the NEWS
HVACR Directory | Extra Edition | Learning Center | Editorial Blogs | Product Gallery
  Home
  About the NEWS
  Subscription Info
  e-Newsletters
  Contact Us
  Resources
  Archived Editorial
  Blogs
  Career Center
  Columns
  Distributor Corner
  Calendar of Events
  HVACR Directory
  Industry Links
  Learning Center
  Manufacturer Reports
  Regional Reports
  Reprints
  Survey Says
  Training Track
  Webinars
  AEC Store
  Market Research
  Extra Edition
  HVACR Forum
  Legal forum
  Business Management
  Dot Comment
  Energy Matters
  Features
  Reader Mail
  Newsline
  People
  Service Hotline
  Service & Maintenance
  Technical
  Advertising
  Ad Index
  Media Kit
  Submit Press Release
  Services
  Classifieds
  Digital Edition
  Post Cards
Search in: EditorialProductsCompanies
Ice Breaker: Evacuation Speed Up
by Joe Marchese
October 6, 2008

ARTICLE TOOLS
EmailEmailPrintPrintReprintsReprintsshareShareshare Use



Advertisement:

For more info, click here
Evacuating a refrigeration system can be a very time-consuming task. It takes time for a vacuum pump to sufficiently reduce the system’s internal pressure to allow the water vapor contained within to be reduced to acceptable levels. Some of the factors that influence the speed of this process include:

• Internal volume of the system;

• Amount of moisture contained within the system;

• Ambient temperature present;

• Amount of internal system restrictions;

• Amount of external restrictions between the system and the vacuum pump; and

• Size of the vacuum pump.

A technician has no control over many of these factors, but there are some areas in which he can help speed up this process.

Technicians should always set up their vacuum pump so it pulls a vacuum from both sides of the system. Pulling a vacuum from only one side greatly increases the time for proper system evacuation. The connecting line between the vacuum pump and the system should be one that is as short as possible and has the largest possible internal diameter.

Many technicians use a standard ¼-inch refrigerant hose during the evacuation process. They should instead be using a 3/8-inch refrigerant hose that is rated for vacuum use or use a section of copper tubing. This will help to reduce the restriction between the vacuum pump and the system.

Schrader valves offer an unneeded restriction during the evacuation process. Systems with service hoses that are connected via a Schrader valve should use a valve core remover that allows the cores to be removed without detaching the hoses from the system. Once the evacuation process is complete, the valve cores can be inserted back into the Schrader valves without losing the vacuum.

Technicians should always use clean oil in their vacuum pumps. This ensures the pump is able to reduce the system’s pressure to an acceptable micron level. Using containment oil will hinder the vacuum pump’s ability to pull a deep vacuum. Technicians can waste valuable time waiting for the system pressure to reach an acceptable level — but is unable to do so because of containment oil. Technicians should always perform a blank-off test before opening a vacuum pump to a system. This will ensure that the vacuum pump can obtain the required vacuum levels.

On larger systems, a technician can use two vacuum pumps. Attach one to the system’s low side and the other to the system’s high side. This will help to reduce the effect of internal restrictions present and speed up the process.

Also, do not forget to use a quality vacuum gauge. This allows a technician to operate a vacuum pump only as long as is required to properly dehydrate the system. Do not base the evacuation process on time. Operating a vacuum on a system for 30 minutes and assuming the system is completely evacuated is not an accurate method and should not be done. That is just guessing at the process and is not very professional.

Using these new practices will help to ensure that a complete evacuation is performed in a timely fashion and will help to make good technicians better technicians.

Publication Date: 10/06/2008