Systematic Troubleshooting

John Tomczyk

The problem we are going to deal with in this and next month’s columns is a restricted liquid line after the receiver. In this column, we will look at eight possible symptoms. In the Dec. 3 column, we will look at a couple of other issues. For both columns, we will use a service checklist that shows that the system has a TXV valve, filter drier, and sightglass. The refrigerant is R-134a.

Here are the measured values:

• Compressor discharge temperature is 125°F.

• Condenser outlet temperature is 70°.

• Evaporator outlet temperature is 30°.

• Compressor inlet temperature is 60°.

• Ambient temperature is 70°.

• Box temperature is 30°.

• Compressor voltage is 230.

• Compressor amperage is low.

• Lowside (evaporating) pressure is 1.8 pounds per square inch gauge at -10°.

• Highside (condensing) pressure is 95 psig at 85°.

Calculated values in °F are:

• Condenser split, 15°.

• Condenser subcooling, 15°.

• Evaporator superheat, 40°.

• Compressor superheat, 70°.

Causes for restricted liquid lines or restricted components in the liquid line could be:

• Restricted filter-drier from moisture, dirt, oil, or sludge.

• Restricted TXV screen or orifice.

• Kinked liquid line.

• Restricted liquid line solder joint.

• Receiver outlet valve (King Valve) partially closed off.

Many technicians believe that when any part of the system’s high side is restricted or plugged, head pressures will elevate. This is simply not the case especially on a TXV/receiver system. A restricted liquid line will starve the evaporator of refrigerant, causing low evaporator pressures. With a starved evaporator, the compressor and condenser will also be starved. This will cause a low condensing pressure. Most of the refrigerant will now be stored in the condenser and receiver simulating a pumped-down system.

SYMPTOMS

Some of the symptoms could be:

• Higher-than-normal discharge temperature.

• High superheats.

• Low evaporator pressures.

• Low condensing pressures.

• Normal to a bit high condenser subcooling.

• Low condenser splits.

• Low amp draw.

• Short cycle of the low-pressure control (LPC).

Higher than normal discharge temperature: High discharge temperatures are caused from high compressor superheats. A starved evaporator will cause the high superheats. High compression ratios from the low evaporator pressure will cause high heat of compressions, thus high discharge temperatures. This is assuming there is still some mass flow rate of refrigerant. The severity of the restriction will determine how high the discharge temperature will be. If the system becomes completely restricted, the compressor will pump down the system and stay off on the low-pressure control.

High superheats: Both evaporator and compressor superheats will be high. This is caused from the TXV, evaporator, and compressor being starved of refrigerant from the liquid line restriction. Most of the refrigerant will be in the receiver, with some in the condenser.

Low evaporator pressure: The low evaporator pressure is caused from the TXV and compressor being starved of refrigerant. The compressor is trying to draw refrigerant from the evaporator through the suction line, but the liquid line restriction is preventing refrigerant from entering the evaporator. This will cause the compressor to put the evaporator in a low-pressure situation.

Low condensing pressure: Since both the evaporator and compressor are being starved of refrigerant, so will the condenser. Reduced refrigerant to the evaporator will cause a reduced heat load to be delivered to the condenser. The condenser in turn does not have to elevate its temperature and pressure to reject heat.

Normal to a bit high condenser subcooling: Since the condenser is being starved, it is not condensing much vapor to liquid. All of the liquid in the condenser will probably sit there for a while and sub-cool because of the low refrigerant flow caused from the restriction. The receiver will have a reduced flow in and out of it. Most of the refrigerant will be in the receiver with some in the condenser. If the receiver is in a hot ambient, sub-cooling may be lost as refrigerant sits in the receiver. This is why some commercial systems have receiver bypasses for certain situations. Receiver bypasses are nothing more than a liquid line solenoid valve controlled by a thermostat, which will bypass liquid around the receiver to the liquid line.

Low condenser splits: Because the condenser is being somewhat starved, there is not much heat to reject. This will cause low condenser splits. Remember, the split is the temperature difference between the condensing temperature and the ambient.

Low amp draw: Because the compressor is being starved of refrigerant from the restriction in the liquid line, it will not have to work as hard in compressing what vapors do pass through it. The low density of the vapors from the low evaporator pressure will require less work from the compressor, requiring a low amp draw.

Short cycle of the low-pressure control: The LPC will cycle the compressor off and on from the low evaporator (suction) pressures. Once off, refrigerant will slowly enter the evaporator and cycle the compressor back on. This on and off of the compressor will continue until the problem is fixed.

Publication Date: 11/05/2007

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

John Tomczyk is a professor of HVACR at Ferris State University, Big Rapids, Mich., and co-author of Refrigeration & Air Conditioning Technology, seventh edition, published by Delmar Cengage Learning. To order, call 800-648-7450. Tomczyk can be reached by email at tomczykj@ferris.edu.

Recent Articles by John Tomczyk

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2013 ACCA Conference & IE3 Expo

Photos from the 2013 ACCA Conference & IE3 Expo in Orlando, Fla.

Podcasts

Cade Clark, assistant vice president of government affairs for the Air-Conditioning, Heating & Refrigeration Institute (AHRI), gives a brief overview of the new version of the Shaheen-Portman bill, what AHRI thinks of the energy-efficiency legislation, and how it might affect the HVACR industry if it becomes law.
More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 05-20-13 cover

2013 May 20

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

HVAC LEASING

Some HVAC contractors have introduced leasing programs for consumers. Do you think this is a viable option?
View Results Poll Archive

Clear Seas Research

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con