Burnouts cause moisture, acid, soot, and hard-core carbon deposits to contaminate the condenser and evaporator and clog the filter-drier. Contaminants may also enter the compressor itself and cause irreparable damage.
If these contaminants are not completely removed from the system, you run the risk of repeated compressor burnout and failures.
After a compressor burnout, a service technician would clean the interior compressor coils by spraying liquid R-11 (which was inexpensive, easy to use, and legal to vent into the atmosphere) directly into the interior of the condenser and evaporator coils. The refrigerant would flush out the contaminants and then evaporate, leaving the coils clean, residue-free, and ready for use.
This cleaning process is no longer legal. In addition to having phased out the production of CFC refrigerants, the Montreal Protocol prohibits the use of liquid refrigerants such as R-11 or -12 as a solvent and cleaner when vented into the atmosphere.
Although you can still obtain select CFCs, they are expensive, highly regulated, and users can be fined heavily if these products are misused.
Since the use of CFCs is impractical and HFCs are ineffective for coil cleaning, using an internal coil-flushing agent is the alternative.
Some coil flush chemicals have been designed for specific applications, such as automotive a/c systems. Others encompass a broader range of applications.
Since these are non-pressurized liquids, the technician must purchase a pumping device such as a motorized chemical-acid-oil pump to circulate this chemical throughout the system. A hand oil pump can be used on small applications, such as domestic refrigerators or vending machines, to move the flushing agent throughout the coils.
It is important that the system be broken down into segments (condensing coils separated from the evaporating coils), or that components such as the drier, accumulator, receiver, expansion valve, or capillary tube be bypassed to allow unrestricted flow and non-trapping of the chemical at any point in the system.
In order to completely dissolve oil, carbon, and tar deposits, it is necessary to completely fill the coils with the interior coil flush. The flushing period should be no less than 20 to 30 min.

When the coil flush is blown out of the system with dry nitrogen, acid, oil, and carbon are completely removed from the interior coil lines.
The chemicals in some brands of coil flush are completely miscible with mineral, polyolester, alkylbenzene, and PAG oils. Circulating these coil flushes can eliminate up to 100% of these oils. (A second flushing may be necessary with some coil-flushing agents currently on the market.)
This process can be done in less than 2 hrs, depending on the size of the system and the type of circulating pump being used.
Service companies must evaluate which coil-flushing agents will accomplish the task without compromising employees’ or customers’ health.
Seal and diaphragm materials such as neoprene, santoprene, nitrile, and polypropylene have a limited compatibility with some coil-flushing agents. Swelling or deterioration may occur that could cause pump failure, and/or leaks, and/or requiring the replacement of the impeller, diaphragm, O-rings, or valves.
Pumps manufactured with Viton® or Teflon® appear to be the most resistant to the chemicals that make up the coil-flushing agents.
There have been a limited number of products and methods to fully clean and prepare the interior lines in an air conditioning or refrigeration system, particularly after a compressor burnout or in a retrofit application.
Ultimately toxicity, flammability, and VOC levels must be considered from personal and environmental safety standpoints.
The decision of which product to use to clean out your customers’ coils may be difficult, but the decision of whether or not to clean your interior coils is obvious: You must.
For more on this topic, visit www.achrnews.com for a sidebar to this story entitled “The Circulating Pump Method.”
1. Recover the entire refrigerant from the system according to the recovery system guidelines and drain all available oil.
2. Disconnect the compressor, drier, accumulator, receiver, and expansion valve or capillary tube from the system.
3. If cleaning the entire system at the same time, connect the tubing where the drier, accumulator, receiver, expansion valve, or capillary tube was taken off-line with vinyl tubing. However, it may be easier if the evaporator and condenser coils are separated from the system and cleaned individually. Always start from the evaporator side, which is considered less contaminated than the condenser.
4. Measure the correct amount of coil flush to fill the coils completely (approximately 1 gal/ton for each coil) and place it in an appropriate-size container. It is important that a notation be made of the exact amount of the coil flush introduced into the coils.
5. Connect a section of vinyl hose from the container to the intake side of the circulating pump and a second section of hose from the outlet side of the pump to the low side of the coil. A third section of hose will be needed to connect the high side of the coil to the container of coil flush. This creates the closed-loop system.
6. Turn the pump on and circulate the coil flush throughout the coils for 20 min or longer.
7. After circulating this chemical throughout the coils, remove the tubing from the pump, and blow the system out with 100 psi of nitrogen, so any remaining coil flush is removed from the system into the original container.
8. Collect the coil flush and measure the amount of coil flush that was returned to the container. Compare this amount to that which was originally introduced into the coils. Do not leave more than 5% of any coil flush in the system. Otherwise, you run the risk of putting too much pumping pressure on the system. Repeat steps 4-7 to clean the condenser coil.
9. Test the system for any oil, acid, or contaminants. Repeat the above steps if necessary and test again. Dispose of the used coil flush according to federal, state, and local guidelines.
10. Clean out the accumulator, receiver, and expansion valve separately.
11. Refit the system with the proper capillary tube/expansion valve and drier according to industry standards. Reconnect a new compressor and all remaining components.
12. Using a vacuum pump and micron gauge, evacuate the system to a minimum of 300 microns in order to remove any coil flush, nitrogen, moisture, or noncondensable. Recharge the system with refrigerant and oil according to the manufacturer's specifications.
13. Start the equipment and make any necessary adjustments.
NOTE: The above procedure is considered as a general guideline only. Please check with the manufacturer of the unit for additional procedures or precautions regarding the use of any of the coil-flushing agents.