Saving With Thermal Storage
May 7, 2007
More than 15 years ago, the leadership at IBM Corp.
challenged the management of the company’s facilities to reduce energy
consumption by 4 percent each year. The staff at IBM Bromont, a semiconductor
manufacturing facility in Bromont, Québec, has consistently met that objective,
saving close to 500,000 MWh in energy during the last 15 years.
As the facility continues to improve its energy efficiency,
however, the ability to record additional energy savings is becoming
increasingly more difficult and leading the Bromont facility to consider new
technologies to achieve its goal.
One of the technologies the company adopted combines a
Novanergy® thermal-energy-storage (TES) system and a YORK® variable-speed
chiller from Johnson Controls.
According to those monitoring the $2.6 million project, the
upgrades are yielding energy and power savings that translate to $350,000
annually. And the ‘green’ factor entered into the equation. The project offers
environmental benefits as it reduces the plant’s refrigerant requirements by 50
percent and its greenhouse gas (GHG) emissions by 35 percent.
REPLACING AGING CHILLERS
IBM Bromont is an 800,000- square-foot facility located near
Montreal that assembles semiconductors from around the world on substrates to
ultimately create microprocessors. These microprocessors are used in Game Cube,
X Box and Playstation game consoles, as well as IBM servers.
In 2005, it was decided to replace two 25-year-old chillers
that used R-12, a no longer produced CFC refrigerant. The chillers were part of
a power plant that also included six 1,000-ton chillers and a 1,000-ton
free-cooling heat exchanger that typically ran from Dec. 15 to March 15.
Together, the chillers and heat exchanger provided chilled
water year-round to meet process-cooling demands. As plant personnel looked to
replace 2,000 tons of cooling capacity, their desire to improve the overall
efficiency of chilled-water production caused them to look at alternatives to
the existing system.
Daniel Paré, advisory engineer at IBM Bromont, recalled an
article he read about TES systems and the phase-change materials (PCMs)
manufactured by another Canadian firm, Groupe Enerstat Inc. “I decided to call
Enerstat, and I invited the company’s president, Dr. Stéphane Bilodeau, to
visit our facility and determine whether their system might fit into our plant.
It soon became apparent that the approach to chilled-water production offered
the potential for significant energy savings, and we agreed to use the TES
system.”
STORAGE SHIFTS
The system uses a chiller to charge its storage tanks at
night, taking advantage of off-peak electricity rates. A thermal fluid
circulates through the storage tanks and stores or draws Btus by changing the
state of the PCM from liquid to solid and vice versa at prescribed temperature
set points.
As the stored cold energy discharges, it provides cooling
during daytime peak hours when electricity rates are typically higher. Benefits
to the building owner include reduced energy usage and costs. The benefit to
the power utility is shifting consumption from day to night, when there is less
demand for electricity.
In addition, PCMs are able to store large quantities of
energy in a smaller space than a traditional chilled-water-storage system,
according to those familiar with the technology.
The project consisted of a 1,500-ton variable-speed chiller,
two 1,600-ton-hour TES tanks, a 2,500-ton plate heat exchanger, a glycol loop
and two pumps. Two separate PCMs offered melting points of 28°F for one tank
and 40° for the second tank.
“The PCMs are excellent energy accumulators (better than
ice) for faster energy transfer,” explained Pare. “And, unlike ice, PCMs do not
expand during the phase change from liquid to solid, eliminating stress on the
tank. In addition, because the tanks are sealed during manufacturing, there is
also less risk of contamination.”
PARTIAL STORAGE
To maximize the energy plant’s efficiency, Enerstat used a
partial-storage approach in which the chiller operates to handle part of the
cooling load in peak periods, and the TES tanks handle the rest of the demand.
This enabled IBM to reduce the size of the chiller.
