Engineered Systems NEWSCase in Point

National Defense Research Lab Fights Silica In Heat Transfer

September 27, 2002
For years, Los Alamos National Laboratories had searched for a solution to the buildup of silica in its chiller, but newer chiller condensers using a brush system have never required manual cleaning.
Los Alamos National Laboratories (LANL) in Los Alamos, NM, is the primary research lab for national security research and development. For years, LANL searched for a solution to the buildup of silica in its chiller condenser tubes. The concentration of silica in the water, about 90 ppm, contributed to tube scaling and great losses in energy efficiency until the research agency implemented a program wherein the tubes are automatically cleaned while the chillers remain on-line.

When it forms on the tubes, the silica acts as an insulator to heat transfer, which in turn increases the operational costs of the chillers. To keep the silica in suspension, LANL incorporates the use of a polymer base inhibitor and maintained low cycles of concentration (2.5 to 3) in the cooling towers. Still, the amount of buildup in the tubes requires regular manual cleaning, which is costly in terms of maintenance, downtime, and additional labor expenses, since the cleaning has to be scheduled over the weekends.

In early 2001, two 1,200-ton and two 600-ton chillers were installed in the LANL Super Computer Center (SCC). These chillers are equipped with an on-line Automatic Tube Brushing (ATB) system manufactured by Water Technology of Pensacola, Inc. (Pensacola, FL) in the condenser tubes to fight the silica problem.

LANL's history with the ATB System goes back to the late 1980s, when a new 800-ton chiller was fitted with the system. Designed to keep condenser tubes continuously clean and thereby provide energy savings through increased heat transfer, the system has been very effective in eliminating the silica problem at LANL.

Nothing To Bristle At

The ATB system consists of a small nylon-bristled brush installed in each condenser tube, open catch baskets that are epoxied into the tube ends in order to suspend the brushes in the water flow, and the ATB system four-way backflushing valve. The valve automatically reverses the flow through the tubes several times per day for a period of 30 seconds, which propels the brushes through the tubes and cleans the tube walls many times each day.

No special challenges came up during the SCC installation. The only requirement for the system is that the supply and return piping for the condenser have a parallel run large enough to accommodate the four-way backflushing valve, from 24 to 48 in. in length depending on the piping size. For retrofits, Water Technology custom manufactures the valves to fit into existing piping.

The ATB system control panel is equipped with a 24-hour clock and adjustable relays that control the duration of the valve reversal. Control options include a flow-switch bypass and an automated chiller-unloading feature (required in chillers over 1,200 tons). A system cycle counter allows the enduser to monitor valve reversals.

Brushing Up On Savings

Solid data that takes into account load factors, chiller efficiency ratings, and local power costs indicate less than a two-year payback on the four SCC systems, which cost just under $100,000. Savings are derived from reduced maintenance requirements and from the energy savings that result from increased heat transfer when fouling is eliminated in the condenser tubes.

"We have a couple of 500-ton chillers that were installed without the brush system in 1986," stated Doug Hefele, P.E., facility engineer at the LANL Super Computer Center. "We have to clean the condenser tubes regularly in those, but we have never once had to rod out the tubes in the 800-ton unit installed in 1988 with the ATB system."

"I've purchased a number of chillers in the last few years," Hefele said, "and after seeing the results, I've made sure all of them are equipped with the brush system." Other buildings at LANL that have the brush system include the Target Fab Center and the Laboratory Data Communication Center. According to Hefele, those chiller condensers, like the ones at the SCC, never require manual cleaning. ES

Share This Story

Looking for a reprint of this article?
From high-res PDFs to custom plaques, order your copy today!

 

Recommended Content

JOIN TODAY
To unlock your recommendations.

Already have an account? Sign In

  • HVAC-enrollment

    The Trades Are Back: HVACR Programs See Nearly 30% Enrollment Spike

    A new wave of future technicians is entering the pipeline.  
    News
    By: Matt Jachman
  • 2025 Top 40 Under 40

    2025 Top 40 Under 40 HVACR Professionals List

    The 11th annual Top 40 Under 40 list highlights those...
    News
    By: Hannah Belloli-Oster
  • LG Ductless Mini-Split Systems

    The 9 Types of Heat Pumps

    As the U.S. moves toward electrification, heat pumps are...
    HVAC Residential Market
    By: Joanna R. Turpin

More Videos

Today's Boiler

Spring 2026 Issue

Today's Boiler - Spring 2026 Cover

Read More from Today's Boiler

Case in Point Logo

Smarter Hydronic Design for Data Centers - Free Webinar - January 22, 2026

Related Articles

  • Nanotechnology Yields What Could Be a Major Advance in Heat Transfer

    See More
  • Lennox To Sell Interest In Heat Transfer Venture

    See More
  • April 22, 2005: Lennox To Sell Interest In Heat Transfer Venture

    See More

Related Products

See More Products
  • plumbing hvac.jpg

    2025 National Plumbing & HVAC Estimator Book

  • 9781439842126.jpg

    Heat Exchanger Design Handbook, Second Edition

  • A-Heat-Pump-Thats-Not-Delivering-Any-Air-DVD-Cover-218x300.jpg

    A Heat Pump That’s Not Delivering Any Air

See More Products

Related Directories

  • Modine, Heat Transfer Products

    Heat exchangers for a wide variety of markets and applications including heating, ventilation, air conditioning, and refrigeration.
×

Sign Up. Stay Informed.

The #1 trusted source for the HVACR industry since 1926

SUBSCRIBE
  • RESOURCES
    • Advertise
    • Contact Us
    • Advisory Board
    • Classifieds
    • Submit a Letter
    • Directories
    • Store
  • ACCOUNT CENTER
    • Create an Account
    • Start a Subscription
    • Manage My Account
    • Sign Up for Newsletters
    • Visit Customer Service
    • Update Preferences
  • SERVICES
    • Marketing Services
    • Reprints
    • Market Research
    • List Rental
    • Survey/Respondent Access
  • STAY CONNECTED
    • LinkedIn
    • Facebook
    • Instagram
    • YouTube
    • X (Twitter)
  • PRIVACY
    • PRIVACY POLICY
    • TERMS & CONDITIONS
    • DO NOT SELL MY PERSONAL INFORMATION
    • PRIVACY REQUEST
    • ACCESSIBILITY

Copyright ©2026. All Rights Reserved BNP Media, Inc. and BNP Media II, LLC.

Design, CMS, Hosting & Web Development :: ePublishing