Figure 1. PTC relay with start capacitor

One type of starting relay used on fractional horsepower compressors is the positive temperature coefficient (PTC) relay. It performs the same function as a current relay or potential relay but in a much different manner. A PTC relay uses a positive temperature coefficient thermistor to remove the start winding and/or start capacitor from the circuit. A PTC thermistor is basically a resistor whose resistance increases on an increase in temperature.



The circuit is wired so that the PTC thermistor is wired in series with the start winding of the motor (Fig. 1). If the motor requires a start capacitor, it will also be wired in series with the start winding and PTC relay. When the motor starts, the resistance of the thermistor will initially be very low and sufficient current will flow through the PTC thermistor, the start winding and/or start capacitor to allow the motor to start normally. As the current flows through the PTC thermistor, it will quickly heat up and its resistance will quickly increase to a point where the current flow will dramatically reduce, essentially removing the start winding and/or start capacitor from the circuit.

Another use for a PTC relay is with a permanent split capacitor (PSC)-style compressor. These compressors are designed to operate with a run capacitor in the motor circuit to give them better running efficiency. Sometimes these compressors will require the addition of a start capacitor to assist the starting of the compressor. Normally a potential relay will be used to disconnect the start capacitor from the circuit. However, a PTC relay can also be used for the same purpose. There are two ways in which a PTC relay can be used to assist in starting a PSC-style compressor.



Figure 2. PTC relay with run capacitor

A PTC relay can simply be wired in parallel with a run capacitor (Fig. 2). During starting, the PTC relay causes a short across the run capacitor. This will allow full-line voltage to the start winding during start-up, giving the motor a stronger phase shift to get started. Once the thermistor warms up, the short across the run capacitor is removed and the motor runs normally.

The other method is to use the PTC relay with a start capacitor (Fig. 3). The PTC relay is wired in series with a start capacitor, and both the PTC relay and start capacitor are wired in parallel with the run capacitor. During the starting of the motor, both the start and run capacitors are in the circuit to assist in starting the motor. Once the thermistor heats up, the start capacitor is essentially removed from the circuit and the motor runs normally.



Figure 3. PTC relay with start and run capacitor

The one disadvantage to using this type of relay is once the motor circuit is shut down, it takes about two to five minutes for it to cool down to a point that its resistance reaches a point where the motor could be started again. If the motor tries to start before the PTC relay has cooled enough, the motor’s overload protector will trip the motor circuit. Once the motor’s protector has reset and thermistor cools down sufficiently, the motor should start normally.

Troubleshooting these relays is normally simple. Remove the relay from the circuit and allow it to cool to room temperature. Place an ohmmeter across the terminals of the relay. At room temperature, the measured resistance should be low. If an infinite resistance is measured the relay needs to be replaced.

Publication date: 09/01/2008

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Recent Articles by Joe Marchese

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-14-14 cover

2014 April 14

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con