Because company officials wanted to periodically operate the
system at temperatures below 32°, they opted to use ethylene glycol as the
thermal fluid. They then searched for a chiller that would be able to operate
efficiently in a secondary thermal storage loop, with variable tower-water and
chilled-liquid temperatures.
TEMPERATURE FLEXIBILITY
In selecting a chiller for the system, IBM officials relied
on the experience of André Paré, manager, commercial and industrial products
with The Master Group, Boucherville, Québec. “What amazed me as I considered
the appropriate chiller for this application was the range of operation of the
centrifugal chiller with variable-speed drive. It allowed efficient operation
at a wide range of off-design conditions,” he said.
In the TES system, tank MCP1 is situated before the chiller
(in the secondary loop), and tank MCP2 is located after the chiller. Set at
40°, one storage tank operates continuously. It can be charged and discharged
several times in a 24-hour period. The other tank is set at 28° and is used to
support fluctuations with large amplitude. It is charged and discharged one or
two times a day. According to Paré, “This project requires a lot of flexibility
on the part of the chiller as it works with a variety of low-side and high-side
temperatures. The excellent efficiency of the chiller at off-design conditions
is a tribute to the variable-speed drive.”
Bilodeau added, “Typically, a drive like this would see only
variations in the tower-water temperature and the building load. In this case,
the drive also sees variations in the chilled-liquid temperature at the same
time.”
TES SYSTEM
The project at the plant demonstrates the ability of a TES
system to reduce not only energy consumption (kWh), but also the peak-power
requirement (kW). By running a smaller chiller during the daytime, electricity
demand is scaled back.
In a partial-storage TES system, the chiller typically runs
at full capacity for 24 hours per day. When the building load is less than the
chiller output, the surplus thermal energy is stored in the TES tanks. When the
load exceeds the chiller output, the tanks satisfy the additional cooling
requirement. On site, the reduction in kW demand is more than 1 MW.
To reduce energy consumption, the chiller operates
efficiently at off-design conditions, with consumption ranging from 0.4 to 0.6
kW/ton compared to the performance of the former chillers of 0.6 kW/ton to 0.9
kW/ton. Additionally, operating the chiller at night with reduced tower-water
temperature represents an improvement in chiller performance by as much as 15
percent.
The TES system also increases the capacity of the existing
free-cooling heat exchanger (FCHE) from 750 tons to a maximum of 1,250 tons.
When daytime ambient temperatures are too warm to use the FCHE, evening
temperatures are often still low enough to charge the TES tanks. IBM can thus
extend the free-cooling period from three months to nine months a year, adding
more than 3,000 free-cooling hours per year and allowing IBM to recuperate more
than 800 tons of free cooling and cut its power consumption by 900 kW. Annual energy
savings amounted to 5,300 MWh.
According to Bilodeau, “The installation of a TES system
that integrates synthetic phase-change materials with free cooling and a
variable-speed-drive chiller was the first of its kind in North America. The project
size was also a first. The storage tanks store more than 50 million Btu per
charge.”
Enerstat also designed a control strategy for the project
that involves the real-time computation of the thermodynamic balance and a
predictive model of the coming peak loads.
ENVIRONMENTAL IMPACT
By replacing the two 1,000-ton CFC-12 chillers with one
1,500-ton chiller that uses HFC-134a, IBM reduced refrigerant requirements by
50 percent. The company also experienced a 35 percent reduction in greenhouse gas
emissions for chilled-water production because of the energy-efficiency
improvement.
The $2.6 million price tag for the project included $1
million already budgeted to replace the two chillers and $1.6 million for the
TES system. With energy savings of 5,312 MWh, which at a low cost of
$0.0274/kWh adds up to $145,500, and annual demand savings of $205,500, the
folks at Bromont are looking at total annual savings of $350,000 and a payback
period of seven years. This estimate does not include savings associated with
upkeep, pumping costs and maintaining water temperature according to
specifications during electrical fluctuations.
For more information, visit www.yorkupg.com.
Publication date: 05/07/2007