When troubleshooting walk-in freezers, technicians often find a frozen evaporator coil. Although there are several possible causes, one common cause involves the defrost system. For some reason, the system is not properly defrosting the evaporator's coil on a regular basis. In order to effectively troubleshoot this problem, a technician must understand the design and operation of the defrost systems typically used.
One popular method of defrosting walk-in freezers is the electric defrost system. This is comprised of several components, including a defrost timer, resistive heater(s), defrost termination switch, fan cycling control, and drain line heater. An electric resistance heater is placed on the outer surface of the evaporator's coils. The energized heater supplies enough heat to completely defrost the coils.