Tune Up Your Cooling System Now

March 21, 2011
KEYWORDS maintenance / tuneup
/ Print / Reprints /
ShareMore
/ Text Size+

When the weather is warm outside, it’s imperative to make sure that your building’s mechanical cooling systems are working at maximum efficiency. Since budgets are still tight, nobody wants high energy costs or, worse, an equipment failure. Emergency maintenance is so much more expensive than routine maintenance. The best way to avoid either of these bad scenarios is to perform a cooling system tuneup.

Here’s a list of check points and values to get you started. A good place to start the tuneup is by listing some typical heating, ventilation, and air conditioning (HVAC) rules of thumb.

CHECKS BY EQUIPMENT TYPE

Since types of cooling equipment can vary widely, typical spring start-up checks are listed by equipment type, from water chillers to cooling towers, air handlers, and package cooling equipment (rooftops and heat pumps).

WATER CHILLERS

Note: Always review and follow manufacturer’s recommendations.

Electrical checks
• Use an insulation tester on oil pump motor and record readings.

• Use an insulation tester on compressor motor at the starter terminals; record readings.

• Measure and record oil pump voltage and amperage.

• Inspect the motor starter for signs of overheating, arcing, burns, etc.

• Clean starter cabinet.

• Inspect starter and starter components for discoloration, burns, moisture, etc.

• Inspect wires for discoloration and burns.

• Test accuracy of motor current (amp meter).

• Test tightness of terminal connections.

• Inspect contacts and change as necessary.

• Measure operating voltage and record.

• Check sensor readings for accuracy.

• Tighten terminal connections on the oil pump motor.

• Verify operation of the oil heater.

• Check starter contacts and change as necessary.

Oil and lubrication system
• Change oil and filter; test oil for acidity and check oil level.

• Clean purge drum and oil separator; change oil in purge pump and oil separator.

• Test oil again after start up for test lab analysis.

• Verify operation of oil cooling system if applicable.

• Clean oil strainer; change oil filter once per year.

• Analyze compressor oil.

• Check oil pump heater and purge oil heater operation.

Miscellaneous
• Leak test system at piping flange connections, exterior refrigerant lines, etc.

• Lubricate and check operation of purge unit.

• For centrifugals, inspect vane motor, shaft, fitting; lubricate inlet vane linkage.

• Check water strainers; clean if needed.

• Start unit; log operating conditions after unit stabilizes.

• Use thermography to check for heat losses and bad insulation.

• Check operation of variable speed drive.

• Check water flow in branch piping.

COOLING TOWERS

• Remove debris from in and around unit; flush as needed.

• Check and clean strainers, bleed, overflow, drain.

• Lubricate fan motor bearings per manufacturer’s recommendations.

• Change oil in gear reducer assembly per manufacturer’s recommendations.

• Check motor pulley, belts, motor mounts, and alignment. Replace or adjust as needed.

• Check motor operating conditions.

• Check operation of variable speed drive on tower fans.

• Inspect electrical connections, contactors, relays, operating/safety controls.

• Clean make-up float valve assembly; check for proper operation.

• Check operating conditions. Adjust as needed.

• Check temperature and flow sensors for accurate readings.

AIR HANDLERS

• Take pressure drop readings across filters; change when indicated.

• Check airflow with pitot tube or at flow measuring station.

• Check sensor readings at building control system. Calibrate if necessary.

• Check airflow at diffusers.

• Check indoor CO2 readings for indoor air quality and ventilation.

• Check economizer operation versus sequence of operation.

• Check and clean fan assembly.

• Lubricate fan bearings.

• Check belts and sheaves.

• Tighten all nuts and bolts.

• Check motor mounts and vibration pads.

• Check electrical conditions and motor operation.

• Lubricate and adjust associated dampers and linkage.

• Check fan operation.

• Clean outside air intake screen.

• Check and clean drains and drain pans.

• Check and clean strainers, steam traps, and hand valves.

• Inspect and clean filters, coils, and humidifiers.

• Clean external surfaces as needed.

• Measure and record voltage and current at fan motors.

PACKAGE COOLING EQUIPMENT (ROOFTOPS AND HEAT PUMPS)

• Check compressor evaporator and condenser pressures.

• Check operating voltage and current readings.

• Check filter pressure drop

• Check thermostat accuracy with recording meter and temperature sensor.

• Check fan operation.

• Check reversing valve operation for cooling switchover.

• Check airflow and static pressure.

Doing some of the checks listed above will definitely pay off. Now is a great time to take the initiative and save energy and reduce excessive downtime.

Sidebar: Typical HVAC Values

Note: Don’t assume that these are laws - they’re only typical values. Each specific HVAC system is different, and the values must be verified for each application.

Air movement: 6 air changes/hour

Ventilation rate: 25 cfm/person

Fan energy: 1,000 to 1,500 cfm/hp

Chiller size: 300 to 400 ft2/ton

Chilled water: 2.4 gpm/ton (10°F rise)

Condenser water: 3 gpm/ton (10°F rise)

Chiller input: 7 to .8 kW/ton

Chillers, pumps, and towers: 9 to 1.0 kW/ton

VAV: 55°F cooling, 10 percent box leakage flow, 40 to 50 percent minimum fan volume

People load: 450 Btu/person/hour

Sidebar: Common HVAC equations

Sensible air conditioning
Btuh = cfm x 60 min/hr x .075 lb/ft3 x .24 Btu/lb x DT

Btuh = 1.08 x cfm x DT

Latent air conditioning
Btuh = 60 min/hr x .075 lb/ft3 x cfm x DH

Btuh = 4.5 x cfm x DH

Water heating and cooling
Btuh = gpm x 60 min/hr x 8.33 lb/gal x 1 Btu/lb/°F x DT

Reprinted with permission from the Fluke Application Note “Tune up your cooling system now!” For more information, visit www.fluke.com.

Publication date: 03/21/2011

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Recent Articles by Ron Auvil

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 MCAA Annual Convention

Scenes from the 2014 MCAA Annual Convention in Scottsdale, Ariz.

Podcasts

NEWSmakers: Julian Scadden

Training is an ongoing process. Julian will discuss how you can generate maximum return on time and energy invested training by following a three part process. Listen to this podcast to get expert tips on training, tracking and follow up. 

More Podcasts

THE MAGAZINE

ACHRNEWS

NEWS 04-14-14 cover

2014 April 14

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

SERVICE CALLS POLL

Which statement on service calls best applies to your business?
View Results Poll Archive

HVACR INDUSTRY STORE

plumbing-hvac.gif
2014 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con