Figure 1. Classic flow-through wall assembly.
AUSTIN, TX — It didn’t take long for Joseph Lstiburek, Ph.D., P.Eng, of Building Sciences Corp., Westford, MA, to get attendees of the Healthy Indoor Environments (HIE) 2002 Conference into the spirit of his discussion on construction defects. “The reason we have more mold problems is that we have more mold — which means we have more water problems,” he said.

Lstiburek discussed various construction methods and materials that contribute to the problem of moisture retention.

“Construction is an inherently wet process,” he explained. “The drying potential has changed; the ability of materials to dry effectively has changed.

“Building assemblies get wet from the outside, get wet from the inside, and start out wet,” Lstiburek continued. “We must control wetting from the outside, control wetting from the inside, and let assemblies dry to the inside, or to the outside, or to both sides.

“Moisture accumulates in the building envelope when the rate of moisture entry into an assembly exceeds the rate of moisture removal. When moisture accumulation exceeds the ability of the assembly materials to store the moisture without significantly degrading performance or long-term service life, moisture problems result.

“The moisture storage capacity of a material depends on time, temperature, and material properties.”

Lstiburek said that wood with a 15% moisture content or less will not decay, nor will any mold form. At 16% and higher, mold will form, and at 20% moisture content, wood will begin to decay.

“In the average home, approximately 4,000 to 5,000 pounds of wood are found in the exterior walls,” Lstiburek said. “This yields a hygric buffer capacity of approximately 400 to 500 pounds of water, or approximately 45 to 50 gallons.

“From a performance perspective, the average home can easily accommodate 45 to 50 gallons of water via hygric redistribution. Most water leaks are not a problem because of this large capacity to store water.”

Wood has always been recognized as a superior building

material, he said, because of its ability to retain moisture and then dry out.

“Matters are considerably different when the exterior walls are constructed with steel studs and gypsum sheathing,” Lstiburek said. “There is no water-storage capacity in the steel studs, and the gypsum sheathing can store approximately 1% moisture content by weight before mold colonization occurs.

“Constructing the average home with steel studs and gypsum sheathing yields a hygric buffer capacity of 5 gallons,” he explained. “In this type of an assembly, even the smallest leak can lead to problems.

CLIMATE ZONES

“Buildings should be suited to their environment, both exterior and interior,” he said. “It is not desirable to construct the same manner of building in Montreal, Memphis, Mojave, and Miami. It’s cold in Montreal, it’s humid in Memphis, it’s hot and dry in Mojave, and it’s hot and wet in Miami. And that’s just the outside environment.

“It is also not desirable to construct the same manner of building to enclose a warehouse, house, school, office, health club with a swimming pool, hospital, or museum. The interior environment clearly influences design of the building envelope and mechanical system.

“Building assemblies need to be protected from wetting via air transport and from vapor diffusion,” he said. “The typical strategies use vapor barriers, air barriers, air pressure control, and control of interior moisture levels through ventilation and dehumidification.

“Climate location and season determined the location of air barriers and vapor barriers, pressurization vs. depressurization, and ventilation vs. dehumidification.

“Moisture usually moves from warm to cold (driven by the thermal gradient) and from more to less (driven by the concentration gradient). In cold climates, moisture from the interior flows toward the exterior by passing through the building envelope. In hot climates, moisture from the exterior flows towards the cooled interior by passing through the building envelope.”

Sidebar: Specifications For Moisture Engineering

The following suggestions are recommended for moisture engineering:

  • Soil surfaces shall be graded away from below-grade envelope surfaces.

  • Materials next to below-grade envelope surfaces shall be free draining and shall connect to a sub-grade drainage system through a filter media that will prevent buildup in the drainage system.

  • A clay cap or other water-flow-resistant surface layer shall be installed to prevent surface water from draining into the free-draining material next to below-grade envelope surfaces.

  • Below-grade surfaces shall be provided with a damp-proofing layer or coating that will be effective as a capillary break.

  • All surfaces subject to wind-driven rain or snow shall be provided with a drainage plane or layer that will prevent rain wetting of internal materials.

  • Indoor dewpoint shall be maintained below the coldest surface temperature inside of the building envelope air barrier.

  • Indoor relative humidity shall be maintained below 70% as measured at the coldest indoor surface.

  • All building envelope assemblies should include at least one air barrier and one vapor retarder or vapor barrier surface.

  • All crawl space assemblies should have a continuous impermeable ground cover, which functions as both an air barrier and vapor barrier.

    Publication date: 06/03/2002