Bob is a service technician who is well trained and
nationally certified. However, he sometimes suffers from the same confusion
that all technicians occasionally do - the facts that he gathers may or may not
point to the obvious cause of the problem or the best solution. But Bob has
something that no one else has. He recalls his long-time HVACR mentor and
imagines him accompanying him as “Btu Buddy,” someone who reminds him to take
time to stop and think before rushing to judgment, helping keep him on the
right track, even with facts that are confusing.
Bob had changed a compressor on a 5-ton air conditioner that
cooled the clubhouse at an apartment complex. He was just about ready to charge
the unit when a problem came up. He had added a liquid line drier and sight
glass just after the drier at the outdoor unit and had leak checked the
connections that he had made and was satisfied there were no leaks. He had
pulled a vacuum down to 500 microns on his electronic vacuum gauge and was
letting it sit for a few minutes and he noticed a rise in the vacuum gauge to
1,000 microns. He was scratching his head when Btu Buddy asked, “What is the
problem, Bob? You looked puzzled.”
Bob described what he had done, then said, “This system is 15
years old and has never had refrigerant added to it according to its history. I
don’t get it; there should not be a leak.”
Btu Buddy asked, “Why did you change the compressor?”
Bob explained, “The compressor was just turning, not pumping, so
I changed it. I will need to start it up to explore what the problem may be.”
Meanwhile the vacuum gauge had climbed to 1,500 microns. There
was a leak somewhere. Bob asked, “Could there be moisture or refrigerant in the
system still boiling and making the pressure rise?”
Btu Buddy said, “It is not likely. Let’s just let it sit for a
few more minutes and see. If it is moisture or refrigerant still in the lines,
it will stop soon. It is not likely that you could have lowered the pressure to
500 microns with water or refrigerant still in the system.”
They waited for 30 minutes and Bob examined the system while
waiting. He changed the filters, oiled the motors, and while he was at the
evaporator he found a potential problem, but it didn’t have anything to do with
the possible leak.
Bob said, “The expansion valve bulb is loose on the suction line
at the evaporator. It looks like someone just loosened it for no reason.”
Btu Buddy explained, “Some older technicians who only go by the
touch system of checking superheat may have loosened it to get more refrigerant
flow, most likely while touch testing the suction line. The problem with that
is they would not know how much more flow they created.”
Bob said, “I bet that is what ruined the compressor. I bet the
oil in the crankcase was washed out and the bearings seized and the crankshaft
broke. You could hear the old compressor turn, but nothing happened. It had
very low amperage when I checked it.”
Btu Buddy said, “That is a good assessment of what may have
happened. How does the vacuum look?”
Bob said, “It is up to 2,500 microns.”

Figure 1. This valve arrangement can isolate
the vacuum pump from the sensor and the sensor from the system. (Figures are
from Refrigeration & Air Conditioning Technology,
5th Edition, by William Whitman, William Johnson, and John Tomczyk, published
by Thomson Delmar Learning.) (Click on the image for an enlarged view.)
Btu Buddy said, “The vacuum rise tells you that you have a leak,
but not where it is. Put a trace of R-22 in the system and push the pressure up
to 150 psig with nitrogen and let’s look around. The first thing that you need
to check is your connections. Remember they were added to the system while you
were doing your work. It is not uncommon for a gauge manifold to leak.”
Bob turned off the valve to the vacuum gauge and added the
refrigerant and nitrogen (Figure 1). He then used his leak detector to leak
check his own gauges and connections he had made for pressure testing and found
them all to be good.
He then started over the connections at the compressor and the
drier and sight glass connections.
Bob said, “Wow, there is a small leak around this sight glass
connection that I don’t believe was here before.”
Btu Buddy then said, “It may not have been there when you leak
checked it. Notice that connection is made with 45 percent silver because the
connection is brass and you had to use flux to make the connection. Take a
close look at where the leak is. Use soap to pinpoint the leak. Tell me what
you find.”
Bob looked close and said, “It looks like the leak is under a
bubble of flux.”

Figure 2. This illustration shows how a leak
can be covered up by the flux. If the flux had not popped up with pressure on
the system, it would have been sucked into the hole and would appear later
during normal operation. (Click on the image for an enlarged view.)
Btu Buddy said, “That is exactly where it is. I noticed that you
didn’t chip away the flux after the connection cooled. There is a pinhole under
the flux that may have been closed when you leak checked it, and while working
around the connection, you loosened the flux and the flux raised up off of the
leak (Figure 2).”
Bob let the nitrogen and trace of R-22 out of the system and
repaired the leak. This time he used a screwdriver tip to chip away the flux
after it had cooled. He then pressurized the system again and there was no more
leak. He then let out the nitrogen and started the vacuum pump.
As the vacuum pump ran, Bob said, “I could have saved some time
on that one. I can’t really charge the customer for that mistake that cost
about an hour of labor.”
Btu Buddy said, “Well, some technicians would charge the customer
anyway, but they are not treating the customer like they would like and expect
to be treated.”
When the vacuum pump was shut off at 500 microns, the system was
allowed to sit for 15 minutes and there was no rise in the micron reading.
Bob then said, “I am going to charge the unit and consider it
repaired after startup.”
Btu Buddy said, “Don’t you think that you should check the
superheat after startup? You shouldn’t just presume the valve is working
correctly.”
Bob charged the unit and checked the superheat at the condensing
unit and it was 15°. The line set was about 35 feet long, so this looked about
right. He then said, “Well, another lesson that turned out OK. I didn’t charge
the customer for the extra time that I wasted in haste.”
Btu Buddy then said, “That is the best thing to do; be fair and
honest.”
Publication
date: 10/22/2007