Engineered Systems NEWSHVAC Engineering SectorsHigh-Performance Buildings & AutomationCommercial HVAC

Back To BASics — Sensors And Actuators

By Ira Goldschmidt P.E.
Ira Goldschmidt, P.E.
April 5, 2018

Continuing last month’s fundamentals-based theme, I’d like to address the devices that make closed-loop control work. As discussed, control loop algorithms are implemented by software within a BAS controller. However, the input and output signals associated with the loops come from the sensors and and go to the actuators that are mounted on/near the controlled equipment. These are the most important parts of what are typically referred to as the “field devices” portion of a BAS.

Sensors provide the “controlled variable” signal input to the algorithm. These devices always provide a varying signal (i.e., they are not on/off devices) and are mostly for temperature or pressure measurement. Airflow and CO2 sensors are becoming more prevalent, and humidity, level, etc., are also used in some applications.

Of the input field devices, temperature sensor selection involves the least challenge. Thermistors or RTDs are essentially all that are used, both of which have a varying resistance vs. temperature and can be readily read by BAS inputs without the need for “transmitter” electronics to amplify or convert the sensor’s low-level signal. Most BAS are designed with a resistance-to-temperature lookup table so that one of these (along with one of the myriad of versions within each type) are most easily accommodated. Therefore, it is best to just specify a reasonable accuracy for these sensor types (i.e., +/-0.5°F) and let the contractor use the sensor technology/type designed for the BAS. More importantly is to specify where/when the various types of sensor configurations are to be used — i.e., surface wall-mount, flush wall mount, pipe insertion (a strap-on should be rarely allowed), single-point duct, extended duct averaging, and outside air with sunshield.

The other sensor types involve a much greater variety of sensing technologies, accuracies, and costs for the engineer to choose from. They also include a transmitter to output (most typically) a 0-5vDC signal readily used by BAS input, so a BAS’s sensor signal “preference” is not the issue. Instead, a cost/benefit approach for selecting the best sensors for each client/project/application is needed.

Actuators are the field devices (along with the associated dampers and valves) that receive the output signal determined by a control algorithm. VFD speed control signaling has also become a common output for modulating control; two-position control more often than not is used for turning on/off fan motors, DX compressors, etc. However, these latter items are not BAS field devices per se, and are not normally specified with the BAS. So actuator specification/selection is important to the success of closed-loop control.

Two-position actuators (i.e., that either fully open or close the damper/valve) typically actuate based on the absence or presence of a 24 or 120vac signal, whereby the energized motor (or other positioning technology) is operating against a spring (or closes from the force of the spring when de-energized). Solenoid valves are a good example of a common combination two-position actuator/valve. There are also actuators with bi-directional motors that must be controlled by two BAS outputs (one to open the actuator and the other to close it). These are sometimes called “floating” or “three-wire” actuators and are rarely used except for VAV box dampers.

Modulating actuators use a variety of motor and position feedback technologies such that the technology used often is considered proprietary to each actuator manufacturer. Therefore, it is probably more important to stick with a known manufacturer rather than to delve into the technological specifics. However, there are a few issues that are important. First, the actuator should use a 0-10vdc input signal. More importantly is the ability of the actuator to provide many steps of positioning (aka “resolution” for which 100 steps is common). There are other specs to consider when the associated damper/valve behavior is also considered, but this will be covered in another column.

 

What About Pneumatic Actuators?

Many assume that “DDC” means electronic actuation, but that’s simply not true. Pneumatic actuation was the standard approach for DDC control until electronic actuator technology became reliable and cost-effective around the turn of the century. Even today, pneumatic actuation is typically less expensive than electronic, but an additional (and costly) device is needed to convert the BAS’s electronic output to a pneumatic signal. However, applications that require fast actuation (e.g., lab pressure control) may still benefit from pneumatic actuation.

Share This Story

Looking for a reprint of this article?
From high-res PDFs to custom plaques, order your copy today!

