The Professor: Compressor Superheated Discharge Temps

[Editor’s Note: This is part one of a two-part article series exploring compressor overheating. This month’s article will explore the compressor’s superheated discharge temperature. Next month’s article will explore compressor overheating, which is often referred to as the number-one cause of compressor failure in the HVACR service field.]

compressor discharge valve
Figure 1. Back of compressor discharge valve. (Photo courtesy Ferris State University)
The compressor’s superheated discharge temperature can tell the service technician what is going on inside a refrigeration or air conditioning system. The compressor’s discharge temperature is a reflection of the hottest part of a refrigeration system, and there are limits as to how hot a discharge temperature should be.

The compressor’s superheated discharge temperature can be measured by placing an insulated thermistor or thermocouple on the discharge line about 3 to 4 inches from the compressor. Today’s technology allows service technicians to use an infrared-temperature-sensing device that can be purchased at a reasonable price. The compressor’s discharge temperature is a measure of the superheated refrigerants vapor temperature. Since the compressor’s discharge temperature is a superheated vapor temperature measurement, a pressure/temperature relationship does not exist, and a pressure gauge cannot be used for its measurement.

Pressure gauges can only be used for a pressure/temperature relationship when a saturation temperature (evaporating and/or condensing temperature) is needed. Since the compressor’s discharge temperature is a reflection of what is going on inside the compressor, it must be monitored very closely. The back of the compressor’s discharge valve (Figure 1) is actually the hottest part of the system, but it is impossible to measure by a service technician. The next closest place, however, is the discharge line of the compressor.

The limit to any compressor discharge temperature is 225˚F. If the discharge temperature gets higher than 225˚F, the system may start to fail from worn rings, acid formations, and oil breakdown. Remember, if the discharge temperature is 225˚F, the back of the actual discharge valve will be about 75˚F hotter. This will bring the actual compressor’s discharge valve to 300˚F. It is a known fact that most oil may start to break down and vaporize at 350˚F. If this occurs, serious overheating problems will occur. And, since compressor overheating problems are today’s most serious causes for compressor overheating, HVACR service technicians must always monitor compressor discharge temperatures and keep them under 225˚F.

Some main reasons for high compressor discharge temperatures are high-condensing pressures, low-suction pressures, high-compression ratios, and high-compressor superheats.

High-Condensing Pressures

Here are some causes for high-condensing pressures:

• Dirty condenser coils;

• Burned out condenser fan motor;

• Broken condenser fan belts;

• Undersized condenser coils;

• Overcharge of refrigerant;

• Non-condensables in the system;

• High ambient temperature;

• Recirculated air over the condenser; and

• Mixed or wrong refrigerant.

A high-condensing temperature causes a high-condensing pressure. Now the compressor must put in more work, thus generate more heat of compression, in compressing the suction pressure to the higher-condensing pressures.

Low-Suction Pressure

Here are some causes for low-suction pressure:

• TXV or capillary tubes underfeeding;

• Low evaporator heat loads;

• End of the cycle;

• Temperature set point set too low;

• Frosted evaporator coils;

• Defrost clock motor burned out;

• Defrost heater burned out causing iced coils;

• Inappropriate defrost schedules;

• Evaporator fan motor out;

• Kinked suction lines;

• Dirty or plugged suction line filter;

• Dirty or plugged liquid line filter/drier;

• Linked liquid lines; and

• Plugged compressor inlet screens .

Again, more work, thus more heat of compression will be generated in compressing a lower suction pressure to the condensing pressure.

High-Compression Ratios

High-compression ratios can be caused from either low-suction pressures or high-head pressures — or both. The higher the compression ratio, the higher the compressor’s discharge temperature will be. This happens because more heat of compression will be generated when compressing the gases through a greater pressure range.

High-Compressor Superheats

High-compressor superheats can be caused from the evaporator being starved of refrigerant. This can happen with a restricted liquid line, undercharge, plugged filter drier, kinked liquid line, or TXV or capillary tube underfeeding.

Conclusion

In conclusion, compressor discharge temperatures reflect:

• All of the latent heat absorbed in the evaporator;

• The evaporator superheat;

• Suction-line superheat;

• Heat of compression; and

• Motor heat generated by the compressor.

It is at the compressor’s superheated discharge temperature where all of this heat is accumulated and now must start to be rejected in the discharge line, condenser, and liquid line.

Publication date: 1/14/2013

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Recent Articles by John Tomczyk

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

Mini Split Installation

Twin Cities contractor Aabott Ferraro helped retrofit an older St. Paul home.

Podcasts

NEWSMakers: Jeff Nusz

Jeff Nusz, president, Reitmeier HVAC Services, Tualatin, Oregon, joins the program to discuss how he modernized his website and gained new clients and more money because of it. We’ll go through the process of the change and much more.  Posted on Aug. 1.

More Podcasts

ACHRNEWS

NEWS 07-28-14 cover

2014 July 28

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

Prohibiting HFCs

EPA is proposing a rule that would prohibit some HFCs in select refrigeration applications. Do you agree with this move?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con