Ice Breaker: Evaporator Superheat Explained

June 1, 2009
/ Print / Reprints /
ShareMore
/ Text Size+

Generally the term “superheat” is used to describe the state of a refrigerant. Refrigerant in its vapor state is said to be superheated because it is at a temperature above its saturation (boiling point) temperature.

The degree at which a refrigerant is superheated is the temperature difference between its actual temperature and its saturation temperature. For example, if the saturation temperature of a refrigerant is 20°F and its actual temperature is 30°, then the refrigerant is said to be superheated by 10°. This could be also stated as “the refrigerant has 10° of superheat.”

In a properly operating system, the refrigerant will be in a superheated state from the last section of the evaporator to the first section of the condenser. Technicians can measure the superheat condition anywhere along this path. One common location is at the outlet of the evaporator. This is typically referred to as the “evaporator’s superheat.”

Measuring the evaporator’s superheat value is an important part of analyzing a system’s performance. If a lower than normal value is measured, too much refrigerant is entering the evaporator for the heat load. Many technicians refer to this as a “flooded evaporator.” If a higher than normal value is measured, too little refrigerant is entering the evaporator for the heat load. Technicians generally refer to this as a “starved evaporator.”

Part of effectively troubleshooting a refrigeration system should always include looking at the performance of the evaporator. This means measuring the evaporator’s superheat value. If this is overlooked, the true system problem can be misdiagnosed.

For example, a system with a lower than normal suction pressure can be the result of several problems, two of which are a low refrigerant charge and a lack of airflow across the evaporator. The difference between these two problems can be seen by looking at the evaporator’s superheat. A low refrigerant charge will have a higher than normal evaporator superheat value. Lack of airflow across the evaporator will cause the evaporator’s superheat to be lower than normal.

PROCEDURE

Below is a procedure for calculating an evaporator’s superheat value:

1. First, measure the pressure of the refrigerant at the outlet of the evaporator. If this is not possible, measure the pressure at the next closest location (usually at the inlet of the compressor) and then estimate the pressure at the outlet of the evaporator by estimating the pressure drop from the measured location to the outlet of the evaporator. For many systems, a 2-psig pressure drop can be assumed from the outlet of the evaporator to the inlet of the compressor.

2. Next, convert the measured pressure to its saturation temperature using a pressure-temperature chart.

3. Then, measure the temperature of the refrigerant at the outlet of the evaporator. This is done by measuring the refrigerant line temperature, which is assumed to be the same as the refrigerant passing through.

4. Finally, subtract the measured refrigerant temperature from the converted saturation temperature. The difference is the superheat value of the refrigerant.

AN EXAMPLE

For example, let’s calculate the evaporator superheat for a walk-in cooler using HFC-134a refrigerant.

1. First, we measured a pressure of 18-psig at the inlet of the compressor (there are no valves at the outlet for the evaporator). Assuming a 2-psig pressure drop across the suction line, we have a 20-psig pressure at the outlet of the evaporator.

2. Next, using a pressure-temperature chart, we determine the saturation temperature to be 22°.

3. Then, we measure a line temperature of 30°.

4. Finally, we subtract 30° from 22°, for a superheat value of 8°.

What is the correct superheat value of the refrigerant leaving an evaporator? It is based on the system’s application and the manufacturer’s design. As a rule of thumb, medium-temperature systems will generally have a superheat of 8° to 10° and low-temperature applications 4° to 6°. But again, always check with the system’s manufacturer for the recommended values.

Technicians should include measuring the evaporator superheat when diagnosing a system problem. Failing to include this measurement can lead to misdiagnosing the true system problem.

Publication date: 06/01/2009

Did you enjoy this article? Click here to subscribe to The NEWS Magazine

Recent Articles by Joe Marchese

You must login or register in order to post a comment.

Multimedia

Videos

Image Galleries

2014 World Energy Engineering Congress

Scenes from the 2014 World Energy Engineering Congress in Washington, D.C.

Podcasts

NEWSMakers: Jim Johnson

Jim Johnson,an experienced trade school and community college instructor, discusses the HVAC industry and his column in The NEWS, ‘The Service Ticket.’ Listen now for a hint to the Not Enough Heat question from the Dec. 15 issue. Posted Jan. 30.

More Podcasts

ACHRNEWS

NEWS 01-26-15 cover

2015 January 26

Check out the weekly edition of The NEWS today!

Table Of Contents Subscribe

Regional Standards

With regional standards for a/c equipment going into effect in 2015, how do you think it will impact the industry?
View Results Poll Archive

HVACR INDUSTRY STORE

2015.jpg
2015 National Plumbing & HVAC Estimator

Every plumbing and HVAC estimator can use the cost estimates in this practical manual!

More Products

Clear Seas Research

 

Clear Seas ResearchWith access to over one million professionals and more than 60 industry-specific publications, Clear Seas Research offers relevant insights from those who know your industry best. Let us customize a market research solution that exceeds your marketing goals.

DON'T MISS A THING

Magazine image
 
Register today for complete access to ACHRNews.com. Get full access to the latest features, Extra Edition, and more.

STAY CONNECTED

facebook icontwitter iconyoutube iconLinkedIn i con