compressor starts, but the outdoor fan motor doesn’t. With the power supply again disconnected and a check with a digital meter on the dual capacitor, you make two tests, one between C and F, the other from C to H. The result of your first test shows a series of zeros on your meter display, and the second test shows 37.5 MFD.

Your troubleshooting question: What is the next step you need to take in repairing this unit?

Compare your answer with ours by clicking here.

Publication date: 01/04/2010

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Recent Articles by Jim Johnson

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-14-14 cover

2014 April 14

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con