All of the electrical loads, including HVAC, in Halifax Health’s new 10-story France Tower are backed up by a 4.5 MW MTU Onsite Energy standby power system.

DAYTONA BEACH, Fla. - Halifax Health is the largest medical center in east central Florida, with 944 beds and 500 physicians representing 46 specialties. Founded as a small community hospital in 1928, it has steadily expanded over the decades, and is now consistently ranked in the top 5 percent of all medical centers in the country in clinical outcomes. When Halifax Health recently added the new 10-story France Tower to the campus for inpatient and emergency treatment, it selected a 4.5 MW MTU Onsite Energy standby power system from Florida Detroit Diesel-Allison, the local distributor for MTU Onsite Energy.

Named in honor of the Bill France family, owners of Daytona-based NASCAR, the France Tower contains one of the largest operating rooms on the East Coast in addition to a central plant that houses the new standby generators, boilers, and chillers. Having a reliable standby power system is not only required by code, but is necessary as a practical matter, because this area of coastal Florida is hit frequently by hurricanes and thunderstorms that cause disruptions in grid power.

Three 1,500 kW MTU Onsite Energy generator sets operating in parallel are each powered by the EPA Tier 2 MTU 12V4000 engine, which the company says provides high fuel efficiency and ability to accept full rated load in one step.

POWER OUTAGES COMMON IN FLORIDA

“Summertime thunderstorms regularly wreak havoc with our local utility due to lightning strikes, but these outages tend to be of short duration,” said James Sawyer, electrical supervisor, Halifax Health. “However, there’s always the threat of bigger storms. In 2004, Hurricane Charley was a Category 4 storm that took out the entire grid, forcing us to run on standby power systems in older parts of the medical center campus from midnight until about 6 a.m. the next day.” While the new MTU Onsite Energy standby power system has not yet been required to run during an extended outage, strong hurricanes are always a possibility. As testimony to the constantly looming danger, the new France Tower has been constructed to withstand a Category 5 storm, Sawyer said.

While there have been several standby power systems installed in the medical center as it has grown over the years, those systems are sized to provide only emergency power for operating rooms and intensive care units and for egress lighting to meet life-safety codes. The older standby generators weren’t sized with the capacity to power the HVAC systems. Since current codes require patient evacuation if an area is without air conditioning for longer than 36 hours (a real possibility during a severe hurricane), Halifax Health officials sized the new 4.5 MW MTU Onsite Energy power system to supply all the loads in the new tower, including the HVAC.

THREE PARALLELED GENERATOR SETS

The power system for the France Tower consists of three 1,500 kW MTU Onsite Energy generator sets operating in parallel for a total capacity of 4.5 MW. The generator sets are powered by the EPA Tier 2 MTU 12V4000 engine, which MTU says provides high fuel efficiency and the ability to accept full rated load in one step. The electrical loads are prioritized and segmented by up to eight automatic transfer switches per generator set. When an outage occurs, all three generator sets start and assume the load when they are up to speed, in about 10 seconds. If the control system detects that only two generator sets are needed to supply the loads, one generator will shut down in order to economize on fuel, according to Sawyer.

Expansion at Halifax Health is continuing, and the new central plant has room for an additional two standby generator sets. In the meantime, Sawyer and his team are making sure that all the critical loads in the medical center are backed up with reliable standby power, no matter what the Florida weather sends their way.

Publication date: 01/18/2010

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-21-14 cover

2014 April 21

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con