Extra Edition / Technical

Checking for Cracked Heat Exchangers

Let us begin by saying there is absolutely no known technique for finding a crack 100 percent of the time.

Probably the best is to visually locate a crack. However, particularly in modern 80 percent and 90 percent forced air furnaces, a thorough visual inspection is time consuming and difficult at best.

In the past there have been many suggested techniques. These include:

• A smoke bomb test - a smoke generator is placed in the heat exchanger, then the outside of the heat exchanger is visually accessed to watch for smoke passing through the crack.

• The wintergreen test - oil of wintergreen is sprayed into the combustion chamber (with the blower operating), then see if the smell is present at the supply registers.

• The salt test - a salt solution is sprayed into the combustion chamber, a hole is drilled in the supply ducting, and a torch is held in the air blowing out of the hole to see if the flame changes color from the salt.

• The pressure test - all openings in the heat exchanger are sealed, the blower energized, and a pressure sensor or draft gauge is inserted inside the heat exchanger to see if a crack is allowing distribution air to blow into the heat exchanger (through a crack or hole).

• The tracer gas test - all openings in the heat exchanger are sealed, a methane tracer gas is injected into the heat exchanger, and a combustible gas leak detector passed around the outside looking for areas where the tracer gas is escaping.

• The flame distortion test - watch the flame when the blower comes on and watch for the flame color, shape, etc., to change.

Most of the above-mentioned tests make several fatal assumptions:

• Leakage is going to be from the flame side to the distribution side of the heat exchanger. This may be the case if the blower is not on and the vent system is not drafting; however, when the blower is on, for example, there is very little chance flue gases, smoke, etc., are going to pass through a crack into the distribution air. When a blower energizes, there is a tremendous amount of pressure around the outside of the heat exchanger; therefore, there is a much greater chance of distribution air being blown into the fire side of the heat exchanger.

• The crack is open when the heat exchanger metal is at (or close to) room temperature. Some cracks have been known to only open when the unit is fired and the heat exchanger metal is hot.

• The service technician has the time, experience, or even reason to suspect the exchanger is cracked.

To test for cracks using a combustion analyzer, simply watch the O2/CO2 readings and the CO reading when the blower comes on - usually several minutes after the burner(s) ignite.

Typically, the O2/CO2 or CO readings will stabilize within 30 to 60 seconds after ignition. If a crack is present, when the blower energizes, air (at 20.9 percent O2) may be blown through the crack in sufficient quantities to raise the O2 (or decrease the CO2) reading on the combustion analyzer.

Using a combustion analyzer to test for cracks in a heat exchanger also has limitations; however, there are some distinct advantages:

• It tests under actual operating conditions.

• It may provide additional information as to how dangerous a crack is. For example, if a crack is visually observed and a combustion test finds that when the blower comes on the carbon monoxide reading rises to excessive levels, a service contractor can be more confident that a dangerous situation exists and has the documentation that the unit needs to be immediately condemned and taken out of operation.

• It can be easily done during the normal course of a service call where combustion testing is performed.

It is important to keep in mind that changes in combustion test readings may also be caused by other factors:

• On oil-fired equipment, loose clean out ports in the heat exchanger will most likely result in O2/CO2 or CO readings changing when the blower comes on.

• Depressurization of the mechanical room due to leakage in the return side of the distribution system may be sufficient to change the readings when the blower is energized.

Reprinted with permission from the Training Room page of the Bacharach Inc. Website. Bacharach is a leading manufacturer of testing equipment for air quality, gas detection, HVAC, combustion, and diesel applications. For more information, visit www.bacharach-inc.com.

Publication date: 03/19/2007

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2015 ACCA Conference

Images from the 2015 ACCA Conference in Grapevine, Texas. Posted on April 8, 2015.

Podcasts

NEWSMakers: Mark Crockett
Mark Crockett vice president, Crockett Facilities Services, explains the importance of technician training, the value of being a top minority-owned company in the U.S., current projects the company is managing, and much more. Posted on April 24.
More Podcasts

ACHRNEWS

NEWS 04-20-15 cover

2015 April 20

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

Global Warming

Do you believe in man-made global warming?
View Results Poll Archive

HVACR INDUSTRY STORE

2015.jpg
2015 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con