Anti-fouling system cures scaling blues in New Orleans

April 14, 2000
/ Print / Reprints /
ShareMore
/ Text Size+
NEW ORLEANS, LA — The city of New Orleans is a hot bed for cool jazz, hot-and-spicy food, good times, and old-fashioned, Cajun-style, Southern hospitality. Hard water and chiller tube scaling are likely the last things that come to mind.

However, condenser tube scale build-up on centrifugal chillers at the New Orleans Airport Hilton did create major operating problems ranging from undesirable compressor surge, to rising wastewater and chemical treatment expenses.

The Hilton’s facility engineers opted to remedy their scale blues, enhance chiller efficiency, and lower operating and maintenance costs by applying a noninvasive, electronic anti-tube fouling system.

Scale never sleeps

The New Orleans Airport Hilton opened in 1989, and since its debut, scale-related troubles have been increasingly problematic.

The hotel’s cooling plant originally was comprised of three centrifugal chillers rated at 135, 185, and 235 tons. The condenser water loop was conditioned using a magnetic water-treatment device to prevent scaling. Chemical treatment was used for biological control.

Nonetheless, as cooling tower water was warmed in the chillers’ condensers, dissolved mineral ions precipitated out of the water and adhered to the condenser tube walls. Over time, soft deposits formed that eventually turned into hard scale. This accumulation decreased the effective heat transfer surface and restricted water flow.

In short, the old magnetic system proved to be ineffective for scale control in this application. What’s more, this system’s failure to alleviate scale formation in the condenser tubes resulted in higher-than-design condenser pressures, which created other operating concerns.

“High condenser pressure increases the chiller’s energy consumption, and if the pressure increases enough, it will force the compressor into surge. A surge condition limits a chiller’s ability to produce cooling, and if left unchecked, can lead to significant compressor mechanical failures,” commented Ned Hebert, zone service manager at York’s Saint Rose, LA office.

Chiller tube fouling can also increase chiller energy consumption. For example, with a fouling factor of 0.003 (0.036-in. scale thickness), the additional energy cost per year for a 500-ton chiller is $25,300.

“Energy use was rising, and maintenance and water treatment costs were going up as well. The magnetic system just wasn’t working and we had to do something to protect our investment for Hilton and its guests,” stated Glenn Ziegler, the hotel’s chief engineer.

Traditional cleaning

Once scaling occurs, traditional tube cleaning involves acid, steel brushes, and abrasives. This method may shorten tube life which, in turn, leads to tube replacement. Also, acid disposal may pose environmental concerns.

Ziegler acted quickly to halt the mineral deposits. In April 1998, an ED2000 electronic anti-tube- fouling system (from York International Corp., York, PA) was installed on each of the condenser water supply lines to the three chillers; the units were also added to the cooling towers’ makeup water supply inlet piping.

The system’s electronic process is based on patented technology, inducing dissolved mineral ions to precipitate into larger insoluble crystals, which pass through the condenser without adhering to the tube walls.

The process is called solenoid-induced molecular agitation (SIMA™). The insoluble crystals settle at the bottom of the cooling tower sump, where they are flushed from the system during blowdown.

Using such a system, “You eliminate the hassles of cleaning tubes with acid, steel brushes, and abrasives. You also save the wear and tear on tubes caused by these cleaning methods,” Ziegler noted.

The system is installed without welding or other invasive procedures, according to the manufacturer. The hardware includes an electronic control box attached to a prewrapped solenoid coil in a weather-resistant enclosure. The solenoid coil is externally fitted to the condenser inlet pipe. Installation takes about 20 min. There is no downtime.

Clean machine

The condenser water loop continues to be treated by a combination approach: the anti-fouling unit for scale control and chemicals for biological control.

About 10 months after the anti-fouling devices were installed, the condenser heads were removed from the three chillers. When the tubes were inspected, no evidence of scale was detected.

In December 1999, a post-installation water chemistry analysis performed by an independent laboratory supported the physical results. The tests showed a significant increase in the amount of calcium ions precipitating out of the tower water.

When compared to the raw makeup water, which was determined to have respective chloride and calcium levels of 84 and 134 parts per million (ppm), the tower water showed chloride and calcium readings of 500 and 400 ppm.

“The ED2000 prematurely precipitated scale, causing the system to take longer to reach the TDS [total dissolved solid] blowdown setpoint. The result was an increase in cycles of concentration and water savings,” noted Ziegler.

Less calcium in the tower water created a proportional increase in chloride concentration, he explained, allowing increased concentration cycles from 3.4 to 5.8, saving up to $3,157 per year in water expenses.

In all, cleaner condenser tubes are predicted to reduce chiller energy usage by about $7,303 per year by improving the chillers’ efficiency from about 0.80 to 0.75 kW/ton.

“Even if these symptoms aren’t evident yet, if you are in a hard-water area like us, scale is likely to be lurking in your tube bundles,” the chief engineer warned.

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

ACHRNEWS

NEWS 04-21-14 cover

2014 April 21

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con