Refrigeration / Ice Machines

The Professor: Ice Flake Machine Troubleshooting

February 7, 2011
/ Print / Reprints /
ShareMore
/ Text Size+
Figure 1. A cutting edge, or flight, is shown to the right in this photo of an auger. (Courtesy of Ferris State University.)

This article is part one of a two-part series on ice flake machine troubleshooting. This article will examine troubleshooting low and high water levels. Next month’s article will examine water impurities and mechanical problems.

Many ice flake machines employ an auger rotating within an insulated freezing cylinder or evaporator. The auger, which is driven and geared down by a gear motor and gear box to about 8-16 rpm, has cutting edges or flights. The flights shave ice from the walls of the freezing cylinder (evaporator) which is flooded with water and has refrigerant lines wrapped around its outer circumference (Figure 1). The refrigerant lines have vaporizing refrigerant in them which will freeze the water that is in close proximity or contact to the inside of the freezing cylinder.

Figure 2. This schematic shows the relationship of the water level with the freezing cylinder in a flake ice machine. (Courtesy of Hoshizaki America.)

A water reservoir supplies the right height or level of water to the freezing cylinder.

Because water will seek its own level, the water level or height in the water reservoir will also be the level in the freezing cylinder (Figure 2). Water level in the reservoir is usually controlled by a single float mechanism, or a dual-float mechanism which controls an electric solenoid valve to bring water to the reservoir.

The water-logged shaved ice is then carried through the water to the top or head of the freezing cylinder where it is squeezed, extruded, shaped, cut and eventually falls to an insulated ice storage bin for use (Figure 3).

It is of utmost importance that the water level in the reservoir and freezing cylinder are at the proper levels for the ice flake machine to operate effectively. What follows are some scenarios for improper water levels in the freezing cylinder, and how they affect other components of the ice flake machine.

LOW WATER LEVELS

If a float mechanism in the water reservoir is adjusted wrong and the water level is low in the reservoir, it will also be low in the freezing cylinder because of water seeking its own level. Since water is the refrigerating load for an ice flake machine, low water level in the freezing cylinder means low load on the evaporator. This condition will cause lower than usual evaporator pressures, thus lower evaporator temperatures.

These low evaporator temperatures will produce harder and colder ice for the auger to cut. This will put an extra load on the auger, gears, and gear motor. Often, the gear motor will trip on its overload and sometimes has to be manually reset. Water reservoirs should have a line indicating the correct water level for that particular machine.

Figure 3. Water-logged shaved ice is carried through the water to the top or head of the freezing cylinder where it is squeezed, extruded, shaped, cut and eventually falls to an insulated ice storage bin for use. (Courtesy of Ferris State University.)

HIGH WATER LEVELS

If the float mechanism in the water reservoir is adjusted wrong, or the seat in the float chamber is leaking and the water level is too high, the freezing cylinder will experience high water levels. This will cause stress on the gear motor from the auger doing more work because there is more surface area of ice to cut.

Again, the overload may trip on the gear motor. When the gear motor’s overload reset button must be reset often, a service technician should suspect water level problems as a possible cause. Often, high water levels will cause water to pour over into the ice storage bin and cause a large melting depression in the stored flaked ice. Also, this new water constantly coming into the freezing cylinder will impose extra heat load on the evaporator and cause higher than normal evaporating pressures and poor ice quality and quantity. This happens because the higher quantities of new water will have to be refrigerated to the freezing point to start making ice.

Publication date: 02/07/2011

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Recent Articles by John Tomczyk

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

ACHRNEWS

NEWS 04-21-14 cover

2014 April 21

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con