Even on small boilers, the prevention of scale formation can produce substantial energy savings. Scale deposits occur when calcium, magnesium, and silica, commonly found in most water supplies, react to form a continuous layer of material on the waterside of the boiler heat exchange tubes.

Scale creates a problem because it typically possesses a thermal conductivity an order of magnitude less than the corresponding value for bare steel. Even thin layers of scale serve as an effective insulator and retard heat transfer. The result is overheating of boiler tube metal, tube failures, and loss of energy efficiency.

Fuel waste due to boiler scale may be 2 percent for water-tube boilers and up to 5 percent in fire-tube boilers. Energy losses as a function of scale thickness and composition are given in the table below.

EXAMPLE

A boiler annually uses 450,000 million Btu (MMBtu) of fuel while operating for 8,000 hours at its rated capacity of 45,000 pounds per hour (lb/hr) of 150-pounds-per-square-inch-gauge (psig) steam. If scale 1/32nd of an inch thick is allowed to form on the boiler tubes, and the scale is of “normal” composition, the table indicates a fuel loss of 2 percent. The increase in operating costs, assuming energy is priced at $8.00 per million Btu ($8.00/MMBtu), is:

Annual Operating Cost Increase = 450,000 MMBtu/yr x $8.00/MMBtu x 0.02 = $72,000

MONITOR FLUE GAS TEMPERATURE

An indirect indicator of scale or deposit formation is flue gas temperature. If the flue gas temperature rises (with boiler load and excess air held constant), the effect is possibly due to the presence of scale.

PERFORM VISUAL INSPECTIONS

Visually inspect boiler tubes when the unit is shut down for maintenance. Scale removal can be achieved by mechanical means or acid cleaning. If scale is present, consult with your local water treatment specialist and consider modifying your feedwater treatment or chemical additives schedule.

Suggested Actions

Any scale in a boiler is undesirable. The best way to deal with scale is not to let it form in the first place. Prevent scale formation by:

• Pretreating of boiler makeup water (using water softeners, demineralizers, and reverse osmosis to remove scale-forming minerals).

• Injecting chemicals into the boiler feedwater.

• Adopting proper boiler blowdown practices.

Resources

U.S. Department of Energy (DOE) - DOE’s software, the Steam System Assessment Tool and Steam System Scoping Tool, can help you evaluate and identify steam system improvements. In addition, refer to Improving Steam System Performance: A Sourcebook for Industry for more information on steam system efficiency opportunities.

Visit the BestPractices Website at www.eere.energy.gov/industry/bestpractices to access these and other efficiency resources.

Reprinted from Steam Tip Sheet #7, “Clean Boiler Waterside Heat Transfer Surfaces,” from the U.S. Department of Energy’s Office of Energy Efficiency and Renewable Energy. For more information, visit www.eere.energy.gov.

Publication date: 02/02/2009  

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 Energy Efficiency Forum

Highlights from the 25th annual Energy Efficiency Forum in Washington, D.C.

Podcasts

NEWSMakers: Jason Vogelbaugh

Jason Vogelbaugh of Alpha Controls drops in to the NEWSMakers podcast to discuss his role with the company, the InsideIQ Building Automation Alliance, and current energy-efficiency projects being worked on. Posted on Sept. 26.

More Podcasts

ACHRNEWS

NEWS 09-29-14 cover

2014 September 29

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

EFFICIENCY STANDARDS

DOE has denied AHRI’s petition for reconsideration of walk-in standards. Is it getting harder to reach consensus on efficiency standards?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con