Troubleshooting The Potential Starting Relay

November 3, 2002
/ Print / Reprints /
ShareMore
/ Text Size+
A simple ohmmeter is all that is needed to troubleshoot a potential relay. After taking all of the connecting wires off of the potential relay, measure the resistance across the 1 and 2 terminals. The resistance should read close to zero, since there are normally closed contacts between terminals 1 and 2. If the meter reads infinity, the contacts are stuck open, and the relay should be discarded and replaced. (See Figure 1.)

If the normally closed contacts between terminals 1 and 2 are dirty or arched and pitted, there is a chance the ohmmeter may read a resistance greater than zero but less than infinity. For example, if the ohmmeter reads 200 ohms, the potential relay should still be discarded because of dirty or pitted contacts.

OPENED CONTACTS

Open contacts between terminals 1 and 2 will prevent the start capacitor from being in the circuit. The start capacitor is a high microfarad capacitor, which is in series with the start winding. (See Figure 2.) The start capacitor gives the start winding circuit more capacitance and gives the current a leading effect (phase shift) on the voltage.

The more the current leads the voltage wave, the more phase shift there will be, and the motor will have more starting power or torque. Without the start capacitor, the motor will usually lock its rotor and draw locked rotor amps (LRA). This will cause the motor’s overload to open and the motor will short-cycle on the overload. This short-cycling is detrimental to motor windings, starting relays, and capacitors because of its overheating effect.

CLOSED CONTACTS

Often, the relay contacts could be stuck or arched in the closed position. In this case, the start capacitor would never be taken out of the circuit. The motor would be stuck in its starting mode and draw high amps. The amp draw would be somewhere between running load amps (RLA) and locked rotor amps (LRA). The motor’s protective device would soon open. A short-cycling situation would occur.

If the contacts are stuck in the closed position, the relay would have to be checked with a voltmeter in the running mode, since the contacts between 1 and 2 are normally closed when not in operation. Once the motor is up and running, use a voltmeter to measure the voltage between terminals 1 and 2. A voltage reading of zero would prove that the contacts are not opening. (See Figure 3.) Also, a high amp draw from the start capacitor and start winding circuit still being energized is a telltale sign that the contacts have not opened.

RELAY COIL

After disconnecting all wires from the relay, ohm the coil between terminals 2 and 5. Since the coil should have a very high resistance, make sure you are using the proper scale on the ohmmeter. The (R x 100) scale is a good one to use. The R x 1 scale can fool a technician into believing that there is an open coil because of the coil’s extremely high resistance. It is not uncommon to have the resistance read in many thousand ohms.

If the ohm reads infinity on the (R x 100) scale, the relay coil is opened. The relay should be discarded and a new one installed. An opened relay coil will prevent the contacts between 1 and 2 from opening. This is caused from no magnetism in the iron core that the coil is wrapped around. This, again, will cause high amp draws. Always use the model number of the old relay when ordering a new one, or cross-reference it with a different manufacturer’s relay.

Tomczyk is a professor of HVAC at Ferris State University, Big Rapids, MI, and the author of Troubleshooting and Servicing Modern Air Conditioning & Refrigeration Systems, published by ESCO Press. To order, call 800-726-9696. Tomczyk can be reached at tomczykj@tucker-usa.com (e-mail).

Publication date: 11/04/2002

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

terminal contact CR Infinity

neil
December 29, 2009
i want to ask about how to particle can be stick on the surface of contact terminal

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-14-14 cover

2014 April 14

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con