Refrigeration / Refrigerants & Reclaim

Avoid Mixing Recovered Refrigerants

July 30, 2012
Trans

As the number and diversity of refrigerant products on the market continues to grow, the occurrence of refrigerant mixing or contamination becomes more likely. When more mixed refrigerant is returned to reclaimers, there is an increased burden of removing impurities or separating mixtures that can add to the cost of refrigerant reclaiming operations.

In many cases, the contamination of recovered refrigerant is avoidable if a few best practices are followed during service and recovery.

Out of Specification

Recovered refrigerant that is determined to be out of specification generally falls into one of two categories:

• Intentional mixing of two or more different refrigerants that are not supposed to be mixed together, resulting in a product that is not close to specification.

• Predominantly one refrigerant is contaminated with some amount of another refrigerant that makes it slightly out of specification.

In the case of the first category — intentional mixing — an obvious suggestion is to avoid mixing different types of refrigerant in the same recovery cylinder.

Unintentional mixing can certainly occur when systems or previously filled recovery cylinders are not labeled correctly.

It is practically impossible to identify a single component refrigerant or refrigerant blend by pressure alone, even though a check of the pressure of a refrigerant against the PT chart will give some clue to its possible identity. For example, a container may have a pressure similar to HCFC-22, but there are several retrofit blends that may also have a similar pressure. The exception might be HFC-410A, which should actually be pretty easy to identify based on the fact that its pressure is significantly higher than other refrigerants.

Not Sure?

If you are not sure of the identity of a refrigerant, put it into a clean, empty recovery cylinder. Do not combine an unknown refrigerant with previously recovered refrigerant that you know is not out of specification.

If a system is not labeled or reliable service records are not available to positively identify the refrigerant in question, then a sample of the refrigerant must be analyzed by a certified laboratory. Occupational Safety and Health Administration (OSHA) regulations require that containers of hazardous materials be labeled with their chemical name and Chemical Abstracts Service (CAS) number. In addition, the Department of Transportation prohibits the transportation of hazardous materials without proper identification of the contents of the cylinder as well as a green nonflammable gas label.

Since equipment owners are required to maintain records related to service or disposal of their HVACR equipment, and technicians or service companies are the source for this documentation, proper identification of cylinder contents are the key to compliance with these record keeping requirements.

Cross-Contamination

In the second instance, the one dealing with cross-contamination between types of refrigerants you encounter every day, the situation can be enough to throw a recovery tank out of spec. While it would be ideal to have refrigerant-specific dedicated hoses, gauges, and recovery equipment for each of the products you handle, that may not be practical. This makes it very important to properly purge, clean, or evacuate refrigerant tools every time they are used for a different product.

Now consider another example of how easy it is to contaminate refrigerant.

An air conditioner that is charged with 6 pounds of R-22 needs only 2 ounces of another refrigerant to be swept out of a contaminated hose to put it below 98 percent. It is entirely possible that a hose or gauge set could contain this much refrigerant if not purged properly after a R-410A job or a refrigeration service call that used another refrigerant. (See Table 1.)

Editor’s Note: The material was prepared by National Refrigerants Inc. and was based on information originally published in its newsletter, National News. For more information, go to www.refrigerants.com.

Sidebar: Best Recovery and Service Practices

Here are some of the most important recovery and service best practices.

• Use dedicated recovery equipment that is separate from normal service or charging equipment.

• Purge or evacuate hoses and gauges prior to using them with a different refrigerant. Use the purge cycle on recovery machines to remove residual refrigerant contained in the machine components. Hoses with low-loss fittings or valves can contain a considerable amount of liquid refrigerant. Make sure they are safely emptied.

• Evacuate all recovery cylinders to 29 inches Hg prior to recovering refrigerant into them. Immediately label cylinders with the type of recovered refrigerant and only use the cylinders for the labeled refrigerant.

• Use a filter-drier on the inlet of the recovery machine to reduce the moisture in the refrigerant and to keep contaminants from damaging the machine.

Paying attention to best recovery and service practices that are designed to avoid contamination can save you and your customers the hassle and expense of dealing with out-of-spec refrigerant after it has been returned to a reputable EPA-certified reclaimer.

Publication date: 7/30/2012

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-14-14 cover

2014 April 14

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con