A visual inspection should be made to verify the condition of safety relief valves. While performing this inspection, some of the conditions to watch for are:
Stacking relief valves is a common maintenance error. This involves adding a second relief valve onto the outlet of an existing relief valve that is leaking. This is not permissible by code.
By installing two relief valves in sequence, you add back pressure above the first relief valve piston, causing a change in the pressure setting. For example, the estimated relieving pressure of a valve stack could be:
First relief valve 300 psi setting
Second relief valve + 300 psi setting
Total valve stack 600 psi setting
As the relief flow then passes through the second valve, the valve stack also experiences a change in its relieving capacity.
Whether stacked relief valves or any of the other previous conditions exists, the valve should be replaced.
The condition of the discharge piping should also be inspected. Valves should be piped to ensure that they do not collect dirt and debris.
Vent pipes should be protected to prevent the entrance of rainwater, which would inhibit valve operation. Any problems with the vent line should be corrected.
First of all, relief valves should be changed out after they discharge, to ensure that the system will still be safeguarded by a properly set valve.
Most systems are subject to accumulations of piping debris, such as metal shavings and solder impurities, as the system is fitted for installation. These impurities are generally blown into the relief valve seats at the time the valve is discharged. The impinged debris then inhibits the relief valve from reseating at its originally set pressure.
In addition, the valves are then found to relieve at considerably lower pressure settings than the stamped valve setting due to the force of the reclosing action.
City, state, or federal regulations may dictate the replacement of valves that have not discharged. Their replacement may also be regulated by industry standards, company policies, insurance requirements, and/or unwritten accepted standards of good practice.
In the case of city, state, and federal regulations and insurance copy regulations, there appear to be no written rules covering the replacement schedule. However, these agencies do govern by verbal requirements requesting that system owners/operators provide proof of the reliability of the existing relief valves.
The International Institute of Ammonia Refrigeration (IIAR), in its Bulletin 109, “IIAR Minimum Safety Criteria for a Safe Ammonia Refrigeration System,” recommends that the relief valve be replaced or inspected, cleaned, and tested every five years.
ANSI Standard K61.1-1989, “Safety Requirements for the Storage and Handling of Anhydrous Ammonia,” is very specific in its requirements. Paragraph 5.8.15 states:
“No container pressure relief devices shall be used after the replacement date as specified by the manufacturer of the device. If no date is specified, a pressure relief valve shall be replaced no later than five years following the date of its manufacture, etc.”
In industrial refrigeration, the current recommendation is to replace the relief valves on a five-year cycle. However, be sure to check with the other agencies to verify that a more stringent regulation is not applicable.
By following these simple rules and recommendations, you can assure your customers that their systems are protected by properly functioning relief valves.