Inlet Water Temperatures and Boiler Corrosion

March 21, 2001
/ Print / Reprints /
ShareMore
/ Text Size+
Since most boilers and water heaters vent with a conventional negative draft flue, it is important to ensure that enough heat remains in the flue products to maintain them as a gas for operation of the vent and discharge into the atmosphere.

However, as the efficiency of a boiler or water heater increases, more heat from the combustion process must be transferred into the water at the heat transfer surface. The relative temperature of the flue products decreases as the efficiency increases.

When the flue products from the combustion process are excessively cooled, they will reach their own dewpoint, which is the temperature where the water vapor and products of combustion condense into a liquid. This liquid collects on both the heat transfer surfaces and in the flue.



Condensate Hazards

Flue gas condensate is acidic (approximately 4 to 5 pH) and can cause major operational, installation, and safety issues when allowed to continue forming in a boiler or water heater that is not designed to condense.

A small amount of condensate may have little effect on initial operation. However, as the volume of condensate formed increases, it can have major detrimental effects on operation.

Condensate obstructs the path of flue products on the heat transfer surface, fouls burners, damages ignition devices, attacks the jacket and related components, and collects in the flue pipe. Flue gas condensate can attack and destroy the venting system. Corrosion of the venting system can create a potentially dangerous condition to the point where flue gas spillage can occur.

Excessively cooled flue products can also result in a loss of draft and spillage of flue products into an occupied space, which causes another potentially dangerous situation.



Figure1. Chart for determining the dewpoint temperature. Note: This curve is determined using Brokaw Program HP-97 with the variables of 50% rh, 60 degrees Farenheit (15.5 degrees Celsius) combustion air temperature, and 30-in.-Hg (101.3-kPa) barometric pressure.

The Role of Minimum Inlet Water Temps

The formation of condensate is controlled by regulating the minimum inlet water temperatures for both boilers and water heaters. ANSI Standard Z21.13, “Gas-Fired Low-Pressure Steam and Hot Water Boilers,” contains a chart that relates the approximate dewpoint temperature of gas flue products to the combustion process. (See Figure 1.)

As gas combustion occurs, the byproducts are principally water vapor and carbon dioxide (CO2). Figure 1 shows the relationship between the CO2 concentration in the gas flue products and the dewpoint temperatures of flue products by providing curves for both natural and LP gas.

Assume that you’re operating a typical high-efficiency, natural gas-fired boiler with a CO2 level of 7.5% in its flue products. By plotting this on the curve, you can determine that the dewpoint for the flue products from this boiler would be approximately 125°F.

Note: The chart assumes typical conditions regarding the combustion air temperatures, barometric pressure, and relative humidity, based on laboratory testing. In real-world applications, these conditions may vary. Typically, this dewpoint temperature is slightly increased to provide a safety factor to compensate for the varying real-world conditions in order to establish a minimum inlet water temperature to control condensation.



Correct Temperatures

A typical mid-efficiency boiler or water heater operated with water temperatures in the range of 130° to 140° will prevent condensate problems.

Note: A water heater must use a thermostatic mixing valve to provide lower-temperature domestic water in order to prevent a risk of scald injury. This has proven to provide reliable temperatures to control condensation based on years of application in the field.

If the minimum inlet temperature to the boiler or water heater is maintained above the minimum dewpoint temperature, condensate is controllable. It is virtually impossible to cool the flue products to dewpoint when the minimum inlet water temperatures are maintained above the dewpoint temperature based on this data.

By controlling minimum inlet water temperatures, we are able to prevent unwanted condensation. This ensures consistent operation of a high-efficiency boiler or water heater, and provides reliable operation of a standard venting system.

Moore is manager of technical services for Lochinvar Corp., Nashville, TN; www.lochinvar .com (website).

Publication date: 03/26/2001

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 ACI Home Performance Conference

The 2014 ACI National Home Performance Conference & Trade Show was held in Detroit.

Podcasts

Jeff Hutchinson, Energy Solutions Manager for mechanical contractor Bruner Corp., talks about the ductless market and how it can be profitable for a commercial contractor.

More Podcasts

ACHRNEWS

NEWS 07-21-14 cover

2014 July 21

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

R-22 PHASEOUT POLL

Some in the industry are calling for the EPA to halt production of R-22 as of 2015. What do you think?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con