Service & Maintenance / Extra Edition

The Case for Hard Start Kits

April 9, 2012
/ Print / Reprints /
ShareMore
/ Text Size+
hard start kitDuring my 50 years in the HVAC trade, I have found that most technicians do not spend time learning about the compressor and the a/c system as much as they should. In their defense, they are simply too busy to take the time once they are out of school.

Consider this: the compressor moves close to 1,000 pounds of refrigerant an hour when operating at a 50ºF evaporator saturation temperature. At a 45º saturation evaporator, it is near 800 pounds of refrigerant. The metering device moves the same amount of refrigerant in a liquid form that the compressor moves in a superheated form. Think of the work that takes place to move that much liquid and vapor gas. The compressor must receive a low pressure cold superheated gas at around 60º and move each molecule to a high pressure superheated gas to near 190º. Therefore, keeping the oil clean and void of moisture is a must. Allowing the compressor to operate in as little time as possible in the in-rush amperage mode is very important.

I recommend a start kit to accomplish a short start-up period. All of the high efficiency compressors that have expansion valve metering devices use start kits. The compressor must overcome the pressure difference at start up when the expansion valve is a positive shut-off valve. In my opinion, the start kit is an aftermarket item that should be offered to every client. The life of the compressor depends on it. I recommend a three-wire hard start kit the HVAC technician can carry, since he typically services most makes of air conditioning compressors.

And when using a start kit, the run capacitor needs to be addressed as well. If the run capacitor is weak, the start kit will start the compressor but will let it operate with higher amperage than designed. This will shorten the compressor’s life.

Another item in the circuit is the contactor. In an older system, the contactor could have pitted contacts. The pits could cause great harm to the compressor motor during the inrush period as well. The inrush amperage is near seven times the running amperage, placing it at times over 100 amps. The high amperage will cause a serious voltage drop that can only be found with an oscilloscope. Technicians do not carry one on the truck. When the pitting gets bad enough to cause a continuous voltage drop, permanent damage has already occurred. Just a visual check will show the pitting, and the tech should recommend a contactor change-out to prevent a continuous problem to the compressor windings.

Again, a start kit helps significantly cut the start-up period. A three-wire hard start kit in many cases will reduce the inrush period by 50 percent.

During this business cycle it is imperative that each technician keep a close eye on the company revenues. Profits are earned by professional technicians, and the more the technician understands about the science of the refrigeration system, the easier it is for the company to charge professional wages.

Keep all of your charges on a legitimate level and back them up with the science — not just an “I think you need to change this out” attitude.

Publication date: 04/09/2012

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-14-14 cover

2014 April 14

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con