 

Iragold

Ira has worked in the building industry for over 35 years as a controls tech, MEP designer, and consultant providing design/guidance for critical-facility BAS and intelligent building systems integration. He is a co-author of the ASHRAE BACnet® standard and Guideline 13 — Specifying DDC Controls.

WWW.ESMAGAZINE.COM/IRA
Use this handy shortcut to see Ira’s collected BAS wisdom in ES columns and other articles.

Recommended Content

JOIN TODAY
To unlock your recommendations.

Already have an account? Sign In

  • HVAC-enrollment

    The Trades Are Back: HVACR Programs See Nearly 30% Enrollment Spike

    A new wave of future technicians is entering the pipeline.  
    Training and Education
    By: Matt Jachman
  • 2025 Top 40 Under 40

    2025 Top 40 Under 40 HVACR Professionals List

    The 11th annual Top 40 Under 40 list highlights those...
    News
    By: Hannah Belloli-Oster
  • LG Ductless Mini-Split Systems

    The 9 Types of Heat Pumps

    As the U.S. moves toward electrification, heat pumps are...
    Ground Source Heat Pumps
    By: Joanna R. Turpin

More Videos

Today's Boiler

Spring 2026 Issue

Today's Boiler - Spring 2026 Cover

Read More from Today's Boiler

Case in Point Logo

Smarter Hydronic Design for Data Centers - Free Webinar - January 22, 2026

Related Articles

  • Ira Goldschmidt, P.E.

    Back To BASics — Control Loops

    See More
  • Ira Goldschmidt, P.E.

    Back To BASics: DDC Controllers (Part 1)

    See More
  • Back to Basics: IAQ & HVAC Survey Techniques and Case Studies

    See More

Related Products

See More Products
  • Lessons Learned in a Boiler Room: A common sense approach to servicing and installing commercial boilers

  • Manual B.jpg

    Manual B - Balancing and Testing Air and Hydronic Systems

  • Building Information Modeling: Planning and Managing Construction Projects with 4D CAD and Simulations

See More Products

Events

View AllSubmit An Event
  • January 14, 2026

    Future-ready HVAC Systems: Transitioning to A2L with New Gas Leak Sensors

    On Demand This session will explore how emerging approaches to leak detection and system monitoring are meeting the demands of modern refrigeration and HVAC applications.
  • September 23, 2025

    How to Get Found First and Chosen Fast

    On Demand When a customer needs help, they don’t wait around—they choose the first business they find and hear back from. This webinar will cover how to get noticed online, capture every lead, and win more business without adding extra staff or hours.
View AllSubmit An Event

Related Directories

  • Cubic Sensor and Instrument Co. Ltd.

    Cubic Sensor and Instrument Co., Ltd. is a publicly listed company in SSE STAR Market (stock code:688665), specializing in smart gas sensors and superior gas analyzers.
  • Innovative Sensor Technology

    An international manufacturer of thin-film sensing devices; RTD temperature sensors, capacitive relative humidity sensors, thermal mass flow sensors, conductivity sensors and biosensors. iST is an ISO 9001 certified company.
×

Sign Up. Stay Informed.

The #1 trusted source for the HVACR industry since 1926

SUBSCRIBE
  • RESOURCES
    • Advertise
    • Contact Us
    • Advisory Board
    • Classifieds
    • Submit a Letter
    • Directories
    • Store
  • ACCOUNT CENTER
    • Create an Account
    • Start a Subscription
    • Manage My Account
    • Sign Up for Newsletters
    • Visit Customer Service
    • Update Preferences
  • SERVICES
    • Marketing Services
    • Reprints
    • Market Research
    • List Rental
    • Survey/Respondent Access
  • STAY CONNECTED
    • LinkedIn
    • Facebook
    • Instagram
    • YouTube
    • X (Twitter)
  • PRIVACY
    • PRIVACY POLICY
    • TERMS & CONDITIONS
    • DO NOT SELL MY PERSONAL INFORMATION
    • PRIVACY REQUEST
    • ACCESSIBILITY

Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

Design, CMS, Hosting & Web Development :: ePublishing